COR15BBCD Service Manual

© 2004, IMI Cornelius Inc.

- 7 -

Publication Number: 630460272SER

PROBLEM

POSSIBLE CAUSE

SOLUTION

THE TEMPERATURE IS NOT 
COLD ENOUGH

The refrigerator has been used 
improperly.

The shelves must never be 
covered with any type of plastic 
or other material that will block 
the circulation of cold air within 
the refrigerator.

The refrigerator has been 
overcharged with the 
refrigerant gas.

Check to see if condensation or 
ice crystals have formed on the 
suction line. If so, charge with 
the correct amount of gas.

The refrigerant gas is leaking.

Find the location where the gas 
is leaking in order to seal it or 
replace the defective 
component. Change the drier. 
Perform a good vacuum and 
recharge the unit.

The evaporator and/or 
condenser fans aren’t working.

Check the electrical 
connections and make sure 
that the fan blade isn’t stuck. 
Replace the fan motor if it 
doesn’t work.

Low voltage.

Use a voltage regulator if the 
voltage is lower than 103 volts.

ELECTRICAL SHOCKS

Wires or electrical components 
are in direct contact with 
metallic parts.

Check for appropriate 
insulation on the connections of 
each electrical component.

NOISE

The refrigerator is not properly 
leveled.

Check if the noise goes away 
after you level the refrigerator.

The condenser is not fastened 
correctly. Copper tubings are in 
contact with metal.

While the compressor is 
working, check to see if metal 
parts are in contact with one 
another and/or if the screws 
that fasten the condenser are 
tightened.

The evaporator and/or 
condenser fans are loose.

Check if the fans are securely 
fastened. Also, check if the fan 
blades are loose, broken or 
crooked. If so, change the 
faulty blade.

Compressor has an internal 
noise.

If the noise persists after all 
other measures have been 
taken, it may be originating 
from the compressor.

EXTREME CONDENSATION 
INSIDE THE REFRIGERATOR

Thermostat knob is set at a 
very cold position.

Set the thermostat knob to a 
warmer position and check if 
the compressor stops 
according to the thermostat’s 
operating range.

The outside environment’s 
relative humidity is very high 
(over 75%).

This type of occurrence is 
caused by local climatic 
conditions and not by the 
refrigerated unit.

Содержание COR15BBCD

Страница 1: ...K BAR COOLER COR15BBCD Service Manual Release Date May 2004 Publication Number 630460272SER Revision Date NA Revision A Visit the IMI Cornelius web site at www cornelius com for all your Literature ne...

Страница 2: ...that appropriate safety precautions are taken and that all local safety and construction requirements are being met in addition to the information contained in this manual To inquire about current re...

Страница 3: ...ring 4 Cleaning and Preventive Maintenance 5 Condensate Disposal System 5 Troubleshooting 6 Possible causes and solutions 6 Espa ol 9 Caracteristicas del equipo 9 Sistema de Refrigeracion 9 Explicaci...

Страница 4: ...COR15BBCD Service Manual Publication Number 630460272SER ii 2004 IMI Cornelius Inc...

Страница 5: ...protector is a thermo sensible device attached to one side of the compressor s box In any given situation if the compressor overheats or the voltage source varies drastically the thermal protector ope...

Страница 6: ...ling cabinet It also starts the compressor motor whenever the cabinet rises above the desired temperature The temperature control consists of a switch which is mechanically activated by a diaphragm Th...

Страница 7: ...discharged into the evaporator 6 The evaporator s serpentine allows the refrigerant to absorb and remove heat from the cooling compartment 7 The drop in temperature inside the cooling compartment is...

Страница 8: ...COR15BBCD Service Manual Publication Number 630460272SER 4 2004 IMI Cornelius Inc ELECTRICAL WIRING FIGURE 3...

Страница 9: ...at the rear and clean it as required Check it regularly for excessive water accumulation 6 Replace any malfunctioning parts as soon as possible Ask your dealer or service agency to order the parts re...

Страница 10: ...ondenser and allow for air circulation Low voltage Use a voltage regulator if the voltage is lower than 103 volts Compressor is stuck Change the compressor THE TEMPERATURE IS TOO COLD Thermostat knob...

Страница 11: ...or electrical components are in direct contact with metallic parts Check for appropriate insulation on the connections of each electrical component NOISE The refrigerator is not properly leveled Check...

Страница 12: ...the door hinges if needed replace the gasket if broken The refrigerator has been placed at an inadequate location The unit must not be near sources that produce too much heat NO ILLUMINATION The ligh...

Страница 13: ...ja del compresor Si el motor del compresor se pone demasiado caliente o toma una cantidad excesiva de corriente el protector t rmico se abrir rompiendo los circuitos de arranque y de marcha del motor...

Страница 14: ...rapa y desplaza humedad del sistema de refrigeraci n a la vez que permite que pase aceite y refrigerante a trav s del sistema Acumulador El acumulador est localizado en el conducto del refrigerante en...

Страница 15: ...sador desplaza calor del refrigerante seg n fluye a trav s del serpent n del condensador y lo libera al ambiente exterior La ca da de la temperatura del refrigerante cambia el vapor a l quido 5 El tub...

Страница 16: ...COR15BBCD Service Manual Publication Number 630460272SER 12 2004 IMI Cornelius Inc DIAGRAMA EL CTRICO FIGURE 7...

Страница 17: ...requerido Rev sela regularmente para prevenir una acumulaci n excesiva de agua 6 Reemplace cualquier pieza o parte defectuosa tan pronto sea posible Dir jase a su distribuidor o agencia de servicio p...

Страница 18: ...Y OBSERVE SI EL COMPRESOR ARRANCA BOBINAS DEL MOTOR DE COMPRESOR CORTADAS O QUEMADAS MIDA LA RESISTENCIA OHMICA DE LAS BOBINAS PRINCIPAL Y AUXILIAR UTILIZANDO UN OHMIMETRO Y COMPARELAS CON LOS VALORE...

Страница 19: ...S PARRILLAS NO DEBEN DE CUBRIRSE CON NINGUN PLASTICO O MATERIAL QUE OBSTRUYA LA CIRCULACION DEL AIRE DENTRO DEL REFRIGERADOR REFRIGERADOR CON SOBRECARGA DE GAS VERIFIQUE SI EXISTE CONDENSACION O FORMA...

Страница 20: ...CTO CON METAL TENIENDO EL COMPRESOR FUNCIONANDO VERIFIQUE SI PARTES METALICAS ESTAN EN CONTACTO Y O QUE LOS TORNILLOS DE SUJECCION DEL CONDENSSADOR ESTEN DEBIDAMENTE APRETADOS ABANICO DEL EVAPORADOR O...

Страница 21: ...JUSTADA O SI EL EMPAQUE ESTA ROTO AJUSTE LA PUERTA O REEMPLACE EL EMPAQUE EL REFRIGERADOR ESTA MAL UBICADO EL REFRIGERADOR NO DEBE DE ESTAR UBICADO CERCA DE FUENTES DE CALOR LAMPARA NO ENCIENDE SWITCH...

Страница 22: ...COR15BBCD Service Manual Publication Number 630460272SER 18 2004 IMI Cornelius Inc...

Отзывы: