Installation Instructions Remote Condensers
1.
Follow the standard installation instructions supplied with
flaker. Do not hook flaker into the power source until the re-
mote condenser and line set installation is complete.
2.
Assembly of remote condenser (see drawing):
a.
Assemble legs to base panel.
Install leg supports on legs.
b.
Locate the remote condenser in a well–ventilated area
on the roof away from other refrigeration equipment’s
condenser discharge air flow.
c.
Use the mounting holes provided to secure the remote
condenser to the roof. Seal over heads of bolts or fasten-
ers with tar or pitch to prevent entrance of moisture.
3.
Remote condenser electrical hook-up:
a.
Connect remote condenser to a power source
(208/230VAC, 60 HZ) separate from the flaker. An exter-
nal disconnect switch must be used.
b.
Make sure the electrical connections follow all local and
national codes.
c.
DO NOT turn condenser on until flaker install and re-
frigerant line connections are complete!
a.
Never wire condenser into flaker section. The con-
denser is an independent electrical connection.
b.
Fan motor will not start until pressure rises to 205
PSIG [14.07 Bars] closing fan cycling switch.
c.
The condenser fan may cycle off during the harvest
cycle – this would be normal.
Note: Installing an IMI Cornelius remote flaker with other
than an IMI Cornelius remote condenser and line set
may be reason to void the warranty.
UNIT
1/4-20 SCREW
LEG
BRACE
LEG
REMOTE CONDENSER
LEG
LEG SUPPORT