Overview 

It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time 

to guarantee lamp life (refer to the manufacturer’s datasheet for details) As this EBDHS-DD-LT30 is able to dim the 

lamps using DALI/DSI, the product provides a facility to disable this for a given period of time. 

Operation 

By setting the “Burn in” parameter, you can select a time during which the lamps are not allowed to deviate from 

maximum output. The unit counts the time, and even remembers how long has elapsed in the event of a power failure. 

To cancel the burn in function, simply select a time of 0. Note that when the lamps are changed, the burn in time should 

be set again. 

Burn-in 

The EBDHS-DD-LT30 is designed to be mounted using either: 

 

Flush fixing, or 

 

Surface fixing, using the optional Surface Mounting Box (part no. DBB). 

Both methods are illustrated below. 

Use the supplied gasket to ensure IP rating 

(not compatible with Surface Mounting Box part no. DBB).

 

Assembly 

Remove connector 
cover 

Push-in sensor 
head connector to 
mating socket on 
power supply unit. 
Locate sensor head 
onto power supply 
and clockwise rotate 
until locked. 

The EBDHS-DD-LT30 
may be supplied in two 
parts. Follow the 
instructions to 
assemble. 

Installation 

Flush Fixing 

Surface Fixing 

Hole Ø64mm 

Warning - be careful 
bending springs when 
mounting unit. 

Pull out spring tab and rotate 
spring arm as shown 

50mm or 60mm fixing centres 

Important 

Ensure that the cables are formed as shown 
before affixing the cable clamp. The clamp 
MUST clamp the outer sheath(s) only. 
 
Bend cores as shown. 

Wire stripping details 

Содержание EBDHS-DD-LT30

Страница 1: ...n controls All functionality is fully programmable using an IR handset Features Front features Back features Ceiling PIR HS presence detector DALI DSI low temperature EBDHS DD LT30 Product Guide Mounting Bezel Sensor Lens which covers PIR Sensor IR Receiver Light Level Sensor Status LEDs Retaining Spring Retaining Spring Power Input Switched Output Connector Channel 1 Dimmable Control Output Conne...

Страница 2: ...15m 30m 10m 20m 6m 12m 3m 8m Height Range Diameter 15m 40m 10m 26m 6m 16m 3m 9m Alignment marks The sensor head has 4 alignment marks These correspond to the 4 outer passive infrared sensors under the lens Use these marks to align with aisles and corridors to ensure the best detection characteristics See example overleaf ...

Страница 3: ...attern for narrowing the detection diameter Lateral tear pattern for making a slot style detection shape Applications Aisles Masking shields trimmed for aisle shaped detection Narrow detection Masking shields trimmed for a narrow beam of detection 1 2 3 4 4 3 2 1 Slot number Masking shield coverage 1 45 2 32 3 22 4 11 Slot number 2 3 4 Diameter number Masking shield coverage 1 89 2 63 3 45 4 32 5 ...

Страница 4: ... ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level maintained illuminance Sensor functionality The UNLCDHS has the ability to read back the settings stored in a device To read back individual parameters N...

Страница 5: ...n in The EBDHS DD LT30 is designed to be mounted using either Flush fixing or Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Use the supplied gasket to ensure IP rating not compatible with Surface Mounting Box part no DBB Assembly Remove connector cover 1 2 Push in sensor head connector to mating socket on power supply unit Locate sensor head ...

Страница 6: ...tch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel mode Set to Switch and dim together S...

Страница 7: ...Set to 1 position switch separate Functions Switches both channels with occupancy Maintains illuminance dims and switches the dimming channel using optional centre biased retractive switch Configured to presence detection Turns on automatically with occupancy Maintains illuminance dimming channel only Press and release down switch to turn off Press and release up switch to turn back on Press and h...

Страница 8: ...ger than the Time Out Period Ensure that the sensor is not adjacent to circulating air heaters or lamps Fault finding Functions Switches channel 1 only with occupancy optional override switch No dimming output Configured to presence detection Turns on automatically with occupancy Press and release down switch to turn off Press and release up switch to turn back on Turns off after occupancy Configu...

Страница 9: ...n Sets the ballast control protocol to be used by the output channel Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Burn in 0 0 50 100 Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Absence Presence...

Страница 10: ...e or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will always power up detecting Disable Detector N Y or N Disables detection leaving the relay output permanently off with t...

Страница 11: ...ights from being turned on by movement Light Level maintained illuminance 600 1 to 998 999 disabled Sets a target light level to be maintained by the lighting system Load Type DALI DSI DALI DALI On Sets the ballast control protocol to DSI Sets the ballast control protocol to DALI DALI On provides a permanent voltage to DALI ballasts when DALI has not been implemented correctly in the ballast Maxim...

Страница 12: ...as if mains potential Use mains rated wiring Terminal Capacity 2 5mm2 Temperature 30ºC to 35ºC Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating 40 without gasket 65 with gasket Compliance EMC 2004 108 EC LVD 2006 95 EC Technical data Part numbers C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333...

Отзывы: