All-In-One Module

Form No. PS

Page 1 of 5

BIF Doc# 1145

Bussmann

® 

Power Module™ Switch

Standard Features:

• 30-400 amp 600 Vac 3p Fused Power Switch
• 200,000 amp RMS Short-Circuit Current Rating
• Shunt trip 120V
• Control power terminal block
• Ground lug per NEC
• Class J fuse mounting only

1

Optional Features:

• Control power transformer with fuses and blocks
• Fire safety interface relay
• Key to test switch
• Pilot light – “ON”
• Isolated neutral lug

2

• Mechanically interlocked auxiliary contact for hydraulic

elevators with battery backup (5 amp 120 Vac rated)

• Fire Alarm Voltage Monitoring Relay (To monitor Shunt Trip   

Voltage)

• NEMA 3R, 4, and 12 enclosures available

3

• Phase failure and undervoltage relay available, consult 

factory

• For added protection, use the Bussmann SAMI fuse

covers to improve maintenance personnel protection

4

(OSHA 1910.333, paragraph C)

Agency Information:

U.L. 98 Enclosed and Dead Front Switch 

Guide 96NK3917, File E182262

NEMA 1, U.L. 50, listed enclosure
cU.L. per Canadian Standards C22.2, No. 0-M91-CAN/CSA

C22.2, No. 4-M89 Enclosed Switch

Power Module™ Switch

Rating (Amps)

Power Module Switch Catalog No.

30

PS3

60

PS6

100

PS1

200

PS2

400

PS4

Optional Accessories

1

Catalog 

Rating

Number

Option 1

Control Power Transformer 

208V

T20

(CPT) Std. 100VA with PRI & 

240V

T24

SEC Fuse (120V Secondary) 

480V

T48

600V

T60

Option 2

Fire Safety Interface

24 Vdc Coil

R2

Relay (3PDT, 10 amp, 120V)

120 Vac Coil

R1

Option 3

Key to Test Switch

120V

K

Option 4

Pilot Light – “ON”

Red

R

Green

G

White

W

Option 5

Isolated Neutral Lug

30-60A

N6

(Full Capacity)

2

100A

N1

200A

N2

400A

N4

Option 6

Mechanically interlocked auxiliary contact

1 NO & 1 NC

A

for hydraulic elevators with automatic 
recall (5 amp 120 Vac rated)

Option 7

Fire Alarm Voltage Monitoring Relay

Single-Pole

F1

(To monitor Shunt Trip Voltage)

Three-Pole

F3

Option 8

Optional Enclosure

NEMA 3R

U

NEMA 4

Y

NEMA 12

Z

Catalog No. Construction: 

Catalog number of PS Switch

Options as required in option order as listed above 
(i.e. option 1, 2, 3, etc.)

Example: • 100A S.T. Switch 480V-3P – PS1

• 480–120V CPT – T48
• 120 Vac Coil Fire Safety Interface Relay – R1
• Pilot Light - “ON” (Green) – G
• Mech. Interlock (1 NO & 1 NC) – A

Catalog Number PS1T48R1GA

1

Class J fuses not included.

2

Oversized 200% rated neutral option available where required by excessive 
non-linear loads.

3

Through 200A.

4

Through 100A.

5

Options 1,2,& 6 are standard for elevator circuits.

Bussmann

®

How to configure Part Numbers:

Step 1: Select Switch Amperage

1

Step 2: Select Options Needed

5

Содержание Power Module PS

Страница 1: ... No 30 PS3 60 PS6 100 PS1 200 PS2 400 PS4 Optional Accessories1 Catalog Rating Number Option 1 Control Power Transformer 208V T20 CPT Std 100VA with PRI 240V T24 SEC Fuse 120V Secondary 480V T48 600V T60 Option 2 Fire Safety Interface 24 Vdc Coil R2 Relay 3PDT 10 amp 120V 120 Vac Coil R1 Option 3 Key to Test Switch 120V K Option 4 Pilot Light ON Red R Green G White W Option 5 Isolated Neutral Lug ...

Страница 2: ... 25 60 50 40 125 100 100 250 200 200 Column Sizing Guidelines A Maximum horsepower rating of switch with Class J fuses light duty inrush B Maximum horsepower rating of switch with Class J fuses medium duty inrush C Maximum horsepower rating of switch with Class J fuses heavy duty or typical elevator cross line start The above table can be used for estimating switch size for motor loads based upon ...

Страница 3: ...A contacts from the duty of the shunt trip FR Fire Alarm Voltage Monitoring Relay used to monitor presence of voltage in switch from a remote location i e Fire Alarm Control Panel PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure CPT Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil SW Aux Normally closed contact when s...

Страница 4: ...onitor presence of voltage in switch from a remote location i e Fire Alarm Control Panel PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure CPT Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil SW Aux Normally closed contact when switch is closed Opens as power switch opens Key Test Key to Test switch used to operate shu...

Страница 5: ...h with shunt trip capabilities The ampere rating of the switch shall be based upon elevator manufacturer requirements and utilize Class J Fuses provided separately It shall include as an accessory a 100VA control power transformer with primary and secondary fuses The primary voltage rating shall be ______ volts with a 120 volt secondary It shall also contain an isolation relay 3PDT 10 amp 120V The...

Отзывы: