P82623 F
Sheet 3 of 6
STEP 1:
Set desired input voltage and dBA sound output level as follows (Refer to Figures 2 and 3):
AMT Multitone Appliances are field set for input voltage and dBA sound output level by inserting a Jumper Plug (DP1) and adjusting a four position
Switch (SW1) as shown in Table 4 and Figures 2 and 3. Use DP1 to select the desired voltage and SW1 Position 1 to select the dBA sound output level.
Table 4: Input Voltage and dBA Sound Output Level Settings
Input Voltage and Decibel Level
DP1 and SW1 Settings
24
VDC
/HIGH dBA:
Set DP1 on 24; set SW1 POS 1 on 1
(Factory Setting)
24
VDC
/
STD
dBA:
Set DP1 on 24; set SW1 POS 1 on 0
12
VDC
/HIGH dBA:
Set DP1 on 12; set SW1 POS 1 on 1
12
VDC
/
STD
dBA:
Set DP1 on 24; set SW1 POS 1 on 1
Figure 2:
Figure 3:
Jumper Plug (DP1) Settings
JUMPER PLUG
SHOWN SET ON 24
SHOWN SET ON 12
12
24
(Use Needle Nose Pliers to Lift and Properly Insert the Jumper Plug)
Switch (SW1) Settings
POS 1
POS 2
POS 3
POS 4
SLIDE HERE FOR (1)
SLIDE HERE FOR (0)
USE A SMALL SCREWDRIVER TO
CHANGE THE SWITCH POSITION.
WARNING: DO NOT APPLY 24VDC INPUT IF THE JUMPER PLUG (DP1) IS SET ON 12. THIS CAN DAMAGE THE UNIT. DOUBLE CHECK
THE JUMPER PLUG (DP1) AND SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT. IMPROPER SETTINGS CAN DAMAGE THE
UNIT OR RESULT IN NO SOUND OUTPUT OR A dBA SOUND OUTPUT LEVEL THAT IS BELOW THE MINIMUM CODE REQUIREMENTS FOR
PUBLIC MODE FIRE PROTECTION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
STEP 2:
Set desired alarm tone as follows (refer to Figure 3 and Table 5).
AMT Multitone Appliances are field set for any one of eight groups of self-prioritized tones by setting a four-position switch (SW1) as shown in Figure 3
and Table 4. Use SW1 POS 2, 3, 4 to select the desired alarm tone (refer to Table 5 below).
Table 5: Alarm Tones
Tones Switch
Settings
PRI 1
PRI 2
PRI 3
POS 2
POS 3
POS 4
Horn Bell Siren
1
1
1
Code 3 Horn
Siren
Vibrating Chime
1
0
1
Slow Whoop
March Time Horn
HI/LO
0
0
1
March Time Horn
HI/LO
Vibrating Chime
1
1
0
Code 3 Horn
Bell
Siren
0
1
1
Siren Horn Vibrating
Chime
0
1
0
Bell
March Time Horn
Siren
1
0
0
Code 3 Tone
HI/LO
Siren
0
0
0
NOTE:
The prioritized tones contained in each group is factory pre-set which can not be changed.
NOTE
The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency
evacuation signaling. They should be used only for fire evacuation signaling and not for any other purpose.
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate
independently. All other tones are recommended for use only on continuous (non-coded) systems.
WARNING: THE AMT APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT”.
WIRING DIAGRAMS: