Wiring connection drawings

4

Zone wiring

Each zone circuit is supplied with an End of Line Monitor unit
(EOLM-1). All zone circuits must be terminated with an EOLM-1,
connected at the end of the installed zone wiring, taking care to
observe the correct polarity.

Do not fit any other component such as an end of line resistor to
the zone circuits.
The EOLM-1 works in conjunction with a diode fitted in each
detector base so that all call points continue to function should a
detector head be removed.
This range of control panels can support up to 32 detectors
(max per zone) and an unlimited number of call points per zone.

Sounder wiring

The standard 1, 2, and 4 zone fire alarm control panels have two
separately protected, line monitored, sounder circuits for use with
polarised and suppressed bells, sounders, strobes, relays etc.
The 8 zone fire alarm control panel has four separately
protected, line monitored, sounder circuits for use with
polarised and suppressed bells, sounders, strobes, relays etc.

The wiring for each sounder circuit is to be a parallel circuit with
the 6K8, end of line resistor (EOLR), fitted at the end of the
installed sounder circuit wiring. No ‘spurs’ or ‘tee’s’ permitted.

+

_

Содержание FX range

Страница 1: ...Installation and user manual for the FX range of fire panels 1 2 4 and 8 zone panels...

Страница 2: ...el installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check 8 Commissioning User information Maintenance Tables Sounder and Visual Indication 9 Technical S...

Страница 3: ...m Within the panel the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS Battery connection The 1 2 4 zone panel requires a...

Страница 4: ...oved This range of control panels can support up to 32 detectors max per zone and an unlimited number of call points per zone Sounder wiring The standard 1 2 and 4 zone fire alarm control panels have...

Страница 5: ...2 then silence then reset check all indicators show momentarily Check each zone and alarm line for open and short circuit fault monitoring Zone circuits Disconnect the mains and battery supply wire in...

Страница 6: ...s the panel indicators and resets faults relay access code level 2 There are 2 access codes used by the control panel access level 2 client code 3112 and access level 3 engineers code These codes are...

Страница 7: ...l times until sounder LED turns off Push button to confirm enable sounders 3 1 2 5 Disable zone Isolates required detection zone from the system access code level 2 3 1 2 5 1 2 3 4 5 1 2 3 4 5 Detecto...

Страница 8: ...ad by activating a call point Log test results in log book Six monthly Test As per quarterly test Visual inspection of site to check for compliance of system to recommendations of local standard The t...

Страница 9: ...el type 1 Zone 2 Zone 4 Zone 8 Zone Detection zones 1 2 4 8 Detectors per zone 32 Alarm lines 2 4 Max alarm line load 300mA total shared 800mA total shared 500mA per alarm line 2A total Fire Fault rel...

Страница 10: ...PINSTFX2200GENR1 PR000 00 513 01...

Отзывы: