background image

CH Series Chiller Operator’s & Installation Manual

© 1999-2010, IMI Cornelius Inc.

- 7 -

Publication Number: 620914801

Figure 5. Cabinet Section Exploded View 

Table 1. 

115V Chiller

Item 

No.

Part No.

Description

1

32386

Temperature Controller

2

31934

Power Switch

3

61014

Evaporator

4

620023502 Wrapper Panel

5

51882

Priming Reservoir Assy

6

24388

Panel, Left Side

7

60992

Compressor

8

31955

Pump

9

24390R

Base Assy

Содержание Chiller ("CH" Series) CH 250

Страница 1: ...AND CH251 Operator s Installation Manual Release Date April 19 2004 Publication Number 620914801 Revision Date April 29 2010 Revision D Visit the IMI Cornelius web site at www cornelius com for all y...

Страница 2: ...n trained and are skilled in working with electrical plumbing pneumatic and mechanical equipment It is assumed that appropriate safety precautions are taken and that all local safety and construction...

Страница 3: ...ion 1 Chiller Installation 2 Location of Chiller 2 Electrical Connections 2 Start Up 3 Process Water Flow Units and Pump and Tank Standard 3 Standard Thermostat Eliwell IC902 3 Chiller Maintenance 4 C...

Страница 4: ......

Страница 5: ...ughly inspected before leaving the factory and the carrier has accepted and signed for it Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier R...

Страница 6: ...ures will remain above 40 F 5 C and will never increase above 100 F 38 C To obtain optimum cooling capacity the ambient temperature should be at or below 80 F 27 C It is very important that the air in...

Страница 7: ...stem is free from the obstruction that all valves are open and the reservoir when available is full push the CONTROL POWER switch to the ON position The pump should now be operating STANDARD THERMOSTA...

Страница 8: ...iller Cleaning of the CONDENSER COIL FINS should be done approximately every three months depending upon cleanliness of your application Pump Motor The PUMP MOTOR should be lubricated with thirty drop...

Страница 9: ...ble De Ionized Water 1 5 Meg ohms Acceptable De Ionized Water 5 Meg ohms Acceptable with Stainless Steel PVC only No Copper or Brass Propylene Glycol Lab Industrial Grade Acceptable 30 Glycol 70 Water...

Страница 10: ...ler Unit runs continuously but is not cooling process water enough A Condenser is restricted B Unit low on refrigerant C Inefficient compressor D Unit is undersized for applica tion A Clean condenser...

Страница 11: ...20914801 Figure 5 Cabinet Section Exploded View Table 1 115V Chiller Item No Part No Description 1 32386 Temperature Controller 2 31934 Power Switch 3 61014 Evaporator 4 620023502 Wrapper Panel 5 5188...

Страница 12: ...otor 11 31488 Fan Blade 12 620023503 Panel Right Side 13 60576 Condenser 14 33082 Relay 15 32378 Transformer 16 32588 Temperature Probe 17 620023504 Panel Front 18 24389 Shroud Condenser Table 2 230V...