Cooper Lighting WaveLinx WOLC Скачать руководство пользователя страница 2

Module Installation

Ensure power to the receptacle has been disconnected before beginning 

to remove/mount the receptacle.

1. Remove the shorting or open cap if supplied with the luminaire.

Note:  Receptacle caps, if supplied with the luminaire, are used for closing or opening the socket circuit. In addition,  

these caps can offer weatherproof protection for the receptacles that are not yet fitted with the WOLC Module.

WOLC Modules can be installed on luminaires that feature ANSI C136.41-

compliant receptacles.

3

2.  Place the WOLC Module firmly into the receptacle (not supplied by Cooper 

Lighting Solutions) and twist it clockwise (Install arrow) until it locks in place.

Overview

 

The Cooper Lighting Solutions WaveLinx Outdoor Lighting Control (WOLC) 

Module extends the WaveLinx System’s controls capability to a building’s 

surroundings or site such as parking lots and short pathways.
The WOLC Module is individually addressable and installs on top of a light pole 

via an ANSI136.41-compliant, 7-pin twist-lock connector. It can switch 

luminaires ON/OFF via an integrated high current relay, dim luminaires 

equipped with 0-10V dimming drivers or ballasts. It communicates with the 

WaveLinx Wireless Area Controller over an IEEE 802.15.4 network.

Important Safeguards

 

When using electrical equipment, basic safety precautions should always 

be followed including the following:

 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS. 

 

Do not let power supply cords touch hot surfaces.

 

Do not mount near gas or electric heaters. Equipment should be mounted in 

locations and at heights where it will not readily be subjected to tampering 

by unauthorized personnel.

 

The use of accessory equipment is not recommended by Cooper Lighting 

Solutions as it may cause an unsafe condition.

 

Do not use this equipment for other than the intended use.

SAVE THESE INSTRUCTIONS

Note

Tip

!

STOP

Note

Tip

!

STOP

Part Number

WOLC-7P-10A

2

Ratings

Voltage

 

Operating voltage: 120-347Vac; 

50/60 Hz

Load Rating

 

120-347Vac E-Ballast; 10A

 

120-347Vac Resistive; 10A

 

120-347Vac Tungsten; 10A

 

120-347Vac General Purpose; 10A

Interface

 

Dimming: 0-10V; 10mA  

(IEC 60929 Annex E)

Environmental

 

Ambient temperature range:  

-40°C to +65°C

 

Protection classification: IP66

 

Relative humidity: up to 95%  

non-condensing

Listings

 

UL: UL916/773  

(File # E222633 USA and Canada)

Communication

 

Wireless Protocol: IEEE 802.15.4

 

Radio Frequency: 2.4 GHz

 

Transmit Power: 20dBm

 

Distance: 150ft (45m) line of site  

between modules

Note

Tip

!

STOP

BLACK: Line In

RED: AC to Driver

GREY/-: Control to Driver   

VIOLET/ +: Control to Driver   

WHITE: Neutral

ORANGE: Unused

BROWN: Unused

3. Mount the control with the arrow and ‘N’ on the cover facing north.  

Note: The receptacle assembly may have to be rotated to face north.

Receptacle

Control Module Cap

     

  O

RG

 P

ow

er

    

  B

R

N

 In

pu

t

GR

Y(-

)/0

-1

0V

VI

O

(+

)/0

-1

0V

     

  O

RG

 P

ow

er

    

  B

R

N

 In

pu

t

GR

Y(-

)/0

-1

0V

VI

O

(+

)/0

-1

0V

Отзывы: