background image

INSTALLING THE OUTDOOR UNIT

INSTALLER

BLEEDING

INSTALLER

1

4

Do not install the outdoor unit in pits or air vents

Installing the pipes

Use suitable connecting pipes and equipment for 

the refrigerant R32.

Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches wor-

king in opposite directions.

Vacuum pump

Humid air left inside the refrigerant circuit can cause com-

pressor malfunction. After having connected the indoor

and outdoor units, bleed the air and humidity from the

refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3-

      way valves.

(2) Unscrew and remove the cap from the service valve.

(3) Connect the vacuum pump hose to the service valve.

(4) Operate the vacuum pump for 10-15 minutes until an

      absolute vacuum of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the 

      low-pressure knob on the vacuum pump coupling.

      Stop the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it

      after 10 seconds. Check all the joints for leaks using

      liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

      nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

Vacuum pump

Vacuum pump

Location

Twisting moment (N.m)

35-40
60-65
45-50
70-75

Φ12
Φ19

Diameter (mm) 

Φ9.52

Φ16

15-20

Φ6

18K unit need to be installed the indoor unit 

Caution: Installation Must be Performed in Accordance 

with the NEC/CEC by Authorized Personnel Only.

conversion joint

18K MODE:

INDOOR

UNIT

Connect to the

indoor unit

Refrigerant fluid di

rection of fiow

3-w

ay valve

2-w

ay valve

inlet

(2)Turn

(8) Secure

(7)Turn to open fully

(2)Turn

(8) Secure

(6) Open by 1/4 turn

(7)Turn to open fully

(2)Turn

(8) Secure

V

alve cap

Valve cap

Service

The refrigerant pipes must not exceed the maximum

Use bolts to secure the unit to a flat, solid floor.

When mounting the unit on a wall or the roof, make

sure the support is firmly secured so that it cannot

move in the event of intense vibrations or a strong

wind.

Install the drain fitting and the drain hose

(for model with heat pump only)

Condensation is produced and flows from the out-

door unit when the appliance is operating in the 

heating mode. In order not to disturb neighbours 

and to respect the environment,install a drain fitting 

and a drain hose to channel the condensate water.

Install the drain fitting and rubber washer on the 

outdoor unit chassis and connect a drain hose to it 

as shown in the figure.

Models(m)

18Kx2

14Kx2

28Kx4

Max. connection pipe length

20

70

Max. connection pipe length

(Simple one indoor unit)

10

20

10

20

21Kx3 24Kx3

60

20

60

20

The sum of the capacity codes of the indoor units should be 

among 50%-150% of that of the outdoor unit.

heights 5m(14K&18K)or 10m(21K&24Kx3&28K).

Содержание CHML-U14RK2

Страница 1: ...t Type Wall mounted Air Conditioner Thank you for choosing our product For proper operation please read and keep this manual carefully CHML U14RK2 CHML U18RK2 CHML U21RK3 CHML U24RK3 CHML U28RK4 CHML...

Страница 2: ...l characteristics technical data and accessories of this appliance may be changed without notice Children should be supervised to ensure that they do not play with the appliance This appliance is not...

Страница 3: ...d to indicate risk of property damage Indicates a hazard that would be assigned a signal word WARNING or CAUTION WARNING CAUTION DANGER NOTICE CONFORMITY AND RANGE GENERAL INFORMATION Please read this...

Страница 4: ...repair be necessary contact your nearest authorized Service Centre The appliance shall be stored in a room without continuously operating ignition electric heater Do not pierce or burn s instructions...

Страница 5: ...ectric shock Donot spray wateronindoorunit It may cause electric shock ormalfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoi...

Страница 6: ...Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner should be properly grounded Incorrect grounding may cause electric...

Страница 7: ...and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the ai...

Страница 8: ...turned on or off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air c...

Страница 9: ...Valve Warning Be sure to cut off the power supply before cleaning the air conditioner otherwise electric shock might happen Wetting of air conditioner may cause the risk of electric shock Make sure no...

Страница 10: ...ct has to be disposed at an authorized place for recycling of electrical and electronic appliances Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner O...

Страница 11: ...ical data Electricity supply Size and clearance TECHNICAL DATA GENERAL INFORMATION TECHNICAL DATA OUTDOOR UNIT WORKING TEMPERATURE RANGE GENERAL INFORMATION 9 Indoor side DB WB Outdoor side DB WB Maxi...

Страница 12: ...tion pipes and the connectiong wirings ofthe unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulati...

Страница 13: ...cable connecting cable To the power supply B brown black CHML U24RK3 An all pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring Wrong...

Страница 14: ...arance of the units that have been purchased Wrong wire connection may cause malfunction of some electric components After fixing cable ensure that leads between connection to fixed point have some sp...

Страница 15: ...handle at the right side plate of the outdoor unit one screw Note The above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units tha...

Страница 16: ...65 45 50 70 75 12 19 Diameter mm 9 52 16 15 20 6 18K unit need to be installed the indoor unit Caution Installation Must be Performed in Accordance with the NEC CEC by Authorized Personnel Only conve...

Страница 17: ...not use any other refrigerant than R32 MAINTENANCE INSTALLER INSTALLATION DIMENSION DIAGRAM INSTALLER 15 CHML U18RK2 CHML U21RK3 CHML U14RK2 30cm Space to the cover or above 30cm 50cm Air inlet side...

Страница 18: ...its Have the length of refrigerating pipe and refrigerant charge amount been recorded Has the unit been safely grounded Problems Owing to Improper Installation The unit may drop vibrate or make noises...

Страница 19: ...4 13 6 15 16 3 17 8 19 3 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 1 1 1 3 1 4 1 6 1 8 2 1 2 3 2 6 2 8 3 1 3 4 3 7 4 floor location wall mounted window mounted ceiling mounted Minimum room 2 ar...

Страница 20: ...66129929357...

Отзывы: