Mounting the Control Panel

1.

Determine mounting location for panel. If distance exceeds
the length of either the float switch cables or the pump power
cables, splicing will be required. For outdoor or wet instal-
lation, we recommend the use of a liquid-tight junction box
with liquid-tight connectors to make required connections.

You must use conduit sealant to prevent moisture or
gases from entering the panel.

2.

Mount control panel with mounting devices furnished.

3.

Determine conduit entrance locations on control panel.

NOTE:

 Be sure the incoming power, voltage, amperage,

and phase meet the requirements of the pump motor being
installed. If in doubt, see the pump identification plate for
electrical requirements.

4.

Drill proper size holes for type of connectors being used.

NOTE:

 If using conduit, be sure that it is of adequate size

to pull the pump and switch cables through.

5.

Attach cable connectors and/or conduit connectors to con-
trol panel.

FOR INSTALLATION REQUIRING

A SPLICE, FOLLOW STEPS 6-9;

FOR INSTALLATION WITHOUT A SPLICE,

GO TO STEP 10.

Installation Instructions

6.

Determine location for mounting junction box according to
state and local code requirements. Mount junction box to
proper support.

7.

Run conduit to junction box. Drill proper size holes for the
type of conduit used. Attach connectors to junction box.

8.

Identify and label each wire before pulling through conduit
into control panel and junction box. Make wire splice con-
nections at junction box.

9.

Firmly tighten all fittings on junction box.

10.

  If a junction box is not required, pull cables through conduit

into control panel.

11.

Set motor protective switch:
a) set the dial to match motor full load amps
b) turn dial on motor protective switch to the ON position

NOTE:

 Resetting the dial with power applied to the motor

protective switch could start the motor.

12.

  Connect pump wires directly to the motor contactor terminal

positions T1, T2, and T3.

NOTE:

 Three phase motors will run in either direction. Check

pump motor before installation for proper rotation. To cor-
rect rotation, change pump cable connections on any two
terminals T1-T2-T3.

13.

  Connect “power-in” conductors to proper locations: 208/

240/480 on 3 position terminal block. 

Install tagged fac-

tory wire to appropriate transformer primary voltage tap.

VERIFY CORRECT OPERATION OF CONTROL PANEL

AFTER INSTALLATION IS COMPLETE.

FIGURE 1 - Three float simplex -
pump down installation

FIGURE 2 - Mounting clamp
detail

FIGURE 3 - Internally weighted float

7"

suspended cable

approximate

 activation level

FIGURE 4 - Float with cable weight

3.5 inch (9 cm)

tether length

Содержание Three Phase Simplex

Страница 1: ...erly WARNING Turn off all power before installing floats in pump cham ber Failure to do so could result in serious or fatal electrical shock 1 Use float label kit to identify and label cables on both the float and stripped ends stop start alarm etc See schematic for float op tions 2 Determine your normal operating level as illustrated in Figure 1 3 Mount float switches as illustrated in Figures 2 ...

Страница 2: ...ode requirements Mount junction box to proper support 7 Run conduit to junction box Drill proper size holes for the type of conduit used Attach connectors to junction box 8 Identify and label each wire before pulling through conduit into control panel and junction box Make wire splice con nections at junction box 9 Firmly tighten all fittings on junction box 10 If a junction box is not required pu...

Страница 3: ...sent Normally closed Contacts are closed under normal con ditions and open when alarm condition is present Both types automatically reset once alarm condition is cleared Seal Failure Circuit and Indicator Light Optional The seal fail circuit has resistance sensitivity and will sense the presence of water in the pump seal chamber Upon in stallation turn the sensitivity dial on the seal fail module ...

Страница 4: ...he float in the ON position the scale should read nearly zero very low resistance Replace the float if you do not get this reading NOTE Readings may vary depending on the length of wire and accuracy of the measuring device Troubleshooting CRANE PUMPS SYSTEMS INC warrants to the original con sumer that this product shall be free of manufacturing defects for three years after the date of consumer pu...

Отзывы: