background image

n

n

n

In case of metal chassis, keep more than 8mm for the part of

to

insulate between lead of component and metal chassis. If it is

less than 8mm, insert the insulation sheet between power supply

and metal chassis.

The mounting screw should be M3. The hatched area shows the

allowance of metal parts for mounting.

Keep isolation distance between metal parts for mounting and in-

ternal components.

4.3 Mounting screw

l

LCC30A

5 Peak Loading

6 Ground

7 Others

n

Peak load current is possible to draw 10 seconds subject the aver-

age current should be less than the rated current. It will damage

devices inside the power supply when the peak load current con-

tinues more than 10 seconds.

n

When installing the power supply with your unit, ensure that the in-

put FG terminal or mounting hole FG is connected to safety

ground of the unit. However, when applying the safety agency,

connect the input FG terminal to safety ground of the unit.

n

n

n

This power supply is the rugged PCB type. Do not drop conduc-

tive objects in the power supply.

At light load, there remains high voltage inside the power supply

for a few minutes after power OFF. So at maintenance, take care

about electric shock.

This power supply is manufactured by SMD technology. The

stress to PCB like twisting or bending causes the defect of the

unit, so handle the unit with care.

LCC

CN1

CN1

CN1

Normal mounting

(A)

(B)

(C)

(Only when forced air)

CN1

CN1

CN1

(D)

(E)

(F)

CN1

CN2

7.5

7.5

7.5

7.5

7.5

7.5

7.5

7.5

unit [mm]

LCC-8

Instruction Manual

AC-DC Power Supplies Open Frame/Enclosed type

June 29, 2011

Отзывы: