Failure

Probable Cause

Fix

1. 

Pans do not fit perfectly in trans

-

port angles

1a. Misalignment

1a. Add or remove shim kit.

2. Power light off, cabinet does 

nothing

2a. Battery not charged.

2a. Charge battery.

3. Thermometer value is flashing.

3a. Cabinet is outside normal temperature. 3a. Allow cabinet to come to temp.

Cabinet is Not Cooling:

Failure

Probable Cause

Fix

1. Compressor not operating.

1a. Sensor issue.

1a. Fix or replace.

1b. Wiring issue.

1b. Fix or replace.

1c. Compressor overheated.

1c. Wait to cool.

1d. Component failure.

1d. Replace.

2. Evaporator fans not operating.

2a. Door open.

2a. Close door.

2b. Wiring issue.

2b. Fix or replace.

2c. Door switch failure.

2c. Fix or replace.

2d. Evaporator fan failure.

2d. Replace.

3. Condenser fan not operating.

3a. Wiring issue.

3a. Fix or replace.

3b. Condenser fan failure.

3b. Replace.

4. Refrigerant loss.

4a. Leak.

4a. Check system for leaks, recharge.

TROUBLE-SHOOTING GUIDE

Unit Condition:

Unit is plugged in. Switch is 

ON

.

NOTES: 

1. For replacement of the electrical parts, refer to our list of authorized service centers (FL-1400). 

MAINTENANCE INSTRUCTIONS

TROUBLE-SHOOTING GUIDE

Содержание KC-UA-11

Страница 1: ...9 Call Toll free 877 CRES COR 273 7267 Fax 800 822 0393 www crescor com Cabinet model number Cabinet serial number Authorized Service Agency Ph Fax Keep this manual for future reference KC UA 11 KC UA...

Страница 2: ...COR PART USING A DIFFERENT BATTERY CHARGER VOIDS WARRANTY AND COULD DAMAGE EQUIPMENT OR CREATE A POTENTIALLY HAZARDOUS SITUATION FIRST TIME OPERATION 1 Keep unit plugged into wall receptacle charging...

Страница 3: ...2 5 Hours KCUA11H Cabinet ON 10 Hours Cabinet OFF 4 5 Hours 3 For longest battery life it is recommended to not let the battery charge go below 10 It is OK to leave unit plugged in after it has reache...

Страница 4: ...oid scratching the surface 3 Use only a soft cloth sponge fibrous brushes plastic or stainless steel pads for cleaning and scouring 4 Rinse thoroughly with fresh water after every cleaning operation 5...

Страница 5: ...ck side or top Damage to the refrigerant and battery systems could result causing a potentially dangerous situation TECHNICAL SPECIFICATIONS Configuration Refrigerant Type Charge Size oz Example Opera...

Страница 6: ...1 Compressor not operating 1a Sensor issue 1a Fix or replace 1b Wiring issue 1b Fix or replace 1c Compressor overheated 1c Wait to cool 1d Component failure 1d Replace 2 Evaporator fans not operating...

Страница 7: ...341 B 0569 341 B 14 Hinge kit 0519 110 K 0519 110 K 15 Door assembly 1221 685 IN 1221 685 IN 16 Door gasket 0861 300 0861 300 REPLACEMENT PARTS Include all information on nameplate when ordering parts...

Страница 8: ...6 075 1416 075 24 Service Tee 1109 038 1109 038 25 Drier 0858 008 0858 008 26 Drain tube 0913 148 0913 148 27 Battery ea 7037 016 7037 016 Description KCUA11 KCUA11H 28 Evaporator fan ea 0769 221 0769...

Страница 9: ...9 12 11 36 37 35 14 30 17 28 6 24 34 26 25 27 28 29 2 2 1 39 38 41 40 1 3 5 29 22 23 32 39 38 41 40 43 43 42 42 87 87a 85 86 30 87 87a 85 86 30 87 87a 85 86 30 11 T P C D I F LOAD AND CHARGER BATTERY...

Отзывы: