OPERATION
Step 1
Lamps or one lamp (bi-level unit) should come on with motion and stay on during a preset amount of time set by the installer.
Step 2
To test, depress test switch. One lamp should come on to simulate power failure.
Step 3
Release switch and lamp should extinguish.
TROUBLESHOOTING
This unit is equipped with a led indicators for diagnostics purposes.
The following diagram shows the failure indications:
Failure indicators on:
Solution:
1
.
Top Lamp Failure . . . . . . . . . . . . . . . . . . . . . . Replace top lamp
2
.
Bottom Lamp Failure . . . . . . . . . . . . . . . . . . . Replace bottom lamp
3
.
Sensor Failure . . . . . . . . . . . . . . . . . . . . . . . . Assure that the sensor board is
connected to the charger board.
Replace if connected.
There are two other LED indicators for reference:
4
.
Power Indicator . . . . . . . . . . . . . . . . . . . . . . . On when power is supplied
5
.
Motion Indicator . . . . . . . . . . . . . . . . . . . . . . . Blinks on/off with motion detection
COOPER LIGHTING
WHITE
(NEUTRAL)
BLACK
(120V)
ORANGE
(277V)
LAMP B
LAMP A
BALLAST A
BALLAST B
PCBA
TRANSFORMER
BATTERY
SWITCHED
SWITCHED
HOT
NEUTRAL
NEUTRAL
HOT
NEUTRAL WIRE (WHITE)
HOT WIRE (BLACK)
Wiring Diagram for Bi-Level Operation
20’
**
Mounting Height
7.5’
30°
**
Area of Sensor
Recognition
TEST
Sense
Ac
1
2
3
4
5
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269
4/07
11677542