background image

 STD 

77 

81 

84 

86 

88 

89 

 
 

ULC Directional Characteristics: 

At a voltage range of 20.0-31.0VDC. 

-3 dBA:  48 degrees left, 41 degrees right   

-6 dBA:  50 degrees left, 58 degrees right. 

 

CAUTION: 

 If these appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that exceeds the maximum 120dBA 

permitted by ADA and OSHA rules.  Exposure to such sound levels can result in damage to a person's hearing.

 

 

WARNING:  THE MULTITONE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM 

TONE BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR POSITION 
SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY 
DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

LIGHT DISTRIBUTION: 

Table 4:  Candela at Various Angles Per UL 1638 

Model Rated 

Candela 

 

 

 

 

 

 

 

UL 

ULC 

 

A1 

A2 

A3 

  A4 

  A5 

A6/A7 

MTWP-2475W 

75.0cd 

180.0cd 

    180 

16 

   16 

  15 

  15 

MTWP-2475C 

75.0cd 

    180 

16 

   16 

  15 

  15 

A7

A4

A6

A1

A5

A3

A2

 

 

CANDELA SELECTION:

 

Figure 1:  Showing Location of Candela Selector and Jumper Plugs 

177

 CANDELA

 POINTER

BOTTOM VIEW

115

               

135

185

 CANDELA

 POINTER

BOTTOM VIEW

               

R

+   STR   -

J3

+   AUD   -

TB 1

3

J2

C

O

E

D

J1

H

L

M

B

P83511  ( )

AH

C1

R5

TOP

CANDELA SELECTOR

3

J2

C

O

E

D

J1

H

L

M

 

NOTE: 

The MT Multi High-Candela Ceiling comes preset at 177cd.  The MT Multi-High-Candela Wall comes preset at 185cd. 

Factory setting is on Medium dB and Code 3. 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  WHEN CHANGING 

THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING THE CANDELA SETTING, THE 
APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION 
AT THE WRONG CANDELA, WHICH COULD RESULT IN A CURRENT DRAW EXCEEDING THE POWER SUPPLY’S CAPACITY. 

MULTITONE SETTINGS: 

 

The Switch (SW1) of the Multitone Appliance, shown in Figure 2, is used to set the dBA sound output level and alarm tone.  The factory settings are shown below.  
Read these instructions carefully before changing any of these factory settings. 
 

Figure 2: 

PC Board Layout Showing Location Switch (SW1) 

1 2

3

4

SW1

4

3

2

1

SW1

+ STB -

-

AUD

+

SLIDE HERE FOR (0)

SLIDE HERE FOR (1)

ON

ON

 

                      The factory settings for 24VDC models are:   HIGH  dBA   

 

SW1  POS 1 set on 1   

                                                                                              HORN TONE   

SW1  POS  2, 3, 4 set on 1, 1, 1 

 

STEP 1: 

Set desired dBA sound output level as follows (Refer to Figure 3).  Multitone Strobe Appliances cannot be field set for input voltage.  Multitone Strobe Appliances are 
field set for dBA sound output level by adjusting a four position Switch (SW1) as shown in Table 5 and Figure 2.  Use SW1 Position 1 to select the dBA sound output 
level. 

 

Table 5: dBA Sound Output Level Settings 

Input Voltage and Decibel Level 

SW1 Settings 

24 VDC/HIGH dBA: 

Set SW1  POS 1 on 1 (Factory Setting) 

24 VDC/STD dBA: 

Set SW1  POS 1 on 0 

P84870E 

Sheet 3 of 6

 