background image

The ENERSTAT-T electronic thermostat will accurately maintain the temperature of 
a room at two levels (or setpoints): the setback temperature and the boost tempera-
ture.  
 
Normally the lower setback temperature level is maintained. When the front of the 
unit is touched, the higher boost level is selected, but only for a preset time period. 
After the time period the unit reverts to using the setback temperature. 
 
Typically the setback level would be used to maintain background heat in a room. 
When the occupant requires extra heat, the boost level provides this, but only for 
the duration of the time period.  
 
The ENERSTAT-T can directly switch a heating load making it ideal for the control 
of panel heaters. 

Wiring 

Warning

. This device works at mains potential. Be sure to take care when 

working with electricity. 

 

1. 

Make sure the load is connected and in working order.  

2. 

Isolate the mains supply to the circuit at the main distribution 
board. 

3. 

Adjust the setback, boost and time settings according to the dia-
gram.  

4. 

Connect the controller via the terminal block. Live supply to the 

L

 

terminal, Neutral supply to the 

terminal and the load to the 

LIVE 

OUT 

terminal.  

5. 

Screw unit to the wall and switch the mains supply on. 

6. 

If the heater has its own internal thermostat, turn this to maximum. 

7. 

When the RED LED is lit, this indicates that the unit is supplying 
power to the heater. 

8. 

When the GREEN LED is lit, the unit is using the BOOST tempera-
ture. 

9. 

The heater will now come on only if the temperature in the room is 
less than the thermostat setpoint. 

10. 

Due to variations in room size, heater efficiency, airflow, mounting 
position, drafts etc. the temperature settings on the dial s should be 
used as guidance only. It may be necessary to adjust the unit to 
different settings in order to achieve the required temperatures. 

11. 

To test that the unit is functioning correctly, repeat from step 2 and 
select maximum boost temperature and minimum timing. 

Installation 

Wire the ENERSTAT-T as in the diagram. 

 

To get accurate temperature measurements, siting the 
unit in the correct location is important: 

 

Always mount onto a wall not a ceiling 

 

Do not install above a heater 

 

Allow a clearance of 500mm from the heater being controlled 

 

Avoid installing near drafts of airflow 

 

Ideally install at a height of 1.2m to 1.5m 

 

Do not cover the slots at the top and bottom 

 

Mounting on an internal wall or partition gives the best meas-
urement accuracy 

Overview 

Electronic Thermostat 

Product Guide 

ENERSTAT-T 

Отзывы: