Bussmann

®

Bussmann

®

Power Module

Switch  

PS

All-In-One Module

Legend:

N.O.F.A.

– Normally Open Fire Alarm contacts supplied from the fire alarm system to initiate the shunt trip.

Shunt Trip 

– Solenoid for remote trip of switch, which is activated by the closing of the fire alarm contacts or key test switch.

Option R2 

– Fire Safety Interface Relay that is operated at 24VDC from fire alarm system. May require an additional power source to be needed.

CR 

– Control Relay used to isolate the N.O.F.A. contacts from the duty of the shunt trip.

FR 

– Fire Alarm Voltage Monitoring Relay used to monitor presence of voltage in switch from a remote location (i.e. Fire Alarm Control Panel).

PL 

– Pilot Light to visually indicate presence of voltage on outside of switch enclosure.

CPT 

– Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil.

SW Aux.

– Normally closed contact when switch is closed. Opens as power switch opens.

Key Test 

– Key-to-Test switch used to operate shunt trip from the outside of switch enclosure. Can be used for trouble-shooting and inspection.

Mechanically Interlocked Auxiliary Contact – Contact used to disconnect secondary source of power.

– Terminal Block Connection Point.

– Pre-wired Connection Points

Typical Control with Wiring Options for Fire Safety Interface (Option R2)

8-29-01

XXXXXX

Form No. PS 

Page 4 of 5

BIF Doc# 1145

Содержание Power Module PS

Страница 1: ... No 30 PS3 60 PS6 100 PS1 200 PS2 400 PS4 Optional Accessories1 Catalog Rating Number Option 1 Control Power Transformer 208V T20 CPT Std 100VA with PRI 240V T24 SEC Fuse 120V Secondary 480V T48 600V T60 Option 2 Fire Safety Interface 24 Vdc Coil R2 Relay 3PDT 10 amp 120V 120 Vac Coil R1 Option 3 Key to Test Switch 120V K Option 4 Pilot Light ON Red R Green G White W Option 5 Isolated Neutral Lug ...

Страница 2: ... 25 60 50 40 125 100 100 250 200 200 Column Sizing Guidelines A Maximum horsepower rating of switch with Class J fuses light duty inrush B Maximum horsepower rating of switch with Class J fuses medium duty inrush C Maximum horsepower rating of switch with Class J fuses heavy duty or typical elevator cross line start The above table can be used for estimating switch size for motor loads based upon ...

Страница 3: ...A contacts from the duty of the shunt trip FR Fire Alarm Voltage Monitoring Relay used to monitor presence of voltage in switch from a remote location i e Fire Alarm Control Panel PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure CPT Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil SW Aux Normally closed contact when s...

Страница 4: ...onitor presence of voltage in switch from a remote location i e Fire Alarm Control Panel PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure CPT Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil SW Aux Normally closed contact when switch is closed Opens as power switch opens Key Test Key to Test switch used to operate shu...

Страница 5: ...h with shunt trip capabilities The ampere rating of the switch shall be based upon elevator manufacturer requirements and utilize Class J Fuses provided separately It shall include as an accessory a 100VA control power transformer with primary and secondary fuses The primary voltage rating shall be ______ volts with a 120 volt secondary It shall also contain an isolation relay 3PDT 10 amp 120V The...

Отзывы: