Cooper 84700 Series Скачать руководство пользователя страница 10

9131 

Rev. M 

 

SECTION 2 

 

TECHNICAL DESCRIPTION 

 
 

2.1 

THEORY OF OPERATION 

 

The operational discussion presented herein pertains to standard model CSC units.  
Equipment supplied with options may deviate somewhat from the exact operational 
description presented, but the basic operating principles are identical for all 
equipment configurations. 
 

2.1.1 

Local Control 

 

The CSC control circuits operate from the 120 VAC primary power source and 
energize the relay coils in the high voltage circuit to supply power to the lighting 
circuit selected.  When switch, remote-off-local, is selected to LOCAL, switches S1 
and S2 (S1 through S4) are active.  When any of these switches is set to ON, a signal 
is applied to the timing circuits located on the circuit card assembly.  The timing 
circuit, in turn, supplies power immediately to the coil of the respective double pole 
relay in the high voltage section.  After a brief delay, less than one second, the timing 
circuit supplies power to the coil of the associated single pole shorting relay in the 
high voltage section, thus energizing the lighting circuit.  (Note:  Due to the 
characteristics of Type L-828 Regulators, the other lighting loads may dim 
momentarily.  This is normal.)  To de-energize a lighting circuit, the respective 
control switch is selected to OFF.  This action immediately de-energizes the single 
pole shorting relay, which places a short across the lighting circuit.  After a brief 
delay, the timing circuit removes power from the coil of the double-pole isolating 
relay, which opens to isolate the lighting circuit from the regulator.  The timing 
diagram in Figure 2-1 may be helpful in understanding the switching sequence. 
 
De-energized switching (Option -1) is installed on all units.  This turns the regulator 
off  prior to switching the circuits and turns the regulator back on after the circuits 
have been switched.  See Sections 3.1.3.2 and 3.1.4 for more detail. 
 

2.1.2 

Remote Operation 

 

The CSC, when operated remotely, functions exactly the same as when under local 
control, except that switches S1 and S2 (S1 through S4) are not active.  Remote 
control power is normally derived internal to the CSC.  However, external power 
sources may be used if the proper option is specified. 
 

2.1.3 

CCR Interlock 

 

An interlock switch is provided for the high voltage section of the CSC.  This switch 
should be connected in series with the control circuit of the CCR to provide for 
immediate shutdown of the CCR in the event that the dead front cover of the CSC is 
removed.  Normally, however, the CCR or CCRs should be de-energized prior to 
removal of the dead front cover  

 
 
 
 
 
 

 
 

Содержание 84700 Series

Страница 1: ...roducts 1200 Kennedy Road Windsor CT 06095 860 683 4300 Fax 860 683 4354 Title COPYRIGHT 2006 Cooper Technologies Company FOR PARTS AND SERVICE CALL 860 683 4300 DOCUMENT 9131 December 5 2006 Revision...

Страница 2: ...1 label to current label 3 Pg 39 revised labeling of TB1 label to accurately represent option 9 function 4 Pg 40 added 3rd view of remote control connections for option 9 A97 516 11 3 97 JAS H 1 On pa...

Страница 3: ...eof Crouse Hinds Airport Lighting Products obligation under this warranty is limited to use reasonable efforts to repair or at its option replace during normal business hours at any authorized service...

Страница 4: ...While practical safety precautions have been incorporated in this equipment the following rules must be strictly observed KEEP AWAY FROM LIVE CIRCUITS Operating and maintenance personnel must at all...

Страница 5: ...INSTALLATION AND OPERATION 3 1 Installation 6 3 2 Operation 12 SECTION 4 MAINTENANCE 4 1 Periodic Maintenance 14 4 2 Corrective Maintenance 14 4 3 Troubleshooting Chart 15 SECTION 5 PARTS LIST 5 1 Sco...

Страница 6: ...w B 21a Figure 5 2 84700 3 or 4 Components 22 Figure 6 2A Wiring Diagram 84700 2 2 28 Figure 6 2B Wiring Diagram 84700 4 2 29 Figure 6 5A Wiring Diagram 84700 5 or 6 30 Figure 6 5B Wiring Diagram 8470...

Страница 7: ...ts either locally or from a remote location without affecting CCR operation 1 2 2 Features The CSC is designed to accommodate lighting loads of up to 70KW at 20 amps and 30KW at 6 6 amps Standard mode...

Страница 8: ...847 3 4 24 H x 30 W x 9 D 103 lbs Mechanical All models supplied in a NEMA 1 enclosure painted blue All high voltage components protected by a clear dead front cover Environmental Temperature 55 to 55...

Страница 9: ...s simultaneous switching i e A or B or A B OPTION SELECTION CHART OPTION NO DESCRIPTION 1 De Energized Switching Included in all units 2 Primary Power 220 to 240 VAC 50 60Hz 3 Remote Control 48 VDC Ex...

Страница 10: ...normal To de energize a lighting circuit the respective control switch is selected to OFF This action immediately de energizes the single pole shorting relay which places a short across the lighting...

Страница 11: ...9131 Rev M 5...

Страница 12: ...of standing water hindering maintenance or normal operations 3 1 2 Power Requirements Standard model CSC units require a source of 120 VAC at 50 60Hz If the particular unit to be installed is equipped...

Страница 13: ...2 Electrical Wiring 1 Connect the ground conductor to the ground lug located in the lower left hand corner of the base plate 2 Connect the remote control leads to 31955 TB1 terminals as indicated L 1...

Страница 14: ...CONNECTING LOAD TO LOOP TERMINALS REMOVE JUMPER FROM ONLY THOSE TERMINALS THAT LOAD IS BEING CONNECTED TO 6 Make any option related connections 7 Re install the dead front cover and fasten securely 3...

Страница 15: ...9131 Rev M 9...

Страница 16: ...9131 Rev M 10...

Страница 17: ...9131 Rev M 11...

Страница 18: ...ergize Refer to Section 2 1 1 for operational details 5 Set switch S1 to OFF and verify visually that the LOOP 1 high voltage relays de energize 6 Repeat steps 4 and 5 for the remaining switches and L...

Страница 19: ...n most cases the CSC will be operated from a remote location To affect this mode set to remote and close the cabinet door No other adjustments are necessary To operate the CSC locally set for local op...

Страница 20: ...trical power B Check all wiring connections for loose or missing screws Check terminal blocks and component connections C Check for broken or damaged wires and components D Remove dust build up E Insp...

Страница 21: ...Particular areas of concern are A Power must be removed from the CSC before attempting to disconnect or re connect the connector plugs from the board B The circuit card is held in place by five screw...

Страница 22: ...9131 Rev M 16...

Страница 23: ...9131 Rev M 17...

Страница 24: ...relay harness Regulator trips off when one or more circuits are activated Miswired lighting Check all wiring Defective relay or open lighting circuit Disconnect wires to R1 R2 using an ohmmeter deter...

Страница 25: ...delay between high voltage relay actions Defective timing circuit card Replace the timing circuit card Observe all precautions of para 4 2 when replacing the timing card High voltage Relay module at...

Страница 26: ...or Parts List 84700 3 or 4 5 2 ARRANGEMENT The Figures and Tables in this section are arranged to show each replaceable part or assembly The parts are identified in each Figure by Index Number The Ind...

Страница 27: ...9131 Rev M 21...

Страница 28: ...9131 Rev M 21a...

Страница 29: ...9131 Rev M 22...

Страница 30: ...Plate 30832 7 1 1 Dead Front Bracket 30828 8 K1 1 2 Relay High Voltage SPNC 34197 9 K2 1 2 Assembly Vacuum Relay L 847 34196 10 1 1 Switch Label 31981 11 1 1 Interlock Switch 10047 1616 12 1 Jumper W...

Страница 31: ...30829 8 K1 3 4 Relay High Voltage SPNC 34197 9 K2 3 4 Assembly Vacuum Relay L 847 34196 10 1 1 Switch Label 31975 11 1 1 Interlock Switch 10047 1616 12 2 3 Jumper Wire 46 245 5X D 4 13 1 1 Ground Stu...

Страница 32: ...card see Figure 5 1 or 5 2 for location changes with Option 4 See Table 6 1 for circuit card part number variations See Figure 6 3 4 11 for external remote control connections 6 5 Option 5 The part nu...

Страница 33: ...tion changes with Option 11 See Table 6 1 for circuit card part number variations See Figure 6 3 4 11 for external remote control connections 6 12 Option 12 Item 14 P N is 10047 2276 except when used...

Страница 34: ...w Opt 3 31955 8 84700 2 3 9 31955 9 84700 1 or 2 w Opts 3 8 31955 10 84700 3 or 3 w Opts 3 8 31955 11 84700 1 or 2 w Opt 11 31955 12 84700 3 or 4 w Opt 11 31955 13 84700 2 9 11 31955 14 84700 1 or 2...

Страница 35: ...9131 Rev M 28...

Страница 36: ...9131 Rev M 29...

Страница 37: ...9131 Rev M 30...

Страница 38: ...9131 Rev M 31...

Страница 39: ...9131 Rev M 32...

Страница 40: ...9131 Rev M 33...

Страница 41: ...9131 Rev M 34...

Отзывы: