Cooper Greengate DLVP Скачать руководство пользователя страница 2

IB503030EN   

page 2

June 2020

www.cooperlighting.com

Quick Start Guide

Greengate - Distributed Low-Voltage Power System

1. Mount Low-Voltage Power Module

Min. 3” 

(75mm)

Min. 24” 

(600mm)

Min. 12” 

(300mm)

 2. Provide Power

 

All new wiring must be fully verified before applying power.

emergency power 

connection

remove divider and wire internally 

when NOT using EM panel

Note: LVPM-03-100-03 and LVPM-06-100-03 do not have emergency inputs

normal power 

connection

Normal Power Input

EM Power Input

120VAC

277VAC

120VAC

277VAC

LVPM-03-100-03-1E

1.76

0.76

0.88

0.38

LVPM-06-100-03-1E

4.40

1.90

0.88

0.38

 3. Configure Power Module

+ -

+ -

+ -

DEMAND

CLOCK

ALERT

LOW

HIGH

1

1

REC

BMS/OUT

2

2

SWITCH

PACK

WALL

SENSORS

1 2 3 4 5
V Y
O N

Occ 

/ V

ac

Par

tial On

Y
N

Y
N

S

elect Occ

Occ Share

F
S

Auto On

DEFAULT

10%

1

20%
30%
40%

2 3 4 5

DIA

G

NORM

DIP Switch Set A

Switch # / Mode

Position

Operation

1 / Occupancy

V

Vacancy

 

O

Occupancy

2 / Partial ON

Y

Partial ON 50%

N

Scene 6

3 Selectable Occupancy

Y

By Zone

N

By Space

4 Occupancy Sharing

Y

Share Sensor

N

No Sharing

5 Scheduled Level

F

Fixed to Full / Off

D

Default Configured Scenes

4. Connect Fixtures

S

TA

TUS

TES

T

RESET

4

5

6

1

2

EMERGENCY

3

LOW-VOLTAGE OUTPUTS

SUITABLE FOR CLASS 2 WIRING

LL5030

18EN

57VDC 90W MAX (EACH OUTPUT)

CAUTION: DO NOT OVERLOAD

+ -

+ -

+ -

DEMAND

CLOCK

ALERT

LOW

HIGH

TRIM

1

1

REC

BMS/OUT

2

2

SWITCH

PACK

WALL

SENSORS

1 2 3 4 5
V Y
O N

Occ 

/ V

ac

Par

tial On

Y
N

Y
N

S

elect Occ

Occ Share

F
S

Auto On

DEFAULT

10%

1

20%
30%
40%

2 3 4 5

DIA

G

NORM

90W MAX 

per LV output 

circuit

Low-voltage 

lighting cable

5. Fixture Zone Assignment

1

2

3

4

5

6

Zone 3

O

N

1

2

3

4

5

6

Zone 2

O

N

1

2

3

4

5

6

Zone 1

O

N

     

ote: 

N

Zone 1 is any DIP switch configuration that is not specifically 

zone 2 or zone 3.

ote: 

N

During normal operation, avoid setting all DIP switches to the  

ON position.