background image

STANDARD RECOMMENDED PROCEDURE 003-873 | ISSUE 2 | APRIl 2016 | PAGE 15 OF 18

9 .4  Install Strain-relief Hardware

If at least 10 m (33 ft) of outside plant cable is routed within an environmentally controlled 

building where temperature fluctuation is minimal, securing the cable sheath is adequate strain-

relief.

Step 1: 

Place hose clamp over the cable and strain-relief bar 18 mm (0.75 inch) below the 

sheath end. Center the sheath retention grip on the opposite side of the cable from 

the hose clamp tensioning body (Figure 21).

IMPORTANT: 

When using armored cable, install strain-relief bracket(s) to the opposite side (180 

degrees) from the location of the grounding clamp. Install the hose clamp and bracket 

25 mm (1 inch) from the end of the cable sheath to prevent the retention grip from 

overlapping the ground hardware.

Step 2: 

If there is a central member 

present, install the central 

member restraint clip as shown in 

Figure 22:

• 

Trim the central member 

flush with the bottom of the 

restraint clip.

• 

Insert the restraint cap 

threaded stud through the 

hole in the restraint clip, 

capturing the central member 

between the two.

• 

Wrap the aramid yarn, if 

present, twice in a clockwise 

direction around the threaded 

stud. 

• 

Install a washer and a nut.

Step 3: 

Tighten the hose clamp to secure the cable(s) to the strain-relief bar.

Step 4: 

Tighten watertight fitting.

IMPORTANT: 

The watertight fitting must be tightened to prevent water intrusion into the enclosure.

KPA-0900

Sheath

Retention 

Grip

Hose Clamp

Strain-relief Bracket

Braided Tubing

Figure 21

 — Attach Hose Clamp to Strain-relief Bar

Install Central Member Restraint Clip

1

Position Central

Member Between 

Restraint Clip and 

Restraint Cap

2

3

Install 

Central 

Member 

Restraint Cap

KPA-0901

Figure 22

 — Strain-relieve Composite Central Member

Содержание OptiTect

Страница 1: ...o 432 Fibers on a Wall 6 5 2 Mounting Cabinets with up to 432 Fibers into a Rack 6 5 3 Mounting Cabinets with more than 432 Fibers to the Floor 6 6 Opening the Cabinet 7 7 Grounding the Cabinet 7 8 Ma...

Страница 2: ...nstalled P N FDH GRND KIT Feeder and distribution cable installation kit Feeder and distribution cable strain relief kit Wall mount and rack mount kit Only included with smaller indoor cabinet Install...

Страница 3: ...pment and supplies 2 2 Materials Mounting hardware to attach the cabinet to the wall is not provided The hardware needed is dependent upon the surface to which the cabinet is being installed 3 Storage...

Страница 4: ...can alter the transmission characteristics of the cable the cable may have to be replaced Step 5 If the unit shipped with cables preinstalled clip the ties from the cables Roll out the cables when re...

Страница 5: ...View Top View 144 to 432 fiber cabinets 576 to 864 fiber cabinets Cabinet installed into frame Parameter 144 288 fiber unit 432 fiber unit 576 864 fiber unit Height H inches 31 33 26 25 w o splice ho...

Страница 6: ...inet and hook the mounting bracket over the bracket on the wall Figure 6 IMPORTANT Lower edge of the cabinet or splice chamber should be approximately 36 inches above the floor Step 5 Screw the bottom...

Страница 7: ...et Step 1 Unlock panel and swing it open Step 2 Open the splice chamber door and pedestal skirt if equipped with these items Slide splice trays out Step 3 Bring ground cable up through the grommet in...

Страница 8: ...put fiber field and the output fibers will be mated to the front of the storage parking panel Step 1 Once service has been ordered remove the appropriate connector from the stored parked position clea...

Страница 9: ...re sharply than the minimum recommended bend radius Do not apply more pulling force to the cable than specified Do not crush the cable or allow it to kink Doing so may cause damage that can alter the...

Страница 10: ...o allow for cable adjustment during braided tubing installation and strain relief activities Cabinet Capacity Distribution Cable s F2 Feeder Cable s F1 144 fibers 9 5 feet 10 5 feet 288 fibers 10 feet...

Страница 11: ...tment D Top of Cabinet 1 5 to 3 5 feet 4 feet All Cabinet Versions to 1 Full Loop of Fiber Around Splice Tray Sub units in Braided Tubing Refer to Table for Cable Sheath Removal Length 4 feet All Cabi...

Страница 12: ...e end of the fiber s with the electrical tape Figure 12 Figure 12 Attach Plastic Rod Step 3 Push the braided tubing over the rod Figure 13 Figure 13 Install Braided Tubing Step 4 Slide tubing toward t...

Страница 13: ...17 Remove Extra Slack Step 8 Secure the other end of the braided tubing Figure 18 Cut off the plastic rod Wrap electrical tape around the end of the braided tubing IMPORTANT Approximately 48 inches of...

Страница 14: ...he teeth on the upper plate into the sheath Step 4 Wrap the grounding connector and split portion of the sheath with a few wraps of vinyl tape Step 5 Attach the ring terminal of the ground wire over t...

Страница 15: ...ing the ground hardware Step 2 If there is a central member present install the central member restraint clip as shown in Figure 22 Trim the central member flush with the bottom of the restraint clip...

Страница 16: ...in the splice housing with Distribution splicing in subsequent trays above Two sub units jacketed or braided tubing with three 12 fiber ribbons per sub unit can be strain relieved to each feeder splic...

Страница 17: ...the organizer and routing slack around the organizer and within the interior of the tray Figure 26 Step 6 Reinstall the splice tray cover ensuring the tray cover is captured beneath the retaining tabs...

Страница 18: ...ng methods WARNING Isopropyl alcohol is flammable with a flashpoint at 54 F It can cause irritation to eyes on contact In case of contact flush eyes with water for at least 15 minutes Inhalation of va...

Отзывы: