background image

1

Installation Manual

Air to Water Heat Pumps

CH-HP08UIMPRM CH-HP12UIMPRM

CH-HP20UIMPRM

CH-HP24UIMPRM

www.cooperandhunter.com

Содержание CH-HP08UIMPRM

Страница 1: ...1 Installation Manual Air to Water Heat Pumps CH HP08UIMPRM CH HP12UIMPRM CH HP20UIMPRM CH HP24UIMPRM www cooperandhunter com...

Страница 2: ...aged as a result of improper installation debugging unnecessary maintenance which is not in line with this manual The unit must be installed by qualified personnel It is vital that the below instructi...

Страница 3: ...and power connection have good earthing otherwise may cause electrical shock Operation Meaning PROHIBITION DO NOT put fingers or others into the fans and evaporator of the unit otherwise harm may occ...

Страница 4: ...he heat pump as it may cause fire 3 Features With new technology of DC Inverter EVI Series can be used in extremely cold area for heating cooling hot water The Series is featured as follows 3 1 DC Inv...

Страница 5: ...has many powerful functions such as water temperature curve easy timing one key mute and mute timer 3 7 APP IOT Simplify your life with WarmLink Via connection by Wi Fi or 4G you can take full contro...

Страница 6: ...Dimension mm 4 1 Models CH HP08UIMPRM 4 2 Models CH HP12UIMPRM 490 442 1002 750 915 805 65 155 332 392 Power Line SignaI Iine Water Outlet 1 Water Inlet 1 Power Line SignaI Iine Water Inlet 1 Water O...

Страница 7: ...6 4 3 Models CH HP20UIMPRM 4 4 Models CH HP24UIMPRM 997 650 437 395 1315 288 75 1605 Water Inlet 1 1 4 Water Outlet 1 1 4 SignaI Iine Power Line...

Страница 8: ...Pprovides the monoblock heat pump without circulation pump and the Hydronic box Hydronic box includes one small size built in buffer tank one main circulation water pump one space heating cooling cir...

Страница 9: ...ion 6 1 Packing List Heat Pump Unit 1 Display Mounting Plate 1 Rubber Feet 4 Drain Connection 1 Display Connecting Wire 1 Thermistor 1 optional accessory 6 2 Installation Site Requirement Unit mm 500...

Страница 10: ...A P17T P24T L 750 953 997 1172 H 805 915 1315 1605 W 442 423 395 397 A 750 700 650 725 B 473 443 400 415 A 1002 700 650 725 B P1 200 200 200 200 P2 150 150 150 150 P3 B 100 B 100 B 100 B 100 60 M10 4...

Страница 11: ...ess than 0 1 sec n 0 5mm 2 10 16A 3 2 5 mm 2 2 5mm 2 32A 30mA less than 0 1 sec 16 25A 3 4 mm 2 4mm 2 40A 30mA less than 0 1 sec 25 32A 3 6 mm 2 6mm 2 40A 30mA less than 0 1 sec 32 40A 3 10 mm 2 10mm...

Страница 12: ...nce 7 1 Precautions for Daily Use Before starting up the unit for the first time or after a long time shutdown the following preparations must be made 1 Thoroughly inspect and clean up the unit 2 Clea...

Страница 13: ...nd hot water with a cleaning agent Do not use abrasive cleaners Do not use solvents Do not use any cleaning agents that contain chlorine or ammonia 7 3 3 Checking the evaporator fan and condensate dis...

Страница 14: ...50 7 20 12 5 Max Current Input A 13 0 21 5 12 0 20 3 12 0 20 3 Water Flow m3 h 1 1 7 2 9 4 2 2 9 4 2 Refrigerant Proper Input kg R32 1 3kg R32 1 7kg R32 2 0kg R32 3 4kg R32 2 0kg R32 3 4kg CO2 Equival...

Страница 15: ...14 9 Wiring Diagram CH HP08UI MPRK CH HP12UIMPRM...

Страница 16: ...15 CH HP24UIMPRM CH HP20UIMPRM CH HP24UIMPRM...

Страница 17: ...rameter temperature curve timer setting and mute setting Fault This icon will flash when there is an error showing up The display will enter fault record interface after tapping this icon Defrosting T...

Страница 18: ...icon then the display will switch to this mode s interface 4 tapping hot water heating mode icon then the display will go into the hot water heating mode s interface 5 tapping hot water cooling mode...

Страница 19: ...be unlocked 10 7 Timer Setting Click the timer setting key to enter the timer setting the interface display is as follows Key No Key name Key color Key function Return key Click this key to return to...

Страница 20: ...ute function mode Curve key Click this key to view the temperature curve Note If the unit has or both functions the corresponding icon will be displayed on the setting interface In the setup interface...

Страница 21: ...ace display is shown as follows Note When the unit is enabled to activate the mute function the icon is displayed as When the unit is enabled to activate the powerful function the icon is displayed as...

Страница 22: ...The value of the abscissa indicates the time from the point on the curve to the current time point The leftmost point on the first page 0 on the abscissa is the latest temperature record e Temperature...

Страница 23: ...nction during the production then the unit parameter reset can be reset the parameter to the factory setting 2 After pushing the Reset button it will have below interface to choose the Yes or No to co...

Страница 24: ...The failure record interface will have the failure code and failure name as well as the failure time b If it needs to clear the failure record it needs to enter the password according to the display d...

Страница 25: ...emp Offset When the house heating needs more energy only during the low ambient temp then it should enlarge the Slope setting When the house heating needs more energy during the whole ambient temp ran...

Страница 26: ...the display whether shown locked icon Check the cable Reconnect the power cable and check if it works Heating effect is not good The compressor running low frequency The fan is not running or speed is...

Страница 27: ...the water temperature up to A04 11 o C or the ambient temp is higher than 1 the error code disappears E19 Primary Anti freezing Protection Ambient temp 0 2 water inlet 4 It is the protection in winte...

Страница 28: ...ace a new compressor driver board F06 DC Bus Undervoltage 1 Check the voltage between DCP IN and DCN IN if lower than 300V it will get this protection 2 Check the input voltage of R S T on compressor...

Страница 29: ...IGBT Power Device Overheat Alarm 1 Check the fans are running or not 2 Check the installation distance and space 3 If they are OK please replace a new compressor driver board 4 Leave enough distance a...

Страница 30: ...00 or higher than 500k please replace a new one P02 Water Outlet Temp Sensor Fault P04 Ambient Temp Sensor Fault P17 Water Outlet Temp Sensor Fault P032 Hot Water Tank Temp Sensor Fault P42 Room Temp...

Отзывы: