Cooper GWC Series Скачать руководство пользователя страница 18

Voltage Restraint

When energized at 120Vac, the voltage charging board
provides fast charging times for the trip energy storage
capacitors. It also acts as a voltage restraint; the sec-
tionalizer will not count an overcurrent interruption of
the protective device unless the voltage at the control is
also interrupted. To check the voltage restraint feature,
proceed as follows:

1. Reconnect X-3 and X-4 leads to the battery charging board.

2. Jumper the ground actuating resistor with a short

lead to disable the ground sensing circuit.

3. Jumper terminals P and D together.

4. Program the sectionalizer for one-count-to-open.

5. Close the sectionalizer by operating the Manual

Control Switch to “CLOSE”.

6. With the test circuit connected to phase A of the sec-

tionalizer and S1 open, close S2 and raise the current
to slightly above the appropriate value shown in
Column B of Table 9. Hold S2 closed at this current
for at least three seconds.

7. Release S2 to simulate a downline device clearing the

overcurrent. The sectionalizer should not open.

8. Disconnect X-3 and X-4 leads on battery charger boards.

9. Again close and release S2. The sectionalizer

should open.

10. Remove the jumper from terminals P and D.

Number of Counts-to-Open

The number of counts-to-open can be verified by inter-
rupting, the preset number of times, an overcurrent
through the sectionalizer. For example, with the control
set for three counts, the sectionalizer will open upon the
third overcurrent interruption. Proceed as follows:

1. Jumper the ground actuating current resistor

with a short lead to disable the ground sensing
circuit.

2. Program the sectionalizer for three counts-to-

o p e n   b y   s e t t i n g   t h e   C O U N T S - T O - O P E N
SELECTOR switch to “3”

3. Close the sectionalizer by operating the Manual

Control Switch to “CLOSE”.

4. With the test circuit connected to phase A of the

sectionalizer and S1 open, close S2 and raise
the test current to slightly above the appropriate
value shown in Column B of Table 9. Hold S2
closed at this current for at least three seconds.

5. Open and close S2 a number of times. The section-

alizer should open upon the third opening of S2.

6. To verify the two-counts-to-open setting, set the

COUNTS-TO-OPEN SELECTOR switch to “2” and
repeat steps 3 through 5. The sectionalizer should
open upon the second opening of S2.

Count Reset

The count reset feature resets the sectionalizer count to
zero whenever current below the actuating level flows
through the sectionalizer for longer than the pro-
grammed reset time without interruption. The reset time
settings have a tolerance of ±10 percent.

It can be verified by interrupting an overcurrent flow

through the sectionalizer one time less than the
counts-to-open setting, then allowing load current to
flow for periods just under and just over the reset set-
ting. The sectionalizer should open if the overcurrent
for the final count is interrupted within the reset time
period (count has reset to zero). The following proce-
dures is used to verify the count reset:

1. Jumper the ground actuating current resistor

with a short lead to disable the ground-sensing
circuit.

2. Jumper terminals P and D together.

3. Program the sectionalizer control for two counts-

to-open and set the COUNT RESET SELECTOR
to 15 seconds.

4. Close the sectionalizer by operating the Manual

Control Switch to “CLOSE”.

5. With test circuit connected to phase A of the sec-

tionalizer and S1 open, close S2 and raise the test
current to slightly above the appropriate value
shown in Column B of Table 9. Hold S2 closed at
this current for at least three seconds.

6 . Release S2 to simulate a backup protective

device clearing the overcurrent. The sectionalizer
will register a count.

7 . Close S1 for 13.5 seconds.

8. Momentarily close and then release switch S2. The

sectionalizer should open, verifying that the count
reset has not been activated.

9. Reclose the sectionalizer. Close and release S2

once to register one overcurrent interruption count.

10. Close S1 for slightly more than 16.5 seconds.

11. Momentarily close and release switch S2. The sec-

tionalizer should not open verifying that the count
reset has been activated and the first count has
been erased.

12. Again, close and release S2. The sectionalizer

should open.

13. Remove the jumper from terminals P and D.

Type GWC Installation Instructions

18

Содержание GWC Series

Страница 1: ...straint 6 Response Time 6 Installation 7 Preliminary Checks 7 Lifting the Sectionalizer 7 Mounting the Sectionalizer 9 Mounting the Control 9 Grounding the Control 9 Control Cable 9 Auxiliary Power 9 Main Wiring 9 Interconnection Wiring Diagram 11 Interconnection Wiring Diagram Control 12 Accessories 13 Auxiliary Switch 13 Bushing Type Multi Ratio Current Transformers 14 Operating Instructions 14 ...

Страница 2: ...information is desired to satisfy a problem not covered sufficiently for the user s purpose please contact your Cooper Power Systems sales engineer SAFETY INFORMATION WARNING Follow all locally approved proce dures and safety practices when installing or operating this equipment Failure to comply may result in death severe personal injury and or equip ment damage G111 0 WARNING High voltage Contac...

Страница 3: ... upon the coordination scheme the sectionalizer will open during the first second and third open interval of the fault interrupting device to isolate per manent faults and confine outages to smaller sections of line The sectionalizer does not interrupt fault current but can be closed into a faulted line It opens during the open inter val of the backup device For this reason it must always be used ...

Страница 4: ...he OFF position this switch disables remote con trol but does not prevent automatic operations by means of the control panel switches An extra set of contacts on this switch can provide switch position information to the remote location 115Vac 5amp Breaker Switch In the ON position this switch energizes all 115Vac power to the control cabinet and the operating housing of the sectionalizer Manual C...

Страница 5: ...tays down and disables the closing circuit to block closing of the sectionalizer The lever must be returned manually to its UP position to re activate the closing circuit INDICATING DEVICES In addition to the contact position indicator lamps on the con trol panel a contact position indicator and an operations counter are located under the sleet hood on the mechanism operator cabinet The yellow con...

Страница 6: ...o values below phase or ground pickup levels Count Restraint The count restraint feature blocks the sectionalizer from generating a count pulse as long as 0 5 amps of load current flows through the sectionalizer Inrush Current Restraint The inrush current restraint feature blocks the phase and ground actuating levels for three seconds after current flow through the sectionalizer has been restored ...

Страница 7: ... approved safety practices when making hitches and lifting the equipment Lift the load smoothly and do not allow the load to shift This unit has two lifting lugs both must be used when lifting the sectionalizer Maximum strength is attained with a vertical lift attached to the lugs Use a spreader bar with a fixed attachment point for the hook at the load center If a sling is used it must have a fix...

Страница 8: ...Figure 7 Double size Cabinet Mounting Dimensions Figure 6 Standard Cabinet Mounting Dimensions Type GWC Installation Instructions 8 Figure 5 Type GWC Sectionalizer in KA146W3 Pole Mounting Hanger ...

Страница 9: ...vent repeated movement due to wind or other out side forces which can damage the cable AUXILIARY POWER All Type GWC sectionalizers require 120Vac auxiliary power to operate The 120Vac supply operates the spring charging motor the closing solenoid the battery charger and the voltage restraint circuit Auxiliary power connections and connections from remote operation are made on a 19 point terminal s...

Страница 10: ...e GWC Installation Instructions 10 INTERCONNECTION WIRING DIAGRAM Figures 10 and 11 show the interconnection wiring of both the sectionalizer and the sectionalizer control Figure 9 Main Wiring connections ...

Страница 11: ...MBLY VARISTOR CAPACITOR ASSEMBLY GREEN NO 1 NO 2 LS 3 3 NC 4 NC GND 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 GND S P M L F D C A G R N K H E B YELLOW ORANGE GREEN RED BLUE BROWN GVA 197C 2 NOTE CUT JUMPER 2 BLUE BROWN GREEN RED YELLOW ORG BLACK VIOLET G H B A D C F E WHITE WHITE WHITE BLACK BLACK BLACK A Ø B Ø C Ø YEL GROUND C Ø B Ø A Ø RED GROUND SENSING CURRENT TRANSFORMERS REF GWA 17B CONNECTOR PHAS...

Страница 12: ... 1 TB1 11 BRN 2 TB2 2 BRN TCB 5A CIRCUIT BREAKER Term To Color 1 TB1 6 RED 2 TB1 11 BRN BP BATTERY PLUG Term To Color BC 2 RED RES 2 BLK X TRANSFORMER 120 25 VAC Term To Color 1 VC A YEL 2 VC B GRN 3 BC 3 BRN 4 BC 4 WHT VC VOLTAGE CHARGING BOARD Term To Color A X 1 YEL B X 2 GRN C GND WHT D EC 18 ORG BC BATTERY CHARGER Term To Color 1 TB2 2 WHT 1 BC 4 WHT 2 TB1 17 RED 2 BP RED 3 TB1 10 BRN 3 X 3 B...

Страница 13: ...any cam position 1 Remove the auxiliary switch cover 2 Detach the switch from the switch link by removing the groove pin and C rings 3 Remove the machine screws attaching the assembly to the cabinet 4 With the switch removed unfasten the two hex nuts and lockwashers from the long machine screws that hold the switch sections together 5 Starting with the rear switch section lift the cams off the ope...

Страница 14: ...relay contact closes connecting the battery to a 24Vdc trip solenoid in the sectionalizer The trip solenoid breaks the toggle latch mechanism which releases the trip springs and opens the sectionalizer contacts The sectionalizer s opening operation closes a switch which connects 115Vac power to the motor The motor operates a gear reduction and lever mechanism to extend charge both the trip and clo...

Страница 15: ...upper right corner of the control cabinet A 120Vac battery charger provides a constant trickle charge to the battery Battery Connections When shipped from the factory the battery is discon nected from the control and its output connector is taped to the side of the battery Plug the connector into the mating receptacle located just below the battery to com plete the battery circuit Battery Check Th...

Страница 16: ...s monitor the conti nuity between test points C and D F and H If no conti nuity exists between either set of test points upon clos ing of the sectionalizer apply 6 amps of load current by closing switch S1 for 3 5 seconds Once continuity has been restored open S1 and proceed with the test proce dures Minimum Actuating Current The minimum actuating current can be verified by test ing at the 10 perc...

Страница 17: ...ous counts of overcurrents interrupted by downline protective devices by blocking the counting operation as long as a minimum of 0 5 amps of uninterrupted line current flows through the sectionalizer The operation of the count restraint can be verified by superimposing an interruptible overcurrent on a constant minimum line current The sectionalizer will not count or open on the interruption of th...

Страница 18: ... number of times The section alizer should open upon the third opening of S2 6 To verify the two counts to open setting set the COUNTS TO OPEN SELECTOR switch to 2 and repeat steps 3 through 5 The sectionalizer should open upon the second opening of S2 Count Reset The count reset feature resets the sectionalizer count to zero whenever current below the actuating level flows through the sectionaliz...

Страница 19: ...he appro priate value shown in Column A of Table 9 5 Release S2 to simulate a backup opening with only load current flowing through the sectionaliz er when current was interrupted The sectionaliz er should not open 6 Close S2 and in no more than three seconds adjust the test current to just below twice the appropriate value shown in Column A of Table 9 to simulate an inrush condition Release S2 Th...

Страница 20: ...Cooper Power Systems Quality from Cooper Industries P O Box 1640 Waukesha WI 53187 http www cooperpower com 1997 Cooper Power Systems Inc Kyle is a registered trademark of Cooper Industries Inc Printed on Recycled Paper KA2048 126 SAFETY FOR LIFE ...

Отзывы: