CopperOptics 150-1318-01 Скачать руководство пользователя страница 12

Section 363-718-100
Revision 01

Page 12

TABLE 13.  FCS-718 WIRING PROCEDURES

Step

Operation

Action

1

Remove CO Fuse

a.

Remove the fuse at the central office fuse panel for the circuit where the
PG-Flex central office battery wire will be terminated.

2

Connect Frame
ground

Note:  Follow local grounding practices to ensure a good frame
ground connection to PG-Flex.

a.

At the COT shelf, connect one end of the frame ground wire to grounding
lug FRAME GROUND.

b.

Connect the other end of the frame ground wire to the central office
ground termination point.

3

Connect CO Battery

Note:  Use 12 AWG or larger wire to ensure good power
connections to PG-Flex.

a.

At the COT shelf, connect the wires used for central office battery and
central office battery return to the -48 V (TB1) and GND (TB2) screw
terminals.

b.

Connect the central office battery return wire to the central office battery
ground termination point.

c.

Connect the central office battery wire to the selected central office fuse
panel termination point.

4

Connect HDSL Lines

a.

Terminate HDSL Pair #1 onto wire-wrap pins A_HDSL_T1 (Tip) and
A_HDSL_R1 (Ring) on the COT shelf.

b.

Terminate HDSL Pair #2 onto wire wrap pins A_HDSL_T2 (Tip) and
A_HDSL_R2 (Ring) on the COT shelf.

Note:  The following steps may not be required if only System “A” is
being installed.

c.

Terminate HDSL Pair #1 onto wire wrap pins B_HDSL_T1 (Tip) and
B_HDSL_R1 (Ring) on the COT shelf.

d.

Terminate HDSL Pair #2 onto wire wrap pins B_HDSL_T2 (Tip) and
B_HDSL_R2 (Ring) on the COT shelf.

5

Connect Metallic
Bypass Pair

Note:  If subscriber drop testing is not required, skip this section.

a.

Connect the metallic bypass pair for System “A” from the MDF to wire
wrap posts A_BYPASS_T and A_BYPASS_R on the COT shelf. These
bypass pairs are also available on P1, see Table 8.

Note:  The following step may not be required if only System “A” is
being installed.

b.

Connect the metallic bypass pair for System “B” from the MDF to wire
wrap posts B_BYPASS_T and B_BYPASS_R on the COT shelf. These
bypass pairs are also available on P2, see Table 9.

6

Connect Alarm Lines

Note:  If external audible and/or visual alarm indications are not
required, skip this section.

a.

Refer to Table 5 for information on connecting alarm leads to the central
office alarm panel.

Table continued on next page

Содержание 150-1318-01

Страница 1: ...STALLATION AND TEST 7 UNPACKING 10 8 PRE PROVISIONING HDSL LINES 10 9 INSTALLATION REQUIREMENTS 11 10 MOUNTING 11 11 WIRING 11 12 TURN UP AND TESTING 11 13 TROUBLESHOOTING 11 CAUTION This product inco...

Страница 2: ...C rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate...

Страница 3: ...owered from 48 V dc CO battery 6 BACKPLANE CONNECTIONS 6 01 The backplane of the FCS 718 COT Shelf Figure 2 contains the following connectors CO Power Table 1 Local Area Network Table 2 Data Table 3 H...

Страница 4: ...5 mm Wire Wrap Tip and ring terminations for HDSL Pair 1 of System 2 to Remote Terminal 2 130 V dc is simplexed on this line for powering the Remote Terminal B_HDSL_T2 B_HDSL_R2 0 45 mm Wire Wrap Tip...

Страница 5: ...e jumpered to the BYPASS pair from RT 1 B_TEST_IN_T B_TEST_IN_R 0 45 mm Wire Wrap Test connection looking into the COT channel unit for the selected subscriber for System 2 This connection must be set...

Страница 6: ...na Termina Ckt 7Ckt 7Ckt 7Ckt 7Ckt 7Ckt 7 Termina Ckt 7Ckt 7Ckt 7Ckt 7Ckt 7 Ckt 7 tion tion Ckt 8Ckt 8Ckt 8Ckt 8Ckt 8Ckt 8 tion Ckt 8Ckt 8Ckt 8Ckt 8Ckt 8 Ckt 8 Notes 1 Each PG Flex channel unit provid...

Страница 7: ...1 9 34 2 10 35 3 11 36 4 12 37 5 34 9 6 35 10 7 36 11 8 37 12 Table continued on next column TABLE 8 CONTINUED Channe l Connector P1 Connector P3 Unit Circuit Ring Tip Ring Tip 4 1 38 13 2 39 14 3 40...

Страница 8: ...34 9 2 35 10 3 36 11 4 37 12 5 34 9 6 35 10 7 36 11 8 37 12 Table continued on next column TABLE 9 CONTINUED Channe l Connector P2 Connector P4 Unit Circuit Ring Tip Ring Tip 10 1 38 13 2 39 14 3 40 1...

Страница 9: ...4 29 Tip 4 5 Sleeve 2 30 Sleeve 1 6 Sleeve 4 31 Sleeve 3 7 OH 2 32 OH 1 8 OH 4 33 OH 3 9 Proceed 2 34 Proceed 1 10 Proceed 4 35 Proceed 3 11 Lock 2 36 Lock 1 12 Lock 4 37 Lock 3 13 38 14 39 15 40 16 4...

Страница 10: ...talk should be kept to a minimum Pair isolation tip ring tip ground and ring ground must be 100 kohms 8 02 The wire pairs from the COT to the RT must meet the following design guidelines Nonloaded cab...

Страница 11: ...of the frame Note If the COT is to support two systems on a single shelf then a second set of HDSL leads must be provided one set to each RT 6 Subscriber Lines Two 25 pair Amphenol ended female cables...

Страница 12: ...nate HDSL Pair 1 onto wire wrap pins A_HDSL_T1 Tip and A_HDSL_R1 Ring on the COT shelf b Terminate HDSL Pair 2 onto wire wrap pins A_HDSL_T2 Tip and A_HDSL_R2 Ring on the COT shelf Note The following...

Страница 13: ...he 48 V dc and GND screw terminals on the COT shelf b Visually verify the HDSL lines are terminated properly and with the correct orientation Note If the HDSL lines are not connected properly the COT...

Отзывы: