background image

P82623 F 

Sheet 1 of 6 

 

 

 
 

273 Branchport Avenue 
Long Branch, NJ  07740   

 

 

 

(800) 

 

631-2148 

(USA) 

 

           

 

 

 

Thank you for using our products. 

(800)  397-5777 (CANADA) 
www.coopernotification.com   

 

 

 

 

 

 

       INSTALLATION INSTRUCTIONS 

AMT MULTITONE APPLIANCES 

AMT-12/24 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 
 

AMT Multitone Appliances are UL Listed under Standard 464 for Audible Signal Appliances for Fire Protective Service and for General Signaling Service. 
They are also ULC Listed under Standard CAN/ULC-S525-07 for Audible Signal Appliances for Fire Alarm Systems.  They are listed for both indoor and 
outdoor use with the backboxes specified in these instructions.  (See Mounting Options A,B,C,D,E,F,G).  Cooper Notification's AMT Appliances are 
unique multitone alarm appliances with separate input terminals for each sound.  They are the ideal choice for Halon Protection Systems and emergency 
signaling systems where distinctive multiple alarm conditions are required.  Eight groups of three self-prioritized sound outputs are provided with 
separate electrically isolated input terminals for each sound (see Table 2 and 5 for sound selections).  Sound output can be field set to provide either 
HIGH (HI) dBA or STANDARD (STD) dBA sound output level.  AMT Multitone Appliances can be field set for either 12VDC or 24VDC operation and are 
designed for use with either filtered or unfiltered Full-Wave-Rectified (FWF) input voltage.  All inputs are polarized for compatibility with standard reverse 
supervision of circuit wiring by Fire Alarm Control Panel (FACP). 
 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE TO COMPLY WITH ANY OF 

THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY 
OR DEATH TO YOU AND/OR OTHERS. 
 
NOTE: 

All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems, CAN/ULC-S524 and 

the Canadian Electrical Code, Part 1.  Final acceptance is subject to authorities having jurisdiction. 

 

WARNING:  THE AMT MULTITONE APPLIANCES MUST BE FIELD SET TO THE DESIRED INPUT VOLTAGE, dBA SOUND OUTPUT LEVEL 

AND ALARM TONE BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR 
POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE 
AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR 
OTHERS. 
 
SPECIFICATIONS:   
 

Table 1:  dBA Ratings for AMT Multitone Signal 

 Typical 

Anechoic 

 

 

dBA at 10 Feet per 

CAN/ULC S525-07 

Rated Reverberant dBA  

At 10 Feet Per UL 464 

Tone At 

Nominal 

At 

Minimum At 

Nominal 

 

Input Voltage 

Input Voltage 

Input Voltage 

 

HI STD  HI STD HI  STD 

Horn 

99 93  88 79 88  82 

Bell 

93 88  82 75 85  79 

March 

Time 

Horn 

98 92  85 79 88  82 

Code-3 Horn * (ANSI S3.41 Temporal Pattern) 

99 

93 

85 

75 

85 

79 

Code-3 Tone * (ANSI S3.41 Temporal Pattern) 

95 

89 

85 

79 

88 

82 

Slow 

Whoop 

99 94  82 75 85  79 

Siren 

97 92  82 75 82  75 

HI/LO 

93 85  82 75 85  79 

Vibrating 

Chimes 

89 83  79 73 82  75 

* - For ULC applications, only Code 3 Horn and Code 3 Tone are required to meet the ULC minimum of 85 dBA and the audible signal temporal  

pattern mandated by the National Building Code of Canada. 

 
 
 
 
Copyright 2015 Cooper Wheelock Inc., dba Cooper Notification.  All rights reserved. 

Содержание AMT-12/24

Страница 1: ...letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS NOTE All Canadian installations should b...

Страница 2: ...THE SYSTEM S PRIMARY AND SECONDARY POWER SOURCES NAC CIRCUITS OR WHEELOCK S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND...

Страница 3: ... SOUND OUTPUT LEVEL THAT IS BELOW THE MINIMUM CODE REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS STEP 2 Set desired alarm tone as follows refer to Figure 3 and Table 5 AMT Multitone Appliances are field set for any one of eight groups of self prioritized tones by setting a four position switch SW1 as shown in Fig...

Страница 4: ...room prior to installing backboxes and conduit 1 AMT Multitone Appliances can be flush mounted to a standard 4 inch square by 2 1 8 inch deep electrical box Figure A or a standard 2 gang by 2 1 2 inch minimum deep electrical box Figure B 2 Select largest backbox shown in Mounting Options where possible to provide additional wiring room for easy installation 3 Conduit entrance to backboxes should b...

Страница 5: ...G BOX 2 GANG x 2 1 2 DEEP BACKBOX AWG 18 AWG 16 AWG 14 AWG 12 10 8 8 4 MAXIMUM NUMBER OF CONDUCTORS 6 32 SCREWS SCREW COVERS C SURFACE INDOOR OUTDOOR 8 18 SCREWS INDOOR OUTDOOR WOOD SCREWS SCREW COVERS 12 12 12 12 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS BACKBOX IOB D CONCEALED CONDUIT MOUNTING EXISTING BOX 8 18 SCREWS INDOOR OUTDOOR SCREW COVERS 12 12 12 12 AWG 18 AWG 16 AWG 14 AW...

Страница 6: ...ision reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between the equipment and receiver 3 Connect the equipment into an outlet on a circuit different from that to which the receiver is connected and 4 Consul...

Отзывы: