Cornelius CH1001-A Скачать руководство пользователя страница 8

CH1001-A Chiller Operator’s & Installation Manual

Publication Number: 620914301

- 4 -

© 2002-2010, IMI Cornelius Inc.

Control Power Switch/Light

A lighted ON/OFF pushbutton switch, shown in Figure 3, is used to switch power to the 24VAC control circuit. The 
switch illuminates to indicate that the chiller power is present.

Bypass Light (Blue)

A blue light, shown in Figure 3, is used to indicate when the system is operating at a reduced capacity. The light 
cycles on and off in response to the temperature controller when the system temporarily requires less cooling.

Safety Light (Red)

A red light, shown in Figure 3, is used to indicate that a fault has occurred in the chiller operation. The following 
conditions illuminate the safety light.

A. High refrigerant pressure.

B. Low process water temperature.

C. Low process water flow (optional, see Optional Equipment section)

High-Pressure Safety

The high-pressure safety, shown in Figure 3, shuts down the compressor and pump when the refrigerant head 
pressure reaches 240-PSIG for R-134A refrigerant units. The high pressure switch must be reset manually. The 
switch is located in the electrical box which must be accessed by removing the chiller lid. The high-pressure 
switch can be re-set by depressing the reset button through the opening in the electrical box cover. If the control 
opens again, check the setting with a set of refrigeration gauges. If the setting is correct, contact the Cornelius 
Technical Service Department.

Low-Temperature Safety

The low-temperature safety shuts down the compressor and the pump when the process water temperature 
drops below 35° F (1.7° C). The switch automatically resets when the water temperature is restored to 38° F (3.3° 
C). The low temperature control is located in the electrical box.

S

TART

 U

P

Process Water Flow, Units with Pumpt and Tank (Standard)

Follow standard plumbing practices and local codes in making water connections. The chiller inlet and outlet 
connections are 3/4”. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh 
strainer should be installed on the chiller inlet to prevent foreign particles from entering the system and should be 
cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near 
radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be 
insulated to prevent condensation and/or significant liquid heat loss.

After ensuring that the system is free from the obstruction, that all valves are open, and the reservoir when 
available is full, push the Control Power switch to the “ON” position. The pump should now be operating.

All chillers with pumps and tank are supplied with a pressure regulating valve on the pump discharge. This valve 
is preset at the factory to ensure that system pressure does not exceed the capabilities of the pump motor and/or 
piping. If this valve requires adjustment, please contact the Cornelius Service Group for the proper setting 
procedure and pressures.

WARNING: Never operate the chiller with it’s panels removed.

Always use the power switch to turn off the chiller when it is not being used (see Fluid

Recommendations page).

Always ensure that all air inlets and outlets are free from obstruction.

Be sure that the reservoir is filled with fluid prior to powering up the unit.

Содержание CH1001-A

Страница 1: ... CH1001 A Operator s Installation Manual Release Date August 9 2002 Publication Number 620914301 Revision Date May 6 2010 Revision E Visit the IMI Cornelius web site at www cornelius com for all your Literature needs ...

Страница 2: ...en trained and are skilled in working with electrical plumbing pneumatic and mechanical equipment It is assumed that appropriate safety precautions are taken and that all local safety and construction requirements are being met in addition to the information contained in this manual To inquire about current revisions of this and other documentation or for assistance with any Cornelius product cont...

Страница 3: ...trol Panel 3 Temperature Controller 3 Control Power Switch Light 4 Bypass Light Blue 4 Safety Light Red 4 High Pressure Safety 4 Low Temperature Safety 4 Start Up 4 Process Water Flow Units with Pumpt and Tank Standard 4 Temperature Controller Operation 5 Chiller MAintenance 5 Condenser 5 Pump Motor 5 Circulation System 5 Filters Strainers 5 Fluid Recommendations 6 Troubleshooting 6 Warranty 12 ...

Страница 4: ......

Страница 5: ...nce the CH Series Chiller will provide years of trouble free service UNPACKING AND INSPECTION This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier Request a written inspection report from the Claims Inspector to substantiate any necess...

Страница 6: ...above 40 F 5 C and never increase above 100 F 38 C To obtain optimum cooling capacity the ambient temperature should be at or below 80 F 27 C It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing objects A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent air flow obstructions It is also impor...

Страница 7: ...rol the process set point temperature The Unit has a large LED readout that displays temperature For adjusting set point and programming options see section on TEMPERATURE CONTROLLER OPERATION Figure 4 CH1001 A Temperature Controller CAUTION On three phase applications it is important that the rotation of the pump when supplied is correct Operating the pump in reverse for more than a few seconds w...

Страница 8: ...rocess water temperature drops below 35 F 1 7 C The switch automatically resets when the water temperature is restored to 38 F 3 3 C The low temperature control is located in the electrical box START UP Process Water Flow Units with Pumpt and Tank Standard Follow standard plumbing practices and local codes in making water connections The chiller inlet and outlet connections are 3 4 Flexible hose a...

Страница 9: ...equired contact the Cornelius Technical Services Department CHILLER MAINTENANCE Condenser On air cooled chillers the condenser fins should be cleaned by blowing compressed air through the condenser from the fan side Dirt and debris accumulate on the condenser fins over time and this build up can severely reduce the performance of the chiller Cleaning of the condenser coil fins should be done appro...

Страница 10: ...mperatures below 40 F Mineral Hydraulic Oils Commercial Automotive Antifreeze NOT Acceptable Silicate Rust Inhibitors in Automotive Commercial anti freeze damages pump seals and housing which lead to failure Acidic Basic Solutions Above 8 or below 6 PH Not Acceptable Mineral Hydraulic Oils Viscosity 50 Centistrokes Not Acceptable Trouble Problem Cause Remedy Chiller does not operate Power Light OF...

Страница 11: ...h pressure conditions B Unit is operating under low tem perature conditions C Unit has experienced low flow condition A Check for dirty condenser fins or obstruction of chiller air intake Press high pressure manual reset switch If this problem persist contact Corne lius Service Department B Low or now process water flow Ensure that there is adequate flow through the system plumbing OR Process wate...

Страница 12: ...Ice Frost Operator s Manual Publication Number M620919596OPR 8 2004 2007 IMI Cornelius Inc Figure 5 Process Water Flow Schematic Figure 6 Refrigeration Schematic ...

Страница 13: ...CH1001 A Chiller Operator s Installation Manual 2002 2010 IMI Cornelius Inc 9 Publication Number 620914301 Figure 7 Wiring Diagram ...

Страница 14: ...357 Pump 187483000 Clamp 32382 Motor 10 620306708 Electrical Box Assy 11 41331 Y Strainer 12 61003 TXV 13 60686 Filter Dryer 14 60687 Sight Glass 15 620602503 Evaporator Assy 16 620603201 Foamed Reservoir 17 22870 Fill Port 3 4 in SS Coupling 18 620313205 Switch Power 19 620602701 Controller Temperature 20 620701209 Gauge Pressure 21 620028002 Panel Rear 22 620602703 Solenoid Valve Hot Gas 6206027...

Страница 15: ...blication Number 620914301 Figure 9 Electrical Box Assemby Exploded View Table 2 Item No Part No Name 1 620028012 Enclosure Electric Box 2 32829R Transformer 3 31001 Safety Low Temp 4 60501 Safety High Pressure 5 33082 Pump Relay 8 620305902 Compressor Contactor 10 31407 Fuse Block ...

Страница 16: ...hat all equipment and parts are free from defects in material and workmanship under normal use and service For a copy of the warranty applicable to your Cornelius or Wilshire product in your country please write fax or telephone the IMI Cornelius office nearest you Please provide the equipment model number serial number and the date of purchase ...

Страница 17: ......

Страница 18: ...IMI Cornelius Inc www cornelius com ...

Отзывы: