![Cooper Kyle Form 4C Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/cooper/kyle-form-4c/kyle-form-4c_programming-manual_2661594019.webp)
19
S280-77-4
!
SAFETY
FOR LIFE
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
09
1
0
YES
45.0
1.8
0.1
Reclose #3 (seconds)
5
•
Reclose #3 is the open time duration after the
third trip operation prior to automatic reclosing.
•
Selects the reclose interval after the third trip
operation.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
08
1
0
YES
45.0
1.8
0.1
Reclose #2 (seconds)
2
•
Reclose #2 is the open time duration after the
second trip operation prior to automatic reclosing.
•
Selects the reclose interval after the second trip
operation.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
07
1
0
YES
45.0
0.3
0.1
Reclose #1 (seconds)
2
•
Reclose #1 is the open time duration after the
first trip operation prior to automatic reclosing.
•
Selects the reclose interval after the first trip
operation.
Programming (cont’d)
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
06
1
0
YES
180
3
1
Reset Time (seconds)
30
•
Reset timing begins after a successful reclose
operation.
•
S u c c e s s f u l r e c l o s e i s d e t e r m i n e d w h e n t h e
recloser is closed and the current sensed is
b e l o w t h e m i n i m u m t r i p v a l u e s ( p h a s e a n d
ground).
Reclose
#1
Reclose
#2
Reclose
#3
CLOSED
OPEN
Figure 5.
Typical four trips to lockout operation. Fault current ini-
tiated with recloser closed.