EAC series
Small, common mode EMI/EMC Filters in 150kHz to 1MHz (1-Stage filter)
EAC -10 -472 -
O
Ordering information
*
The dimensions change when the option is set.
Refer to External view.
1
2
3
4
Features of EAC series
Circuit Diagram
Derating Curve
LINE
Case
: Mounting Plate
1
2
4
3
CY
CY
CY : Line to ground capacitor
LOAD
Small, common mode EMI/EMC Filters in 150kHz to 1MHz(1-Stage filter)
-
Single Phase 250 VAC
-
Small-size
-
Quick and easy push-down terminal
Just connect the wires,push-down and tighten
the screws with a screwdriver
Ambient Temperature [
C
]
Load Factor [%]
90
50
60
70
80
20
0
-40
40
-30
-20
100
80
60
40
55
Specifications
No.
Items
EAC-03-472
EAC-06-472
EAC-10-472
EAC-16-472
EAC-20-472
EAC-30-472
1
Rated Voltage[V]
AC 1
f
250 / DC250
2
Rated Current[A]
3
6
10
16
20
30
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4
Isolation Resistance (Terminal-Mounting Plate)
500 VDC 500M
W
min at room temperature and humidity
5
Leakage current 125/250V 60Hz
0.5mA/1.0mA max
6
DC resistance
180m
W
max
110m
W
max
40m
W
max
20m
W
max
10m
W
max
6m
W
max
7
Safety agency approval temperatures
-25 to +85
C
(Refer to Derating Curve)
8
Operating temperature
-40 to +85
C
(Refer to Derating Curve)
9
Operating humidity
20 to 95%RH (Non condensing)
10
Storage temperature/humidity
-40 to +85
C
/20 to 95%RH (Non condensing)
11
Vibration
10 to 55Hz, 19.6m/s
2
(2G), 3min. Period, 1hour each X, Y and Z axis
12
Impact
196.1m/s
2
(20G), 11ms Once each X, Y and Z axis
13
Safety agency approvals
UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
14
Case size (without projection) /Weight
39
X
30
X
85 mm [1.54
X
1.18
X
3.35 inches] (W
X
H
X
D) /170g max (Option : -D refer to external view)
DIN rail installation type is option
The terminal cover is retracted inside the unit
1
Model Name
2
Rated Current
3
Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
Leakage Current
(Input 125/250V 60Hz)
Line to ground
capacitor
(nominal value)
681
75.5 A/ 150 A max
680pF
102
0.13 mA/ 0.25mA max
1000pF
222
0.25 mA/ 0.5 mA max
2200pF
332
0.38 mA/ 0.75mA max
3300pF
472
0.5 mA/ 1.0 mA max
4700pF
*
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4
Options
D :DIN rail installation type
EA/ES-1
R