background image

UAF-8

4.1 Installation method

n

When two or more power supplies are used side by side, position

them with proper intervals to allow enough air ventilation.Ambient

temperature around each power supply should not exceed the

temperature range shown in derating curve.

4 Assembling and

Installation Method

NO

YES

n

n

In parallel operation, output voltage increases like stairs due to a

delay of the rise time of output voltage at turn on.

In parallel operation, please connect diode to the +side of the out-

put circuit. If diode is connected to the -side, it will damage the

unit or/and the balancing function will not work.

n

n

n

Fan for forced air cooling is optional. Do not block the ventilation at

suction side (terminal block side), its opposite side and upper side.

When unit operates at dusty place, attach air-filter to avoid dust

into the unit. In this case, avoid poorly ventilated environment.

When unit mounted except below drawings, it is required to con-

sider ventilated environment by forced air cooling for tempera-

ture/load derating. For details, please consult our sales or engi-

neering departments.

Note:

In the hatched area, the specification of Ripple, Ripple Noise is

different from other area.

4.2 Derating

UAF

No

n

When fan is set separately, the temperature of part A of the unit

should be below 75 degree by flowing cooling-air inside of the

unit.

130

37

A

AIR

FAN

Instruction Manual

AC-DC Power Supplies Enclosed type

June 29, 2011

Отзывы: