Crest Audio FBN0751 Скачать руководство пользователя страница 22

1  

Service

        

                       Service Manual

22

HWG Rate Limiting

This parameter determines the maximum rate to be used when 
heating a HWG tank.  This setting may be used when the tank 
is unable to accept all of the BTU’s available from the boiler.  
This parameter may be adjusted by the installer by accessing 
parameter 

F10

HWG Type

This parameter gives the installer a choice of piping the Hot 
Water Generator (HWG) directly to the boiler, or as a zone in 
the heating system.  This parameter can be adjusted through 
parameter 

F11

.  For direct HWG select 

Normal

, for treating the 

HWG as a zone, select 

Zone

HWG System Pump Mode (Type Zone Only)

This parameter allows the installer to determine how the system 
pump responds to a HWG call for heat.  The parameter can be 
adjusted through parameter 

F12

.  Select 

Always Off

 if you want 

the system pump to always turn off during a HWG call for heat.  
Select 

Always On

 if you want the system pump to always turn 

on during a HWG call for heat.  Select 

Normal

 if you want the 

system pump to ignore the HWG call for heat and operate based 
on the System Pump Mode setting only.

Service Mode Timeout

The Service Mode allows the installer to set the unit to any firing 
rate for the purpose of combustion analysis.  The delay sets the 
length of time the boiler will stay in the Service Mode if no keys 
have been pressed before going back to its original state.  This 
parameter can only be changed by the installer by accessing 
parameter 

F11

Controlling Sensor

The SH controlling sensor parameter selects the sensor the 
control will use to regulate the boiler firing rate.  This parameter 
is adjustable by the installer by accessing parameter 

F12

. The 

sensor selections are as follows:  The outlet sensor regulates the 
firing rate based on the outlet water temperature of the boiler 
and the inlet sensor regulates the firing rate based on the inlet 
water temperature of the boiler.  If the outlet sensor is selected, 
and the optional system supply sensor is connected, the control 
will regulate the firing rate based on the system supply sensor 
temperature.  If the inlet sensor is selected, and the optional 
system return sensor is installed, the control will regulate the 
firing rate based on the system return temperature.  

Inlet Control Time Delay

When the inlet sensor is selected as the controlling sensor, the 
SMART TOUCH control will start by controlling the outlet/
system supply temperature to the SH set point.  After a time 
delay, the control will start to increase and regulate the system 
supply temperature in order to maintain the inlet/system return 
temperature to the SH set point.  This time delay should be long 
enough for the heated water to work its way through the system 
loop and be measured by the inlet/system return sensor.  This 
time delay is adjustable by the installer by accessing parameter 

F13

.

Freeze Protection Burner On

If running the pumps does not prevent the inlet 
temperature from falling closer to freezing, the SMART 
TOUCH control will fire the burner at low fire if in the ON 
state.  The installer can adjust the temperature at which the 
burner fires by adjusting parameter 

F4

Freeze Protection Burner Differential

Once the burner has started firing due to a low inlet 
temperature, the inlet temperature must increase by this 
amount before the burner turns back off.  The installer can 
adjust this differential by accessing parameter 

F5

HWG/SH Switching Time

When a boiler has a HWG demand and it receives a space 
heating demand, the SMART TOUCH control will start 
a timer.  Once the timer expires, it will stop the HWG 
demand and service the space heating demand.  This 
feature does not apply when the HWG is programmed as a 
zone, or in Cascade. The installer can adjust the length of 
time the boiler will service the HWG demand by accessing 
parameter 

F6

SH/HWG Switching Time

When a boiler has a space heating demand and it receives 
a HWG demand, it will immediately switch to the HWG 
demand and start a timer.  Once the timer has expired, the 
boiler will switch back to the space heating demand and 
start another timer.  Once this timer expires, it will switch 
back to the HWG demand.  This feature does not apply 
when the HWG is programmed as a zone, or in Cascade. 
The installer can adjust the length of time the boiler will 
service the space heating demand by accessing parameter 

F7

.  

Anti-Cycling Time

Once a SH demand has been satisfied, a set amount of time 
must elapse before the control will respond to a new SH 
demand.  The control will block the new heat demand and 
anti-cycling will be shown in the display until the time has 
elapsed or the water temperature drops below parameter 
F9.  This parameter can be changed by the installer by 
accessing parameter 

F8

Anti-Cycling Differential

The control will bypass the anti-cycling time if the inlet 
water temperature drops too much.  The control will use 
the inlet water temperature at the time the boiler shut off 
as the starting point.  If the inlet temperature drops below 
this temperature parameter the control will abort anti-
cycling and allow the boiler to fire.  This parameter can be 
changed by the installer by accessing parameter 

F9

Содержание FBN0751

Страница 1: ...hnician Read all instructions including this manual and the Crest Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe personal...

Страница 2: ...ted to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing boiler 4 Boiler operation 4 Boiler water 4 F...

Страница 3: ...ca in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cr...

Страница 4: ...ve sediment The high efficiency heat exchanger can be damaged by build up or corrosion due to sediment Do not use petroleum based cleaning or sealing compounds in the boiler system Gaskets and seals i...

Страница 5: ...ation Crest boiler operation Initial Setup Set Points Outdoor Reset Ramp Delay BMS Advanced Setup SH Night Setback HWG Night Setback ModBus Cascade Pumps Service Notification Maintenance Service and m...

Страница 6: ...W CHECK VALVE TYPICAL Y STRAINER RECOMMENDED RELIEF VALVE BALL VALVE TYPICAL AIR SEPERATOR DRAIN PORT TYPICAL SYSTEM CIRCULATOR BACK FLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TAN...

Страница 7: ...e information regarding this screen Main Menu button Pressing this button brings up the Main Menu Screen From this screen navigation to nine 9 other screens is possible Modulation button Pressing this...

Страница 8: ...T TEMPERATURE HI LIMIT SENSOR FLUE GAS SENSOR LOUVER PROVING SWITCH FLAME SENSOR 1 2 LOW WATER CUTOFF BLOCKED DRAIN SWITCH DISPLAY PANEL PC INTERFACE SMART CONTROL MODULE AIR PRESSURE SWITCH SYSTEM SE...

Страница 9: ...ENT SYSTEM BOILER PUMP CONTACTOR SYSTEM PUMP CONTACTOR HWG PUMP CONTACTOR IGNITOR BLOWER GAS VALVES BOILER RATE OUTPUT DISPLAY PANEL PC INTERFACE 120V SUPPLY SYSTEM PUMP BOILER PUMP DHW PUMP MAX 1 5 A...

Страница 10: ...y adjusting control parameters These parameters set operating temperatures and boiler operating modes Sequence of operation Table 1A page 12 shows control module normal sequences of operation for spac...

Страница 11: ...reen To adjust the setting use the buttons to the left and right of the current setting Note If the above mentioned buttons to adjust settings do not appear the correct PASSWORD has not been entered P...

Страница 12: ...he blower speed constant for a few seconds to allow the flame to stabilize then begin modulating the firing rate in order to maintain the controlling sensor to the desired set point temperature 9 If t...

Страница 13: ...Pump Mode 25 N A N A N A No Yes B 1 SH Min User Setpoint 18 32 185 32 No Yes 2 SH Max User Setpoint 18 32 185 185 No Yes 3 SH Setpoint 18 32 185 125 Yes Yes 4 SH Offset 18 0 36 9 9 No Yes 5 SH Differe...

Страница 14: ...y Limit 1 20 10 100 20 No Yes 9 Ramp Delay Limit 2 20 10 100 30 No Yes 10 Ramp Delay Limit 3 20 10 100 40 No Yes 11 Ramp Delay Limit 4 20 10 100 55 No Yes 12 Ramp Delay Limit 5 20 10 100 75 No Yes 13...

Страница 15: ...0 40 40 No Yes 14 Controlling Sensor 22 0 4 2 No Yes 15 Inlet Control Time Delay 22 0 40 3 No Yes 16 Modulation Factor 23 40 100 100 No Yes 17 Min Boiler Rate 23 4 100 100 No Yes 18 Freeze Protection...

Страница 16: ...Night Setback Fri Begin 23 N A N A N A No Yes 12 HWG Night Setback Sat End 23 N A N A N A No Yes 13 HWG Night Setback Sat Begin 23 N A N A N A No Yes 14 HWG Night Setback Sun End 23 N A N A N A No Yes...

Страница 17: ...0 33 No Yes 3 Boiler Pump Mode 25 1 3 2 No Yes 4 System Pump Mode 25 1 5 2 No Yes 5 System Pump Delay 25 0 5 2400 30 No Yes 6 System Pump Anti Seize Time 25 0 40 0 33 No Yes 7 HWG Pump Delay 25 0 5 2...

Страница 18: ...G Tank Set Point By installing a tank sensor the SMART TOUCH control can perform the tank thermostat function The SMART TOUCH control automatically detects the presence of this sensor and generates a...

Страница 19: ...ing see FIG 1 6 However if the user set point is set lower the water temperature will be limited by the user set point instead This parameter can be changed by accessing parameter C1 SH Set Point at H...

Страница 20: ...d Once the SH demand has been satisfied the set point will revert back to its calculated setting The boost temperature can be changed by the installer by accessing parameter C8 Shift OA Reset Curve Th...

Страница 21: ...m parameter E7 is set by parameter E9 21 BMS Set Point at Maximum Volts When programmed for BMS control through the 0 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT the set...

Страница 22: ...to increase and regulate the system supply temperature in order to maintain the inlet system return temperature to the SH set point This time delay should be long enough for the heated water to work...

Страница 23: ...ncy Optimization This method is used when it is desired to have the most efficient system When the first boiler reaches a certain rate default 80 it lowers its rate to 40 and turns on the next boiler...

Страница 24: ...to reduce the risk of temperature overshoot with a Cascade this parameter defines the minimum time delay from starting one unit until the next unit may be started The installer can adjust this time d...

Страница 25: ...minder Screen at that time This can be programmed by accessing parameters L4 and L5 When selected another menu will appear with PHONE and NAME Note that the phone number is limited to 10 characters an...

Страница 26: ...The level of the indicator will rise and fall indicating the approximate power level of the boiler The display box above each power level will display the following 100 A percentage indicates that fir...

Страница 27: ...e selected by highlighting the parameter and pressing the SELECT button A maximum of five 5 items can be graphed at one time Figure 1 9 Graph Screen_Parameter Selection Graph Screen Figure 1 10 Graph...

Страница 28: ...st ten 10 lockout faults Preceded by each fault is the date and time of when the fault occurred The lockout faults can be reset by pressing the RESET FAULTS button Figure 1 11 History Screen_Lockout F...

Страница 29: ...mpted to ignite since the last reset Successful Ignition attempts Shows the number of times the control has successfully ignited since the last reset Total Power hours Show the total number of hours t...

Страница 30: ...essed the integrated control will automatically revert back to its original status after the Remaining time in Service counter expires Once the boiler has been placed into Service Mode it will light a...

Страница 31: ...and performance verification per Section 9 of the Crest Installation and Operation Manual Flame inspection stable uniform Check both flame signals at least 10 microamps at high fire Test low water cu...

Страница 32: ...ws securing the top cover to the condensate trap and remove the cover FIG 2 1 2 Locate the plastic ball inside the float tube Verify there is nothing under the ball causing it to not seat properly 3 F...

Страница 33: ...e sense electrodes making sure the gaskets are in good condition and correctly positioned Check ignition ground wiring 1 Inspect boiler ground wire from the heat exchanger access cover to ground termi...

Страница 34: ...thepropershutdownprocedure and to schedule an annual start up at the beginning of the next heating season NOTICE The burner gasket burner burner baffle and gas air manifold access cover can only be in...

Страница 35: ...n firing 3 Remove the top access panel to remove the gas air manifold assembly 4 Remove the nuts securing the burner to the burner mounting plate Remove the burner reference FIG 2 2 and follow the ste...

Страница 36: ...on the outlet piping of the boiler see FIG 2 3 This will begin to restrict the flow and simulate a low flow condition 6 While slowly shutting off the isolation valve refer to the Status Screen to watc...

Страница 37: ...oiler startup Check control module fuses ALWAYS check control module fuses before replacing control module or any major components blower etc If one of these fuses is blown it can prevent the control...

Страница 38: ...this manual No Burner Operation Main control board temperature set point satisfied Review temperature setting Remote thermostat satisfied Review remote thermostat setting Outside air temperature abov...

Страница 39: ...tant to note that the flue inlet air pre mix and outlet water sensors each have two temperature sensing devices in one housing These devices are designated as S1 S9 outlet sensor S3 S1 flue sensor and...

Страница 40: ...ner Refer to page 34 in this manual for the burner removal and inspection procedure Clean or replace the burner as necessary Air in the piping system Properly purge all air from the piping system No P...

Страница 41: ...a manual reset once condition has been corrected Press the RESET button on the SMART TOUCH display to reset The blocked drain switch has detected excessive condensate build up inside the unit Check c...

Страница 42: ...1 0 3 5 kPa Refer to Section 6 Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply Verify that the plastic hose from gas valve 1 to the ai...

Страница 43: ...nual for removal and cleaning procedures Replace if necessary Flame Failure 2 Running will require a manual reset once the condition has been corrected Press the RESET button on the SMART TOUCH displa...

Страница 44: ...Auto Reset High Limit The outlet water temperature has exceeded the setting of the automatic reset high limit Verify that the system is full of water and that all air has been properly purged from the...

Страница 45: ...er pump motor on a call for heat If voltage is not present check wiring back to the main control board Replace the pump relay if necessary If 120 vac is present on a call for heat and the boiler pump...

Страница 46: ...nspect the flue sensor and associated wiring Measure the resistance of the flue sensor and compare to Table 3E on page 39 of this manual Replace the sensor if necessary Verify that the vent air intake...

Страница 47: ...e RESET button on the SMART TOUCH display to reset After downloading parameters from a laptop the main control board must be reset Press the RESET button on the SMART TOUCH display panel Sensor Open w...

Страница 48: ...the flue side of the heat exchanger Inspect the flue sensor and associated wiring Measure the resistance of the flue sensor and compare to Table 3E on page 39 of this manual Replace the sensor if nec...

Страница 49: ...e main control board Wrong Error Code The main control board has detected an internal fault Press the RESET button on the SMART TOUCH display panel Flame Sense Out of Sequence 1 will require a manual...

Страница 50: ...metering valve Replace the air metering valve Replace the control board Check the slide switch on the inside of the air metering valve actuator Air Metering Valve Stuck Open will require a manual res...

Страница 51: ...ctions between the outlet temperature sensors and the control board Make sure all connections are dry and secure Check the resistance of the two outlet sensors see page 39 Replace the control board Fl...

Страница 52: ...ke methods for the Crest boiler Check for obstructions at the vent air intake terminals Gas Supply Pressure Refer to Section 6 Gas Connections of the Crest Installation and Operation Manual for the pr...

Страница 53: ...crease CO2 levels After one adjustment on the valve follow the Combustion Analysis Procedure on page 52 of this manual to measure the combustion If combustion is still not within the specified range r...

Страница 54: ...3 Troubleshooting 54 NOTES...

Страница 55: ...3 Troubleshooting 55 NOTES...

Страница 56: ...Revision Notes Revision A ECO C17106 initial release Revision B ECO C17419 reflects the addition of the large Crest models 1501 2001 FBII SER Rev B 03 15...

Отзывы: