1. Mount Low-Voltage Power Module

Min. 3” 

(75mm)

Min. 36” 

(900mm)

Min. 18” 

(450mm)

 2. Provide Power

 

All new wiring must be fully verified before applying power. 

MAX Ampacity (Amps)

Normal  

Power Input

EM  

Power Input

Single Panel  

Input Only

120VAC 277VAC 120VAC 277VAC 120VAC 277VAC

LVPM-12-100-64-2E

9

4

1.8

0.8

10.8

4.8

 

        

 

 

 

Normal Power

input only

Normal Power

with Centralized EM

remove divider 

and wire internally

normal power

emergency power 

connection

normal power 

connection

normal power

transfer

switch

normal 

power

emergency

power

emergency

panel

 

 

 

 

3. Connect Fixtures

ALERT

7

8

9

10

11

12

1

2

3

4

5

6

TEST

RESET

UNPAIR

IDENTIFY

DIAG

STATUS

EMERGENCY

57VDC 

90W MAX

 

(EACH OUTPUT)

      CAUTION: DO  NOT OVERLOAD 

LOW VOLTAGE OUTPUTS

SUITABLE FOR CLASS 2 WIRING

LL5030

16EN

Connect 90W MAX per LV output

MAX light fixtures per power module = 36

Dip switches not used

Assure all are in OFF position

Low-voltage 

lighting cable

1

2

3

4

5

6

O

F

F

1200W Power Module

WaveLinx Low-Voltage