17 Wiring of the Signal Line of the Wired Controller
1) Open the cover of the electric box of the indoor unit.
2) Let the signal line go through the rubber ring.
3) Insert the signal line to the four-pin socket on the printed circuit board of the indoor unit.
4) Fix the signal line with the binding wire.
18 Electric Installation
Table 7
Indoor Unit
Power Cord
Running
Current
(A)
Input Power(W)
Recommended
Power Cord
(Sectional
Area× Pieces)
Type
Model
Indoor
Fan
Motor
Cooling
Heating
Cooling
and
Heating
CHML-ID09NK
220-240V~ 50Hz
0.406
75
575
1.0×4
CHML-ID12NK
220-240V~ 50Hz
0.348
65
865
1.0×4
CHML-ID18NK
220-240V~ 50Hz
0.428
80
1080
1.0×4
CHML-ID21NK
220-240V~ 50Hz
0.588
110
1610
1.0×4
CHML-ID24NK
220-240V~ 50Hz
0.588
110
1610
1.0×4
Notes
:
The sectional area listed above is applicable to the power cord with at most a length of 15 meters. For the
longer cord, its sectional area should be enlarged to avoid the cord burning out caused by the over-current.