6.3 Isolation

¡

When you run a Hi-Pot test as receiving inspection, gradually in-
crease the voltage to start.  When you shut down, decrease the 
voltage gradually by using a dial.  Please avoid a Hi-Pot tester 
with a timer because, when the timer is turned ON or OFF, it may 
generate a voltage a few times higher than the applied voltage.

¡

When you test a unit for isolation between the input and output or 
between the output and the terminal FG, short-circuit between the 
output and the terminals RCG, PGG and AUXG.

6.4 Auxiliary Power (AUX)

¿ 

PBA300F, PBA600F, PBA1000F and PBA1500F

¡

The power supplies can generate an auxiliary power (AUX: 12V 
0.1A) from CN3 to provide for remote ON/OFF and attached cir-
cuits.

¡

AUX circuit is isolated from other (input, output, FG, RC and PG) 
circuits.

¡

Please do not draw a current of 0.1A or higher from the auxil-
iary power because doing so could damage the internal circuits or 
cause malfunction.
When you connect a DC-DC converter, a current a few times 
higher than normal current may flow at start-up.  Please check the 
current.

6.5 External Component (Noise Filter)

¿ 

PBA1500F

¡

You can have the power supplies comply with FCC Part 15 class 

B and EN55022-B by connecting an external noise filter.

Examples of Constant Values of the External Noise Filter
  L 1 : 0.45mH 

L 2 : 0.45mH

  C1 : 0.1 F 

C2 : 0.1 F 

C3 : 0.1 F

  C4 : 4700pF 

C5 : 4700pF

  R1 : 2M

W

 

R2 : 2M

W

6  Others

6.1 Output Current Monitor

¿ 

PBA300F, PBA600F, PBA1000F and PBA1500F

¡

You can monitor an output current by measuring a voltage be-
tween the terminal CB and the terminal -S on either CN1 or CN2.

¡

Fig.6.1 shows the relationship between the voltage of the terminal 
CB and the output current.
Fig.6.1 shows a typical characteristic of PBA1500F-5.  Please 
contact us for the characteristics of the other models.
The output current shown in Fig.6.1 should be used only as a 
guide.

¡

Please note the followings when measuring the voltage of the ter-
minal CB.

-

Wire carefully to avoid malfunction caused by noise. 

-

Use a measuring instrument whose input impedance is 500

W

 

or more.

-

Do not short-circuit between CB terminal and -S terminal.  Do-

ing so could cause a failure.

6.2 External Capacity

¿ 

PBA10F, PBA15F, PBW15F, PBA30F and 

PBW30F

¡

When a capacitor with large capacity is connected to the load 
side, a power supply may stop or start hunting.  Please contact us 
for details.

Unit type

Instruction Manual

A-42

PB

Unit type

Instruction Manual

A-43

PB

Fig.6.2 External noise filter

Recommended noise filter : ZRAC2220-11 (TDK)

AC(L)

AC(N)

FG

AC(L)
AC(N)
FG

C5

R1 C1 L1

Noise filter

PBA1500F

L2

C3 R2

C2 C4

Fig.6.1 Load current conversion graph(PBA1500F-5)

Voltage of CB terminal

0

-2

2

-4

-6

[V]

100

200

300

Load current

[A]

Содержание PBA1000F

Страница 1: ...bling and Installation A 40 A 35 A 35 A 35 A 35 A 36 A 36 A 36 A 37 A 38 4 1 Series Operation 4 2 Parallel Operation Master slave Operation 4 3 N 1 Parallel Redundancy Operation 5 1 Installation 5 2 D...

Страница 2: ...output 12V 0 1A RC1 Remote ON OFF AUXG Auxiliary output GND N C No connection PG Alarm PGG Alarm GND Matching connecters and terminals on CN1 CN2 and CN3 Connector Housing Terminal Mfr CN1 CN2 CN3 S1...

Страница 3: ...rcuit When you turn the power ON OFF repeatedly within a short period of time please have enough intervals so that the inrush current limiting circuit becomes operative When the switch of the input is...

Страница 4: ...1 gives you only an estimate Please contact us if you need accurate numbers Output voltage Xrated output voltage 1 Please do not apply an external voltage of 0 7V or less or 3 0V or more There is more...

Страница 5: ...ltage may dramatically fluctuate because of an imped ance of wiring and load conditions Please check and evaluate carefully before using the remote sensing function If the output voltage becomes unsta...

Страница 6: ...High vary depending on models and conditions PBA300F and PBA600F less than 1 second PBA1000F and PBA1500F less than 10 second 2If the output voltage is turned off through a remote ON OFF cir cuit the...

Страница 7: ...imum number of units you can use in parallel operation is 5 4 2 Parallel Operation Master slave Operation PBA10F PBA15F PBW15F PBA30F PBW30F PBA50F PBW50F PBA75F PBA100F and PBA150F You can use the po...

Страница 8: ...PBW30F Input Voltage Derating Curve Input voltage derating curve is shown in Fig 5 2 PBA300F PAB600F PBA1000F and PBA1500F Ambient Temperature Derating Curve Derating curve depending on an ambient te...

Страница 9: ...ting curve Unit type Instruction Manual A 41 PB Fig 5 3 Ambient temperature derating curve Ambient temperature C Load factor 80 70 80 90 100 30 40 50 60 70 71C 0 10 20 30 40 50 60 20 10 20 0 10 Fig 5...

Страница 10: ...filter Examples of Constant Values of the External Noise Filter L1 0 45mH L2 0 45mH C1 0 1 F C2 0 1 F C3 0 1 F C4 4700pF C5 4700pF R1 2MW R2 2MW 6 Others 6 1 Output Current Monitor PBA300F PBA600F PB...

Страница 11: ...ns Doing so may cause a failure F1 PBA600F PBA1000F PBA1500F Option F1 units have a longer life fan instead of a standard fan This option is not available for PBA300F Differences from standard version...

Страница 12: ...PBW30F PBA50F and PBW50F 2 Matching Molex Connectors and Terminals for PBA75F PBA100F and PBA150F R PBA50F PBW50F PBA75F PBA100F and PBA150F You can control output ON OFF remotely in Option R units To...

Страница 13: ...5F and PBA30F has been filed Safety agency approvals will be void if the cover is attached after the unit is ex factoried N1 PBA10F PBA15F PBW15F PBA30F PBW30F PBA50F PBW50F PBA75F PBA100F and PBA150F...

Отзывы: