Intelligent Addressable Passive Repeater Panel - DF6000PR
Code
CF30000PR
Description
Passive repeater panel
Standards
EN54 Pt4
Specification
Mains Input Voltage
230V ac +10% / -15%
Operating Voltage
24V dc
System Indicators
Power on, fire, fault, test, disable and scroll
System Controls
Silence alarms, evacuate and reset
Input Ports
RS232 (for connection of programmer)
Battery
1 x 12V 3.2Ah
Standby Duration
24 hours
Environmental
Operating Temperature
0°C to +25°C
Humidity (Non Condensing)
0 to 75% RH
Physical
Construction
PC/ABS
Colour
Light Grey
Dimensions (H x W x D)
332mm x 270mm x 92mm
Weight
3.6kg
Ingress Protection
IP30
Compatibility
Suitable for use with
Menvier intelligent addressable fire systems
Technical Specification
Installation
1. Wall mounted by means of 4 fixing screws.
2. Cable entry at top or back.
3. 12 top entry gland holes with push out blanking
plugs.
4. 4 separate rear access cable entry facilities.
5. Local mains supply required.
System Functionality
1. Panel operates in either normal, supervisor or
engineer mode.
2. Supervisor and engineer modes are accessed via
4 digit pass codes.
3. Supervisor mode allows silence, evacuate and
reset commands to be sent to host panel (loop
connected) or to network (network connected).
4. Engineer mode enables password to be changed if
required and allows access to text download menu
5. When connected to network, all text is transmitted
via network, changes to other network panels
update automatically.
6. When connected to a detector
loop, text for host is
downloaded to repeater and
updated manually as required.
7. Zonal fire and fault indication is
by means of 2 x 40 character
LCD display.
Device Overview
1. Panel can be connected to
either the detection loop of a
single panel or to a network as
part of a networked system.
2. Supplied with integral power
supply and standby battery.
Dimensions
W
H
D2
D1
1
2
3
4
5
SCROLL
MUTE
BUZZER
H (mm)
W (mm)
D1 (mm)
D2 (mm)
270
332
45
47
Code
Description
DF6000PR
Intelligent addressable passive repeater panel, loop connected
DF6000PRNC
Intelligent addressable passive repeater panel, network connected
Product Codes
Mains Supply
Network Link
Mains Supply
Mains Supply
Network Link
Loop Connected
Network Connected
Note:
In this configuration the repeater would give
‘text’ information for the panel that is on the
loop, but only address number for the other
panel on the network.
Standard Connection
- +
SCREEN
- +
SCREEN
LOOP
OUT
LOOP
IN
SCREEN
Tx +
Tx -
Rs485
MIMIC
TEXT DOWNLOAD