CAUTION:  

Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE 

SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR 
WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY 
FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING FUSE 
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT 
IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

 

WIRING AND MOUNTING INFORMATION:

 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If these 

limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 

CAUTION:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 

multiconductor cable or 3/4" conduit fittings are used. 
 
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Wheelock recommends use of the largest backbox 
option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the 
product from wiring. 

 

FLUSH MOUNTING

A

STD. SINGLE-GANG

BACKBOX 2" DEEP

#6-32 SCREWS

STROBE MOUNTING

PLATE (SMP)

              COVER 

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

FLUSH OR SURFACE MOUNT

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

B

STROBE

MOUNTING PLATE

#8-32 SCREWS

ROUND 

COVER 

4"SQ. X 1-1/2" DEEP BACKBOX

OR 100M X 37.5MM

EUROPEAN BACKBOX

 

FLUSH OR SURFACE MOUNT

C

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

DOUBLE-GANG X 2-1/4"

DEEP BACKBOX

#6-32 SCREWS

STROBE MOUNTING

PLATE (SMP)

             COVER 

#8-32 SCREWS

D

SURFACE MOUNTING

SHALLOW SURFACE

BACKBOX (SHBB)

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

STROBE MOUNTING

PLATE (SMP)

             COVER 

 

 

NOTE

:  All Mounting Options are available with the Round Cover as shown in Mounting Option B. 

 

Figure 1:  Wiring Diagram 

 

OR END OF LINE

FROM PRECEDING
APPLIANCE, FACP

TO NEXT SIGNAL

+

-

STROBES

RESISTOR (EOLR)

OR SYNC MODULE

 

 

Figure 2: 

• 

All Strobe Appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge 
(AWG) wires at each screw terminal.  Strip leads 3/8 inches and connect to screw terminals.   

• 

Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in 
Figure 2.  The polarity shown in the wiring diagrams is for the operation of the appliances.  The polarity 
is reversed by the FACP during supervision.

 

P84442 

Sheet 2 of 4 

J

 

Содержание RSS-24MCCH

Страница 1: ...Strobe Candela cd Mounting Options RSS 24MCCH 24 16 0 33 0 115 177 A B C D RSS 24MCCHR 24 16 0 33 0 115 177 A B C D NOTES 1 Strobes will produce 1 flash per second over the Regulated Voltage range 2 Clear and amber strobes meet the required light distribution patterns defined in UL 1971 3 All models are listed by UL for indoor use with a temperature range of 32 F to 120 F 0 C to 49 C and maximum h...

Страница 2: ... of the largest backbox option shown and the use of approved stranded field wires whenever possible to provide additional wiring room for easy installation and minimum stress on the product from wiring FLUSH MOUNTING A STD SINGLE GANG BACKBOX 2 DEEP 6 32 SCREWS STROBE MOUNTING PLATE SMP COVER MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 4 4 4 4 FLUSH OR SURFACE MOUNT MAXIMUM NUMBER OF ...

Страница 3: ...SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG CANDELA WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS Figure 5 Cover Removal 1 Hold flat screwdriver near the...

Страница 4: ...or a period of three years from date of manufacture as determined by date code Correction of defects by Cooper Wheelock Inc providing repairs or a replacement shall be at Cooper Wheelock Inc s sole discretion and shall constitute fulfillment of all warranty obligations The foregoing limited warranty shall immediately terminate in the event any part not furnished by Cooper Wheelock Inc is installed...

Отзывы: