Installation Manual

Installation Manual

Step 1: Fix the support of outdoor

Select it according to the actual installation situation

1. Select installation location according to the house structure.
2. Fix the support of outdoor unit on the selected location with expansion screws.
Note:
● Take sufficient protecttive measures when installing the outdoor unit
● Make sure the support can withstand at least four times of the unit weight.
● The outdoor unit should be installed at least 3cm above the the floor in orde

to install drain joint.

● For the unit with cooling capacity of 2300W~5000W, 6 expansion screws are

needed; for the unit with cooling capacity of 6000W~8000W, 8 expansion
screws are needed; for the unit with cooling capacity of 10000W~16000W,

10 expansion screws are needed.

Step 2:  Install drain joint

(Only for cooling and heating unit)

1. Connect the outdoor drain joint into the hole on the chassis, as shown in the

picture below.

2. Connect the drain hose into the drain vent.

Step 3:  Fix outdoor unit 

1. Place the outdoor unit on the support.

2. Fix the foot holes of outdoor unit with bolts.

drain joint

Step 4:  Connect indoor and outdoor pipe

union nut

pipe joint

1. Remove the screw on the right handle of outdoor unit and

then remove the handle.

2. Remove the screw cap of valve and aim the pipe joint

at the bell mouth of pipe.

3. Pretightening the union nut with hand.

4. Tighten the union nut with torque wrench by referring to

the sheet below.

liquid valve

gas valve

7.4  Installation Outdoor Unit

Step 5:  Connect indoor and outdoor pipe

1. Remove the wire clip; connect the power connection wire and signal control wire (only for cooling and heating unit) to the

wiring terminal according to the color,fix them with screws

2. Fix the power connection wire and signal control wire with wire clip (only for cooling and heating unit).

Note: 
● After tighten the screw,pull the power cord slightly to check if it is firm
● Never cut the power connection wire to prolong or shorten the distance.

Step 6:  Neaten the pipes

1. The pipes should be placed along the wall,bent reasonably and hidden
possibly. Min.semidiameter of bending the pipe is 10cm.

2. If the outdoor unit is higher than the wall hole, you must set a U-shaped curve
in the pipe before pipe goes into the room, in order  to prevent rain from getting 
into the room. 

Hex nut diameter

Tightening torque (N.m)

Ф 6

15~20

Ф 9.52

30~40

Ф 12

45~55

Ф 16

60~65

Ф 19

70~75

Note:

The through-wal height of drain hose shouldn't be higher than the outlet pipe hole of indoor unit.
The water outlet can't be placed in water in order to drain smoothly.

Содержание CH-S09FTXN-E2wf

Страница 1: ...MODELS CH S09FTXN E2wf CH S12FTXN E2wf CH S18FTXN E2wf CH S24FTXN E2wf SERVICE MANUAL Nordic EVO II Series Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunter com EN...

Страница 2: ...rol Operation 16 7 Installation Manual 18 7 1 Notices for Installation 18 7 2 Installation Dimension Diagram 20 7 3 Installation Indoor Unit 21 7 4 Installation Outdoor Unit 24 7 5 Check after install...

Страница 3: ...site after installation Make sure no foreign objects are left in the unit Always ensure effective grounding for the unit Incorrect handling could result inpersonal injury or death Incorrect handling...

Страница 4: ...ht kg 11 5 11 5 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model Compressor Trademark panasonic SANYO Compressor Model 5SS072ZJA21 C 1RZ110H1AE Compressor Oil FV50S or equivalent FV50BX Comp...

Страница 5: ...ked Layers 7 7 Net Weight kg 14 16 5 Gross Weight kg 17 20 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model Compressor Trademark SANYO SANYO Compressor Model C 6RZ146H1AG C 6RZ146H1AG Compre...

Страница 6: ...ng to Temperature 50 60 70 80 90 100 110 120 130 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Capacity ratio Outdoor temp C Capacity ratio Heating Cooling 20 15 10 5 0 5 10 110 120 130 100 90 80 70 60...

Страница 7: ...f 792 279 195 CH S12FTXN E2wf 792 279 195 CH S18FTXN E2wf 972 302 224 CH S24FTXN E2wf 1081 327 248 CH S09FTXN E2wf CH S12FTXN E2wf CH S18FTXN E2wf 3 2 Outdoor Unit Unit mm Model CH S09FTXN E2wf CH S12...

Страница 8: ...Compressor Refrigerant pipe diameter Liquid 1 4 6 mm Gas 3 8 9 52mm 9 12K 1 2 12mm 18K 5 8 16mm 24K 5 Schematic Diagram 5 1 Electrical Wiring Symbol OG WH YE RD YEGN BN BU BK VT Color symbol ORANGE W...

Страница 9: ...3 12 Function and Control Function and Control 6 Function and Control 6 1 Remote Control Operations Health button Wi button I feel button I feel Wi fi There is no this function for some remote control...

Страница 10: ...rom the aircon when press this button Default WIFI open on remote control WIFI button for air conditioner WIFI link Note Health button Note Note Note Note Turn on the back cover of the remote control...

Страница 11: ...will run in few minutes before turn off when turn off in heating or indoor temperature above environment temperature 3 Sensor malfunction If the environment sensor or pipe sensor AD is above or equal...

Страница 12: ...4 Select a location which is out of reach for children 5 The location should be ableto withstand the weight of indoor unit and won t increase noise and vibration 6 The appliance must be installed 2 5m...

Страница 13: ...f the plastic expansion particle is loose please drill another fixing hole nearb Step 3 Open piping hole 1 Choose the position of piping hole according to the direction of outlet pipe The position of...

Страница 14: ...e clip 4 Put wiring cover back and then tighten the screw 5 Close the panel Note All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire...

Страница 15: ...ew on the right handle of outdoor unit and then remove the handle 2 Remove the screw cap of valve and aim the pipe joint at the bell mouth of pipe 3 Pretightening the union nut with hand 4 Tighten the...

Страница 16: ...wing requirement after finishing installation Items to be checked Possible malfunction Has the unit been installed firmly The unit may drop shake or emit noise Have you done the refrigerant leakage te...

Страница 17: ...to the diameter of liquid pipe See the following sheet Additional refrigerant charging amount for R22 R407C R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe mm Gas pipe mm...

Страница 18: ...01 1 15 fan motor clamp board S22020002 S22020002 1 16 fan motor S16800001 S16800001 1 17 fan motor clamp board S22020001 S22020001 1 18 drain pipe S1301000101 S1301000101 1 19 step motor S17000001 S1...

Страница 19: ...10620007 1 16 fan motor clamp board S22020004 1 17 fan motor S16800003 1 18 fan motor clamp board S22020007 1 19 connction pipe pressed plate S22020005 1 20 motor stand S22020006 1 21 drain pipe S1301...

Страница 20: ...ame S10620017 1 16 fan motor clamp board S22020008 1 17 fan motor S16800008 1 18 connction pipe pressed plate S22020005 1 19 drain pipe S1301000104 1 20 step motor S17000003 1 21 crank S61200002 1 22...

Страница 21: ...9 S12620010 1 16 discharge pipe S12610015 S12610014 1 17 noise absorption sponge inside S61410020 1 18 noise absorption sponge outside S61410019 S61410024 1 19 big handle apricot grey S22210001 S22210...

Страница 22: ...S3380000209 1 17 right side panel apricot grey S10600004P S10600004P 1 18 big handle apricot grey S22210002 S22210002 1 19 valve cover S21420007 S21420007 1 20 valve support subassembly apricot grey...

Страница 23: ...s below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process...

Страница 24: ...cause of poor radiating 1 Check the voltage of power supply 2 Check the system see the process below see the process below 1 the wiring terminal between the mainboard and wifi module loosened or poorl...

Страница 25: ...45 44 Troubleshooting Troubleshooting...

Страница 26: ...2 11 1 Cold pasma zero wire connector 2 Power supply zero wire connector 3 PG fan contral connector 4 Cold pasma fire wire connector 5 PG fan feedback connector 6 Auto key 7 Vertical swing connector 8...

Страница 27: ...del Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboard with the same model End Yes Yes Yes Yes Yes No No No No No 2 IDU A...

Страница 28: ...nated Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Is the motor started up No Replace PG motor Replace the mainboard with the same model End Reinstall the blade and mo...

Страница 29: ...inal between temperature sensor and controller is loosened or poorly contacted yes yes yes yes Insert the temperature sensor tightly no no no no Eliminate the malfunction Check whether the temperature...

Страница 30: ...ording to the service manual Noted the detection method of the coil of the eletric expansion valve there is five pieces of the coil of the eletric expansion valve the resistance of one of them the lef...

Страница 31: ...expansion valve 6 Compressor start failure protection L1 Main checking points If the connection wire of the compressor is connected properly Flow chart If the stop duration of the compressor is suffic...

Страница 32: ...itable Flow chart 8 ODU Charging malfunction U1 Main checking points If the mainboard is broken If the wiring of the induction is connected well and if the induction is broken Flow chart Energize the...

Страница 33: ...it Refrigerant is leaking Discharged air temperature during cooling is higher than normal discharged wind temperature Discharged air temperature during heating is lower than normal discharged wind tem...

Страница 34: ...ormal phenomenon Abnormal sound will disappear after a few minutes When turn on or turn off the unit there s abnormal sound due to flow of refrigerant inside airconditioner Water running sound can be...

Страница 35: ...08 42 24 128 78 6 542 114 2 2409 29 853 66 7 113 37 43 23 186 79 6 3315 115 2 1816 28 799 98 8 107 96 44 22 286 80 6 1288 116 2 1242 27 750 18 9 102 85 45 21 425 81 5 9336 117 2 0686 26 703 92 10 98 0...

Страница 36: ...shaft on both sides of the panel to make it separate from the groove Remove the panel 3 Remove guide louver Remove axial sleeve of guide louver Procedure Note 5 Remove the filter 4 Remove electric box...

Страница 37: ...at the joint of the evaporator and rear case B Adjust slightly the pipe on the evaporator to separate the pipe with the evaporator C Remove the evaporator to separate the evaporator with rear case ass...

Страница 38: ...3 Remove protective grille Remove the screws fixing protective grille and then remove the protective grille Procedure 4 Remove axial flow blad Remove the nut fixing the blade and then remove the axial...

Страница 39: ...iring terminals Then lift the electric box to remove it Right side plate Electric box assy Screw Left side plate Note Procedure 10 Remove motor and motor support Remove tapping screws fixing the motor...

Страница 40: ...valve assy When unsoldering the spot weld wrap the 4 way valve with wet cloth completely to avoid damaging the valve due to high temperature 4 way valve assy Isolation sheet Screw Note Procedure 14 Re...

Страница 41: ...co onstantly y w w wo o ork king g to o im m mpro o ov v ve th heir pro o od d du u ucts so o th he inf f fo o orm m matio on in th his m m manu ual is su u ub b bj jject to o ch hang ge w with h ho...

Отзывы: