CARBON MONOXIDE (CO) DETECTOR

WITH RELAY OUTPUT

G 227

25.11.08 MZ

REV. 01

RGS 328  

Eng.

2. TYPICAL INSTALLATION

• Conforms to CEI EN 50291 & CEI EN 50292 standards

• Incorporates internal sensing element of electrochemical cell type

• LEDs for power supply, pre-alarm, alarm & sensing element fault

• SPDT relay output

• Power supply  230 V~ ; protection  IP 42

3. TECHNICAL DATA 

Power supply  

230 V ~ ± 10% 

Frequency 

50…60 Hz

Consumption 

2,5 VA

Protection 

IP 42

Electromagnetic compatibility 

CEE 93/68

Ambient temperature : 

– operating 

0…40 °C

– storage 

– 20…+ 60 °C

Permitted ambient humidity 

classe F DIN 40040

Weight 

250 g

Output SPDT relay : 

– type 

 stagno a gas inerte

– maximum switching voltage 

250 V ~

– maximum switching current 

5 (1) A

Acoustic alarm 

85 db / 1 meter

Sensor stabilisation time 

120 s

Sensing element: 

  

    – electrochemical cell 

   Sixth-Sense  ECO-Sure/2e

Alarm & pre-alarm thresholds: 

    

    – alarm 

"thr time"

< 50 ppm: no alarm

50…100 ppm: 60 minutes

100…300 ppm: 10 minutes

> 300 ppm:immediate alarm

    – pre-alarm 

 time between exceeding 

threshold and alarm

1. APPLICATION

Carbon monoxide (CO) is undoubtedly one of the most toxic gases for the human body. Its danger, moreover, 

is compounded by the fact that it is odourless, colourless and non-irritating and so absolutely undetectable by 

human senses. 
The RGS 328 detector is able to detect the presence of carbon monoxide in the air and can, therefore, ensure the 
safety of persons in domestic spaces where there are gas appliances.
An output relay can activate devices for changing the air and turning off, where possible, the combustion (e.g. by 
closing a shut-off valve for appliances operating on combustible liquids or gases).

Содержание RGS 328

Страница 1: ... V maximum switching current 5 1 A Acoustic alarm 85 db 1 meter Sensor stabilisation time 120 s Sensing element electrochemical cell Sixth Sense ECO Sure 2e Alarm pre alarm thresholds alarm threshold time 50 ppm no alarm 50 100 ppm 60 minutes 100 300 ppm 10 minutes 300 ppm immediate alarm pre alarm time between exceeding threshold and alarm 1 APPLICATION Carbon monoxide CO is undoubtedly one of th...

Страница 2: ...or sink near doors or windows near air extractors in places where the temperature and humidity could be at variance with those indicated under 3 TECHNICAL DATA in places where dust or dirt could block and so render ineffective the sensor in places where air movement could be hindered by furniture in places where it might be sprayed by water in places where it would be especially difficult to reach...

Страница 3: ...wer lights intermittently after this stabilization period the green LED remains lit and the detector is ready for the detection of the gas Signalling a normal situation The power supply LED green must be lit whilst the LEDs for signalling a fault yellow and pre alarm alarm red must be unlit The acoustic alarm must be off and the output relay switched off 10 2 Preallarm and alarm thresholds for car...

Страница 4: ...hts and stays lit indicating presence alarm the internal acoustic alarm is switched on the external switch is switched on relay switched on Release the push button after about 5 seconds the alarm ceases and the detector returns to its normal operating condition if the detector is connected to a solenoid valve with manual reset it is necessary to re open it with the reset le ver 11 2 Life cycle of ...

Отзывы: