3.1 Output current derating
3.1 Output derating
■
Please have sufficient ventilation to keep the temperature of point A in Fig.3.1 at Table 3.1
or below. Please also make sure that the ambient temperature does not exceed 85
℃
■
Derating curve is shown Fig.3.2.
Note: In the hatched area, the specification of Ripple, Ripple Noise is different form other area.
Table 3.1
Point A Temperature
Fig. 3.1
Temperature measuring
point on the case
(Top view)
Fig. 3.2
Output derating
A-8
Model
TUHS3
TUHS5
TUHS10
Point A
105
℃
105
℃
105
℃
100
℃
95
℃
100
℃
TUHS15
TUHS25
Output voltage
all
all
all
12V,24V
15V
all
2.1 Pin configuration
3.Derating
(A) TUHS3 Derating curve(Reference)
(B) TUHS5 Derating curve(Reference)
(C) TUHS10 Derating curve(Reference)
(D) TUHS15 Derating curve(Reference)
Point A(Center of the Case)
Applications Manual