Change IP address via the Ethernet port

EG2 is supplied from the factory without DHCP enabled; therefore, it is necessary that the 

Ethernet port of the PC is set to the correct IP Address and Subnet Mask. For details of 

setting the IP address of your computer consult information on line. This will depend on your 

Operating System.

For example:

IP Address      192.168.0.99

• 

Subnet mask    255.255.255.0

• 

Gateway 

   192.168.0.1

• 

To connect the EG2 directly to the PC, it may be necessary to use a Crossover Cable, 

however, most modern computers are able to connect directly to another Ethernet device 

without a crossover cable.

The Ethernet port of your computer will need to configured to a compatible IP address.

Open iCANsoft. It will be required to set iCANsoft to communicate using the Ethernet Port.

This is done by selecting from the Tool bar Tools>Options>Network.

Select Ethernet Gateway and change the IP address to 192.168.0.100. Also ensure the ‘Use 

Password’ check box is ticked. The detault password is 

Cooper123 

(Case sentitive).

Select OK to confirm and set the 

address. 

iCANsoft can now be used to configure 

any items connected on the network. 

Set the IP address of the EG2 as 

described in section above for 

iCANsoft. The new IP address will 

become valid when the EG2 is reset 

or power to the device is removed and 

re-instated.

Reset to factory defaults

Factory defaults may be reset by the following procedure:

Remove power from the board.

Press the CAN ID button and reapply power. Keep the button pressed until the CAN LED 

flashes then stays on. At this point the Ethernet settings will have been restored to defaults.

After setting to factory defaults, the IP address of the device will revert to 192.168.0.100

Содержание EG2

Страница 1: ...EG2 Ethernet Gateway Installation guide ...

Страница 2: ...vant standards Introduction Welcome The Ethernet Gateway 2 provides connection between an iLight CAN network and an Ethernet LAN This allows a user to control and configure the iLight system using iCANsoft on a LAN network PC rather than by connecting directly into the network The EG2 also facilitates connection to the internet when installed behind a firewall This then enables remote connection f...

Страница 3: ... its sides to allow convection cooling and in no circumstances should these be blocked Ambient atmosphere requirements Temperature 2 C to 40 C 36 F to 104 F Humidity 5 to 95 non condensing IP Rating IP20 Dimensions Weight 159mm w x 90mm h x 58mm d 0 25Kg 0 55 lbs Mounting Always mount in well ventilated location Allow 50mm 2 above and below the unit if trunking with a depth greater than 50mm 2 is ...

Страница 4: ... and or received Red LED on indicates a CANbus error iCAN status Green flashing LED indicates normal operation Product Overview The label on the enclosure identifies the position of the status LEDS switches connectors iCANnet iLight network connection See P6 for wiring details TIMECLOCK N A Future use RESET Switch that resets the device Only press this on direct instruction from Cooper Controls to...

Страница 5: ...minal sizes iCANnet 5 x 1 5mm iCAN Network Connections A removable 5 way connector screw terminal plug is provided for the connection of iCAN network cables The recommended cable to use for iCANnet is CAT5 FTP V V Set Up Instructions iCANnet Connect the EG2 to the CAN network using the iCANnet connector If the EG2 is at the end of a network set the Term link to ON otherwise set to the OFF position...

Страница 6: ...akes approximately 60 seconds to be ready for use once power is applied Wait for the Green CAN LED to flash slowly The Green Power LED will double flash continuously while EG2 is on If Ethernet is connected the Link and Data LEDs will indicate successful connection Setting the IP address The factory set IP Address can be changed using the iCANnet connection or using a computer connected directly t...

Страница 7: ...set iCANsoft to communicate using the Ethernet Port This is done by selecting from the Tool bar Tools Options Network Select Ethernet Gateway and change the IP address to 192 168 0 100 Also ensure the Use Password check box is ticked The detault password is Cooper123 Case sentitive Select OK to confirm and set the address iCANsoft can now be used to configure any items connected on the network Set...

Страница 8: ...r any other liability in connection with any of its goods except in writing and signed by the Seller The Seller makes no representation that the goods comply with any present or future federal state or local regulation or ordinance Compliance is the Buyer s responsibility The use of the Seller s goods should be in accordance with the provision of the National Electrical Code UL and or other indust...

Отзывы: