S0600 43T 06/06
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accor-
dance with Wheelock Inc. standard terms and conditions.
Wiring
(All Bell Models)
The alarm signals shall be Wheelock Series 43T Bells or approved equal. They shall be UL Listed for Fire Protective
Service with models for vibrating operation and optional steel shells from 6” to 10” diameter. Sound output at 10 feet
shall range up to 88 dBA. The bells shall semi-flush mount to standard 4” square backboxes or surface mount to
Wheelock indoor BB backbox or outdoor WBB backbox. All bell models shall be polarized for line supervision and
shall have screw terminals for in-out field wiring. The finish on all models shall be textured enamel.
Architects and Engineers Specifications
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and
operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance
with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed
by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories
(UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other
applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the
requirements of the local authority having jurisdiction (AHJ).
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE US-
ING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARN-
INGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.