LED Floodlight

FMV Series LED Fixtures

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1622

APPLICATION

Champ

®

LED Floodlights are suitable for use in the following hazardous (classified) locations as

defined by the National Electrical Code (NEC

®

):

• Class I, Division 2, Groups A, B, C, D  

Refer to the floodlight nameplate for specific classification information, maximum ambient
temperature suitability and corresponding operating temperature (T-Number).    

Champ

®

LED Floodlights construction is designed for use indoors and outdoors in marine and wet

locations, where moisture, dirt, corrosion, vibration and rough usage may be present.  

WARNING

To avoid the risk of fire, explosion, or electric shock

, this product should be installed,

inspected, and maintained by a qualified electrician only, in accordance with all applicable
electrical codes.

WARNING

To avoid electric shock

:

Be certain electrical power is OFF before and during installation and maintenance.

Floodlight must be supplied by a wiring system suitable for Class I, Division 2 per NEC with
an equipment grounding conductor.

To avoid burning hands:

Make sure lens and lamp are cool when performing maintenance.

To avoid explosion: 

Make sure the supply voltage is the same as the floodlight voltage.

Do not install where the marked operating temperatures exceed the ignition temperature of the
hazardous atmosphere.

Do not operate in ambient temperatures above those indicated on the floodlight nameplate.

Use only replacement parts from Cooper Crouse-Hinds.

Use proper supply wiring as specified on the floodlight nameplate.

All gasket seals must be clean.

Before opening, electrical power to the floodlight must be turned off.  Keep tightly closed when
in operation.

IF 1622  •  04/11

Copyright © 2011, Cooper Industries, Inc.

Page 1

INSTALLATION

Mounting

WARNING

Yoke Mount - Wall Mount Using Floodlight Yoke Only

1.

Using floodlight yoke as a template, mark and drill desired location on mounting surface.

2.

Secure floodlight yoke to surface using ½" bolts or lag screws (not provided).

WIRING

Wiring the Floodlight

1.

All components in the fixture are prewired so only line in, neutral, and ground need to be
connected in the fixture to the lead wires (or terminals) per the wiring diagrams using
methods that comply with all applicable codes.  Terminate the equipment grounding
conductor (green) first, the common (white) next, and finally, the line voltage (black) last.
For DC voltage applications, connect the positive (+) lead to the white wire and the negative
(-) lead to the black wire.  Tighten all electrical connections.

Figure 1

LINE IN (BLK)

NEUTRAL (WHT)

V+ (RED)

V- (BLK)

INPUT

OUTPUT

DRIVER

INPUT

NEUTRAL (WHT)

LINE IN (BLK)

OUTPUT

V- (BLK)

V+ (RED)

DRIVER

INPUT

NEUTRAL (WHT)

LINE IN (BLK)

OUTPUT

V- (BLK)

V+ (RED)

DRIVER

INPUT

NEUTRAL (WHT)

LINE IN (BLK)

OUTPUT

V- (BLK)

V+ (RED)

DRIVER

LED SUBARRAY

LED SUBARRAY

LED SUBARRAY

LED SUBARRAY

LED ARRAY 

TRANSFORMER

347V OR 480V (BLU OR RED)

NEUTRAL (WHT)

LINE OUT (BLK)

NEUTRAL (WHT)

347V OR 480V 60HZ INPUT 

VMV11L 

137W VERSION (OTHER VERSION WIRING WILL VARY*)

LINE IN (BLK)

NEUTRAL (WHT)

INPUT

LINE IN (BLK)

NEUTRAL (WHT)

INPUT

LINE IN (BLK)

NEUTRAL (WHT)

INPUT

INPUT

NEUTRAL (WHT)

LINE IN (BLK)

100V TO 277V (BLK)

NEUTRAL (WHT)

100V TO 277V 50 OR 60HZ INPUT OR 108 TO 150VDC INPUT

VMV11L 

LED ARRAY 

V+ (RED)

V- (BLK)

OUTPUT

V+ (RED)

V- (BLK)

OUTPUT

V- (BLK)

DRIVER

DRIVER

LED SUBARRAY

LED SUBARRAY

V+ (RED)

OUTPUT

OUTPUT

V- (BLK)

V+ (RED)

DRIVER

DRIVER

LED SUBARRAY

LED SUBARRAY

*NOTES:

5L VERSION WILL HAVE TWO (2) DRIVERS AND FOUR (4) LED'S

7L VERSION WILL HAVE TWO (2) DRIVERS AND SIX (6) LED'S

9L VERSION WILL HAVE THREE (3) DRIVERS AND EIGHT (8) LED'S

 

 

FOR DC WIRING, ATTACH POSITIVE (+) LEAD TO LINE OUT (BLK) AND ATTACH NEGATIVE (-) LEAD TO 

NEUTRAL (WHT) WIRE

GROUND (GRN)

GROUND (GRN)

Figure 2 - Wiring Diagram

Champ

®

LED Floodlights are supplied for use with a choice of voltages:

• 100VAC - 277VAC, 50/60Hz, 108-150VDC
• 347VAC 60Hz
• 480VAC 60Hz

• NEMA 4X

• UL IP66