Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
INSTALLATION INSTRUCTIONS
IMPORTANT
: READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN FOR FUTURE REFERENCE
CD61*/CD62*/CD6S*
Commercial Recessed CFL
Rough-In Installation Instructions
705300-Rev. INS
08/29/2012
page 3 of 4
PORTFOLIO
®
Note for Wall Wash Installations
Electrical Wiring Diagrams
CAUTION:
Make certain no bare wires are exposed outside of wire nut connectors.
Step 1.
Provide electrical service according to the
“National Electrical Code” or your local
electrical code to the junction box (located
on the plasterframe). Supply wire insulation
must be rated for at least 90 C. The junction
box is rated for a maximum of 8 No. 12 AWG
Branch Circuit conductors and is also suitable
for at least 90 C.
Step 2.
Remove junction box cover.
Step 3.
Remove appropriate round pryout and connect conduit to junction
box with proper connector (not included).
Step 4.
Connect supply lead wires to junction box lead wires (line, neutral
and ground) in the fixture using properly sized wire nuts.
Be careful not to leave any bare conductors outside of the
wire nut connectors.
Step 5.
Connect white to white, black to black, and green (from electrical service) on the supply side to the bare copper
wire in the junction box. Place all excess wiring and connections into the junction box and replace the cover.
BLACK LINE
WHITE NEUTRAL
GREEN/BARE COPPER
GROUND
Electrical Connection
Housing is to be installed with one of (2) sides (A,B) facing the wall.
A
B
BLACK
WHITE
RED
BLUE
BALLAST
RED
BLUE
YELLOW
YELLOW
HOT-BLACK
NEUTRAL-WHITE
RED
RED
BLUE
BLUE
BALLAST
1-LAMP
2-LAMPS