background image

TECHNICAL BULLETIN

Part #: 026-4212  Revision 0  Date: 10/17/2006

COMPUTER PROCESS CONTROLS - http://www.cpcus.com/

Page 1

Ethernet Gateway Board Installation Instructions

Overview

The Ethernet Gateway Board (

CPC P/N 537-3094

) provides a hardware platform that can be used 

to communicate with RS485 or RS232 devices through an Ethernet connection. The Ethernet 
Gateway Board can be used in various applications, such as providing a web or HHT-accessible 
interface to CPC I/O Network devices (such as the MultiFlex).

Mounting

The Ethernet Gateway Board is typically 
installed near the devices it will be commu-
nicating with. The board is designed to fit 
in a standard 4” snap-track or it may be 
mounted in a panel or against a wall using 
stand-offs. Follow the dimensions in 

Fig-

ure 1

 for panel mounting. Leave at least 2 

inches of clearance on the left side of the 
board to allow room for the Ethernet and 
RS232 connections.

The Ethernet Gateway Board must be 
mounted in an environment with ambient temperature between -40°F and 150°F with a non-con-
densing humidity between 5% and 95%.

Powering

The Ethernet Gateway Board requires 24VAC power from a Class 2 

center-tapped

 transformer. 

CPC supplies several sizes of center-tapped transformers for powering multiple 16AIs, 8ROs, and 
other RS485 peripheral boards of the E2, Einstein, and REFLECS systems.

Figure 2

 shows how to connect the 56VA and 

80VA transformers to the Ethernet Gateway Board 
power connector.

Three-Board

Six-Board

P/N

640-0056

640-0080

Power Rating

56 VA

80 VA

Table 1-US and Canada Power Ratings for 

CPC Transformers

Figure 1 - Ethernet Gateway Board Diagram

Figure 2 - Power Transformer Wiring