Series PS-12/24-8CP
or PS-12/24-8MP
EOLR
F
A
C
P
OUTPUTS
1-4
4-CLASS
"B"
OR
2-CLASS
"A"
AS
AS
AS
RSS
RSS
RSS
+
-
+
-
+
-
FROM
PRECEDING
APPLIANCE
OR FACP
TO NEXT
APPLIANCE
OR EOLR
Wiring Diagrams
#
#
For detail using SM or DSM Sync Module refer to Data Sheet
S3000 or Installation Instructions P83123 for SM and P83177
for DSM. For wiring informationon the power supplies refer to
Installation Instructions P84662 for PS-24-8MC.
SERIES AS APPLIANCES NON-SYNCHRONIZED
SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE
CLASS”A” NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN-
GLE CLASS “B” NAC CIRCUIT WITH AUDIBLESILENCE FEATURE
SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH
PS-12/24-8CP and PS-12/24-8MP
AS
AS
EOLR
+
-
SM
F
A
C
P
STROBE
Audible
STROBE
+
- Audible
Audible
NAC
Circuit
Strobe
NAC
Circuit
Note
: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery.
**For Weatherproof Series AS/AH specifications see data sheet S9004.
***Refer to Data Sheet S7000 for Mounting Options.
Model Number Order
Code
Strobe
Candela
Non-
Sync
Sync w/SM,
DSM or
PS-24-8MC
24
VDC
12
VDC
Wall
Mount
Ceiling
Mount Mounting Options***
Agency Approvals
UL MEA CSFM FM BFP
AS-24MCW-FR
9024 15/30/75/110
X
X
X
-
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AS-24MCW-FW
9025 15/30/75/110
X
X
X
-
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AS-24MCWH-FR
3468
135/185
X
X
X
-
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
*
AS-24MCWH-FW
3469
135/185
X
X
X
-
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
*
AS-241575W-FR
7405 15 (75 on Axis) X
X
X
-
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AS-121575W-FR
7410 15 (75 on Axis) X
X
-
X
X
-
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AS-24MCC-FR
3161 15/30/75/95
X
X
X
-
-
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
*
AS-24MCC-FW
3162 15/30/75/95
X
X
X
-
-
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
*
AS-24MCCH-FW
3467
115/177
X
X
X
-
-
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
*
ASWP-2475W-FR** 9012 75 @ -31°F
X
X
X
-
X
-
I (see Data Sheet S9004) X
X
X
X X
AH-24-R
7892
-
X
X
X
-
X
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AH-24-W
7893
-
X
X
X
-
X
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AH-12-R
7891
-
X
X
-
X
X
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AH-12-W
7894
-
X
X
-
X
X
X
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X X
AH-24WP-R**
7416
-
X
X
X
-
X
X
K
X
X
X
X
AH-12WP-R**
7415
-
X
X
-
X
X
X
K
X
X
X
X
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in
accordance with Wheelock Inc. standard terms and conditions.
Specifications and Ordering Information
*PENDING
F
A
C
P
DSM #3
Audible NAC Cir
.
Strobe NAC Cir.
DSM #2
DSM #1
Strobe NAC Cir.
Strobe NAC Cir.
Audible NAC Cir
.
Audible NAC Cir
.
AS
AS
AS
AS
AS
AS
Sync
Sync
Sync
+
-+
+-
-
DSM Interconnecting wiring shown. Maximum of
twenty (20)
SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM
MODULES