background image

NOTE: All CAUTIONS and WARNINGS are identified by the symbol  . All warnings are printed in bold capital letters.

 

  WARNING:  PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING 

OR APPLYING THIS PRODUCT.  VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION 

INSTRUCTIONS.  FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, 

INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND 

SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

General Notes:

 

Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.  Note that NFPA-72 specifies a flash rate 

of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.

• 

All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.

• 

Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and 

maximum humidity of 93% (± 2%).   

• 

Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). 

• 

“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range.  Prior to this change UL used the 

terminology “Listed Voltage Range”.

Table 1: Ratings Per UL Standard 1971

Model

Input 

Voltage

VDC

 Regulated 

Voltage 

Range 

VDC/FWR

Strobe Candela 

(CD)

NS-24MCW

24

16.0 - 33.0

15/30/75/110

NS-241575W

24

16.0 - 33.0

15 (75 on Axis)

NS-121575W

12

8.0 - 17.5

15 (75 on Axis)

NS-24MCC

24

16.0 - 33.0

15/30/75/95

NS-24MCCH

24

16.0 - 33.0

115/177

Table 2:  dBA Ratings for Series NS/NH Horn

Description

Volume

Reverberant dBA 

@ 10ft per UL 464

Anechoic dBA 

@ 10 ft

12 

VDC

24

VDC 

12

VDC

24

VDC

Continuous 

Horn

High

83

87

89

95

Low

76

81

84

90

Code 3 

Horn

High

79

82

89

95

Low

72

76

84

90

Table 3:  UL Max Current*

Series NS/NH 

24 VDC

Audible

Wall Mount Strobe Models

Ceiling Mount Strobe Models

NH-12/24 NS-241575W

NS-24MCW

NS-24MCC

NS-24MCCH

@24VDC

15/75cd

15cd 30cd 75cd 110cd 15cd 30cd 75cd 95cd 115cd 177cd

High (95) dBA

24VDC

0.044

0.104

0.074 0.107 0.184 0.244 0.082 0.124 0.209 0.275 0.350 0.477

Low (90) dBA

24VDC

0.018

0.096

0.066 0.101 0.177 0.232 0.071 0.114 0.201 0.261 0.306 0.429

Series NS/NH

12VDC

Audible Wall Mount

NH-12/24 Aud/Strobe

@12V

NS-121575W

High (89) dBA

12 VDC

0.021

0.220

Low (84) dBA

12VDC

0.012

0.210

* RMS current ratings are per UL average RMS method.  UL 

max current rating is the maximum RMS current within the listed 

voltage range (16-33v for 24v units).  For strobes the UL max 

current is usually at the minimum listed voltage (16v for 24v 

units).  For audibles the max current is usually at the maximum 

listed voltage (33v  for 24v units).  For unfiltered FWR ratings, 

see installation instructions.