LOAD
16 Amp resistive heating
Not suitable for controlling quartz heaters
SUPPLY VOLTAGE
220-240 Volts AC 50 Hz
TIME OUT PERIOD
Adjustable 30 seconds to 4 hours
SETBACK TEMERATURE
Adjustable 5°C to 20°C
BOOST TEMPERATURE
Adjustable 10°C to 30°C
FIXING METHOD
Surface fixing 25mm deep plastic surface mount moulded box.
Flush fixing
35mm steel wall box (ensure top and bottom lugs are removed) or 35mm deep cavity wall box.
TERMINAL CAPACITY
4.0mm
2
MATERIAL
Flame retardant ABS
TYPE
Class 2
TEMPERATURE
-10°C to 40°C
CONFORMITY
EMC-89/336/EEC
LVD-73/23/EEC
HEATER DOES NOT COME ON
Check that the temperature in the room is below the setpoint. If not, then
the heater will not come on. Adjust the temperature settings accordingly.
Check that the boost has been selected—the green light should be on. If
this has not been selected then the lower setback temperature setting will
be used.
Check the circuit by strapping across L and LIVE OUT terminals.
BOOST LIGHT DOES NOT COME ON
Press the touch pad on the front of the unit.
Check that the unit is powered up by measuring the supply voltage across
L and N
ROOM TOO COLD
Check that the heater is working and the thermostat on the heater is
turned to maximum.
Check the temperature settings and increase if necessary.
Make sure that the thermostat is not installed above or near to the heater.
ROOM TOO HOT
Check the temperature settings and reduce if necessary.
Ref: #WD009 Issue 3
Fault Finding
Specification
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:
+ 44 (0) 333 900 0671
Fax:
+ 44 (0) 333 900 0674
www.cpelectronics.co.uk
[email protected]
IMPORTANT NOTICE!
This device should be installed by a
qualified electrician in accordance with
the latest edition of the IEE wiring
regulations.
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
FM 45789
EMS 534520