![Cover JR 10 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/cover/jr-10/jr-10_user-manual_2673717016.webp)
14
5.
Audible alarms and event codes
5.1.
Audible alarms
Description
Alarm
The possibility of mute
Bypass mode
1x / 2 minutes
YES
Battery mode
1x / 4 seconds
Damage
continuous
Overload
2x / 1 second
NO
Other
1x / 1 second
YES
5.2.
Warning codes
Code
Error
Code
Error
01
Batteries not connected
36
Unbalanced inverter current
02
N wire missing
3A
Service Bypass included
04
Incorrect phase sequence of the rectifier
power supply
3C
Extremely unbalanced load
05
Incorrect phase sequence of the bypass
supply
3D
Unstable bypass
07
Battery overcharging
3E
Battery voltage too high
08
Low battery voltage
3F
Battery voltage unbalanced
09
Overload
40
Charger short circuit
0A
Fan failure
41
No Bypass power
0B
Active EPO
42
Isolation transformer overheating
0D
Overheating
43
DC BUS Soft Start Error
0E
Charger failure
44
EEPROM reset
21
Different rectifier feed lines in a parallel
system
45
External output switch open
22
Various bypass feed lines in a parallel
system
46
External battery switch open
33
Bypass mode lock after 3 times overload for
30 minutes
47
External Bypass switch closed
34
Inverter is out of symmetry
48
External input signal open