3.2 Derating

¡

Environment to use it and Installation environment

  When using it,it is necessary to radiate heat by the heat of the pow-

er supply.

  Table 3.1 - 3.9 shows the relation between the upper limit tempera-

ture (Point A and Point B) and load factors.

  Please consider the ventilation so that the convection which is 

enough for the whole power supply is provided.

  And temperature of Point A and Point B please become lower than 

upper limit temperature.

  The expectancy life in the upper bound temperature (Point A and 

Point B) is three years or more. 

  Please refer to External View for the position of Point A and Point B. 

  In case of with Chassis and Cover, please contact our sales offi ce 

for getting more information.

Remarks:

*

Please be careful of electric shock or earth leakage in case of 

temperature measurement, because Point A and Point B is live 

potential.

*

Please refer to 3.4 if you want to extend the longevity of the ex-

pectancy life.

Table 3.1 Temperatures of Point A, Point B LFA10F-

O

Mounting 

Method

Cooling 

Method

Load factor

Max temperature

Point A[

C

]

Point B[

C

]

A

Convection

20%

<

Io

[

100%

70

84

Io

[

20%

75

79

B

Convection

20%

<

Io

[

100%

70

81

Io

[

20%

73

77

C

Convection

20%

<

Io

[

100%

76

80

Io

[

20%

76

77

D

Convection

20%

<

Io

[

100%

70

78

Io

[

20%

75

77

E

Convection

20%

<

Io

[

100%

73

84

Io

[

20%

76

79

F

Convection

20%

<

Io

[

100%

74

80

Io

[

20%

76

78

A,B,C,D,E,F Forced air

70%

<

Io

[

100%

75

75

Io

[

70%

75

75

2.2 Parallel Operation

¡

Parallel operation is not possible.

¡

Redundancy operation is available by wiring as shown below.

¡

Even a slight difference in output voltage can affect the balance 

between the values of I

1

 and I

2

.

Please make sure that the value of I

3

 does not exceed the rated 

current of a power supply.

I

3

 

[

 the rated current value

3.1 Installation method

¡

This power supply is manufactured by SMD technology.

The stress to P.C.B like twisting or bending causes the defect of 

the unit,so handle the unit with care.

¡

In case of metal chassis, keep the distance between d

1

 & d

2

 for to 

insulate between lead of component and metal chassis, use the 

spacer of 8mm or more between d

1

. If it is less than d

1

 & d

2

, insert 

the insulation sheet between power supply and metal chassis.

3  

Assembling and 
Installation Method

¡

There is a possibility that it is not possible to cool enough when 

the power supply is used by the sealing up space as showing in 

Figure 3.2.

   Please use it after confi rming the temperature of point A and point 

B of Instruction Manual 3.2.

AC-DC Power Supplies Open Frame/ Enclosed Type

Instruction Manual

LFA-24

LFA

I

2

I

1

I

3

-

+

+

-

Load

Power
Supply

Power
Supply

Fig.2.4 Example of redundancy operation

Fig.3.1 Installation method

= 8mm min

= 4mm min

CN1

CN1

d

2

d

1

d

2

d

2

d

2

d

2

d

2

Power supply

Case

Fig.3.2 Installation example

me̲lfa1.indd   LFA-24

me lfa1 indd LFA-24

2015/06/15   15:22:54

2015/06/15 15:22:54

Содержание LFA100F

Страница 1: ... 3 Yes Yes No LFA15F Flyback converter 100 0 35 Thermistor CEM 3 Yes Yes No LFA30F Flyback converter 130 0 65 Thermistor CEM 3 Yes Yes No LFA50F Active filter 60 440 0 67 Thermistor CEM 3 Yes Yes No Flyback converter 130 LFA75F Active filter 60 440 1 0 Thermistor CEM 3 Yes Yes No Flyback converter 130 LFA100F Active filter 60 1 3 Thermistor CEM 3 Yes Yes No Forward converter 140 LFA150F Active fil...

Страница 2: ...range 1 2 Inrush current limiting 1 3 Overcurrent protection 1 4 Overvoltage protection 1 5 Output voltage adjustment range 1 6 Output ripple and ripple noise 1 7 Isolation 1 8 Reducing standby power LFA 22 LFA 22 LFA 22 LFA 22 LFA 22 LFA 23 LFA 23 LFA 23 5 1 Outline of options 5 2 Others LFA 30 LFA 32 5 Option and Others LFA 30 2 1 Series Operation 2 2 Parallel Operation LFA 23 LFA 24 AC DC Power...

Страница 3: ...istor technique is used in the inrush current limiting circuit When you turn power ON OFF repeatedly within a short period of time please have enough intervals so that the inrush current limit ing circuit becomes operative When the switch of the input is turned on the primary inrush cur rent and secondary inrush current will be generated because the thyristor technique is used for the inrush curre...

Страница 4: ...creased The specification of the Ripple Ripple Noise changes by this intermittent operation The value of the ripple ripple Noise when intermittent operates changes in the input voltage and the output current Please contact us for details Remarks When GND cable of probe with flux of magnetic force from power supply are crossing ripple and ripple noise might not measure correctly Please note the mea...

Страница 5: ...on 20 Io 100 73 84 Io 20 76 79 F Convection 20 Io 100 74 80 Io 20 76 78 A B C D E F Forced air 70 Io 100 75 75 Io 70 75 75 2 2 Parallel Operation Parallel operation is not possible Redundancy operation is available by wiring as shown below Even a slight difference in output voltage can affect the balance between the values of I1 and I2 Please make sure that the value of I3 does not exceed the rate...

Страница 6: ...100 75 75 Io 70 75 75 Table 3 5 Temperatures of Point A Point B LFA75F O Mounting Method Cooling Method Load factor Max temperature Point A C Point B C A Convection 70 Io 100 85 70 Io 70 86 76 B Convection 70 Io 100 77 65 Io 70 81 71 C Convection 70 Io 100 81 68 Io 70 83 72 D Convection 70 Io 100 78 58 10 Io 70 80 63 Io 10 84 72 E Convection 70 Io 100 73 66 10 Io 70 83 68 Io 10 83 79 F Convection ...

Страница 7: ...0 74 88 F Convection 80 Io 100 61 68 60 Io 80 68 71 Io 60 76 80 A B C D E and F 3 3V 5V 12V 15V Forced air 50 Io 100 75 75 85 85 Io 50 75 75 85 85 A B C D E and F 24V 30V 36V 48V Forced air 50 Io 100 75 75 85 85 Io 50 75 75 85 85 AC DC Power Supplies Open Frame Enclosed Type Instruction Manual LFA 26 LFA Inside is with case cover Inside is with case cover Fig 3 3 Ambient temperature derating curve...

Страница 8: ...ounting 2 A F mounting 10 70 60 50 40 0 3 2Forced air 0 5m3 min 1Convection 80 100 60 40 2 25 0 0 20 1 15 0 0 Load factor C Ambient temperature 1 C mounting 1 A mounting 1 B mounting 1 D F mounting 1 E mounting 2 A F mounting Fig 3 11 Ambient temperature derating curve 10 60 50 40 0 3 2Forced air 0 5m3 min 1Convection 80 75 100 60 40 20 10 0 20 10 0 Load factor C Ambient temperature 1 C mounting 1...

Страница 9: ...ing is necessary For more details please contact our sales or engineering departments 3 3 Mounting screw The mounting screw should be M3 The hatched area shows the allowance of metal parts for mounting If metallic fittings are used on the component side of the board ensure there is no contact with surface mounted components This product uses SMD technology Please avoid the PCB installation method ...

Страница 10: ...s 6years Ta 35C 6years 6years C Convection Ta 25C or less 6years 6years Ta 35C 6years 5years D F Convection Ta 25C or less 6years 6years E Convection Ta 25C or less 6years 5years A B C D E F Forced air Ta 60C 5years 5years Table 3 17 Expectancy Life LFA240F O Mounting Method Cooling Method Average ambient temperature year Expectancy Life Io 75 75 Io 100 A Convection Ta 30C or less 6years 6years Ta...

Страница 11: ... Average ambient temperature year Warranty Io 75 75 Io 100 A Convection Ta 40C or less 5years 5years Ta 50C 5years 3years B C Convection Ta 35C or less 5years 5years Ta 45C 5years 3years D E F Convection Ta 25C or less 5years 5years Ta 35C 5years 3years A B C D E F Forced air Ta 60C 5years 3years Table 3 25 Warranty LFA150F O Mounting Method Cooling Method Average ambient temperature year Warranty...

Страница 12: ...out the detail of LFA300F SNF LFA300F 5 12 24 TY In option SNF the cover chassis and cooling fan are added The appearance of option J units is defferent from the of stan dard appearance Please contact us about the detail Oil and other chemical liquid splashing environment may cause the performance degradation and failure Y Option Y units can adjust the output voltage by the potentiom eter is attac...

Страница 13: ...trol Standby power LFA100F LFA150F LFA240F 0 2Wtyp AC100V 0 7Wtyp AC200V LFA300F 0 25Wtyp AC100V 1 1Wtyp AC200V T LFA240F LFA300F Option T units have vertically positioned screws on a terminal block Please contact us for details about appearance The screw can be held to terminal block by inserting and lifting the screwdriver from the side of terminal block T1 LFA300F Option T units have horizontal...

Страница 14: ...e oper ation Please contact us for details when you connect the capaci tor LFA10F LFA15F When these power supplies are connected to the input terminal in parallel the total capacitance between line and line becomes big Therefore the electrical discharge resistance on the safety stan dard might become necessary Please contact us for details when safety standard is necessary at multiple units usage ...

Отзывы: