STD
77
81
84
86
88
89
ULC Directional Characteristics:
At a voltage range of 20.0-31.0VDC.
-3 dBA: 48 degrees left, 41 degrees right
-6 dBA: 50 degrees left, 58 degrees right.
CAUTION:
If these appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that exceeds the maximum 120dBA
permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person's hearing.
WARNING: THE MULTITONE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM
TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR POSITION
SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY
DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
LIGHT DISTRIBUTION:
Table 4: Candela at Various Angles Per UL 1638
Model Rated
Candela
UL
ULC
A1
A2
A3
A4
A5
A6/A7
MTWP-2475W
75.0cd
180.0cd
180
16
16
15
15
8
MTWP-2475C
75.0cd
~
180
16
16
15
15
8
A7
A4
A6
A1
A5
A3
A2
CANDELA SELECTION:
Figure 1: Showing Location of Candela Selector and Jumper Plugs
177
CANDELA
POINTER
BOTTOM VIEW
115
135
185
CANDELA
POINTER
BOTTOM VIEW
R
+ STR -
J3
+ AUD -
TB 1
3
J2
C
O
E
D
J1
H
L
M
B
P83511 ( )
AH
C1
R5
TOP
CANDELA SELECTOR
3
J2
C
O
E
D
J1
H
L
M
NOTE:
The MT Multi High-Candela Ceiling comes preset at 177cd. The MT Multi-High-Candela Wall comes preset at 185cd.
Factory setting is on Medium dB and Code 3.
WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION. WHEN CHANGING
THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING THE CANDELA SETTING, THE
APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION. IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION
AT THE WRONG CANDELA, WHICH COULD RESULT IN A CURRENT DRAW EXCEEDING THE POWER SUPPLY’S CAPACITY.
MULTITONE SETTINGS:
The Switch (SW1) of the Multitone Appliance, shown in Figure 2, is used to set the dBA sound output level and alarm tone. The factory settings are shown below.
Read these instructions carefully before changing any of these factory settings.
Figure 2:
PC Board Layout Showing Location Switch (SW1)
1 2
3
4
SW1
4
3
2
1
SW1
+ STB -
-
AUD
+
SLIDE HERE FOR (0)
SLIDE HERE FOR (1)
ON
ON
The factory settings for 24VDC models are: HIGH dBA
SW1 POS 1 set on 1
HORN TONE
SW1 POS 2, 3, 4 set on 1, 1, 1
STEP 1:
Set desired dBA sound output level as follows (Refer to Figure 3). Multitone Strobe Appliances cannot be field set for input voltage. Multitone Strobe Appliances are
field set for dBA sound output level by adjusting a four position Switch (SW1) as shown in Table 5 and Figure 2. Use SW1 Position 1 to select the dBA sound output
level.
Table 5: dBA Sound Output Level Settings
Input Voltage and Decibel Level
SW1 Settings
24 VDC/HIGH dBA:
Set SW1 POS 1 on 1 (Factory Setting)
24 VDC/STD dBA:
Set SW1 POS 1 on 0
P84870E