STEP 1

•  Mount the supplied 2W-ITS (2 wire illuminated test 

switch) in a location that is visible and accessible by 

maintenance personnel. 

•  The 2W-ITS mounts through a ½” hole in the ceiling next 

to the luminaire or on the wall with the provided test 

switch plate. See

 Figure 3.

STEP 2

•  Wire the test switch per E

lectrical Connections Section 

on the last page. 

•  If wired correctly, the 2W-ITS indicator light should be ON 

when AC power is supplied to the luminaire, indicating 

that the emergency inverter battery is charging. 

After installing, mark with the “PUSH TO TEST” and 

“CHARGING INDICATOR LIGHT” labels.

•  For Mounting Height: Refer to below table.

TEST SWITCH MOUNTING

3

Model #

S-DL4-EB

S-DL6-EB

S-DL8-EB

Wattage

-11L
-15L
-24L
-34L

Max mounting Height 
36.1 ft (11 m)
41.2 ft (12.5 m)
37.2 ft (11.3 m)
40.67 ft (12.4)

Wattage

-42L
-50L
-63L
-75L

Max mounting Height 

Wattage

-84L

Max mounting Height 

40.2 ft (12.2 m)
31.6 ft (9.6 m)
34.5 ft (10.5 m )
32.4 ft (9.8 m)

34.8 ft (10.6 m)

TRIM INSTALLATION

4

STEP 1

•  Remove plastic bag and cable tie prior to installation.

STEP 2

•  Connect the reflector to the light engine by aligning the key hole slots 

of the reflector with the retained screws of the light engine and rotate 

in to place. See 

Figure 4 and 5.

STEP 3

•  Push up until the reflector flange is tight against the ceiling and 

tighten the retained screws to 20 in-lb torque. 

STEP 4

•  Attach the inner optic by aligning the notches in the inner optic with 

the tabs on the light engine. Rotate inner optic in a clockwise direction 

to lock it in place. See 

Figure 4 and 6.

6

5

Luminaire

Charging Indicator 

Light/Test Switch

Wall Plate

Wall or Ceiling

Flexible Conduit

Switch Box

(Wiring Box)

LED Engine

(2) Key Holes

Reflector

Inner Optic

Screws

(2) Key Holes

Reflector

Inner Optic

Отзывы: