24
Mini Chiller
Service Manual
2 WATER PIPING WORK
2.1 Installation Procedure
For all guidelines, instructions and specifications regarding refrigerant pipework between the indoor unit and
the outdoor unit please refer to the outdoor unit installation manual.
The units are equipped with a water inlet and water outlet for connection to a water circuit, which must be
provided by a licensed technician and must comply with all relevant national regulations.
2.2 Matters of Attention
Air vents must be provided at all high points of the system. The vents should be located at points which are
easily accessible for servicing. An automatic air purge should be used. Check the valve is not tightened too
much so that automatic release of air in the water circuit remains possible.
2.3 Antifreeze
% by Weight
0
12
22
30
Freezing Point
℃
(
℉
)
0(32)
-5(23)
-10(14)
-15(5)
-20(-4)
-30(-22)
Ambient Temperature
℃
(
℉
)
8.3(47)
3.3(38)
-1.7(29)
-6.7(20)
-11.7(11)
-16.7(2)
Cooling Capacity Correction Factor
1.0
0.985
0.980
0.974
0.970
0.965
Water Flow Correction Factor
1.0
1.02
1.04
1.075
1.11
1.14
Pressure Drop Correction Factor
1.0
1.07
1.11
1.18
1.22
1.24
3 ELECTRIC WIRING WORK
3.1 Wiring Principle
POWER SUPPLY — The electrical characteristics of the available power supply must agree with the unit
nameplate rating. Supply voltage must be within the limits shown. See 3.3 for electrical and configuration data.
FIELD POWER CONNECTIONS — All power wiring must comply with applicable local and national codes.
Install field-supplied, branch circuit fused disconnect(s) of a type that can be locked off or open. Disconnect(s)
must be located within sight and readily accessible.
3.2 SPECIFICATION OF POWER CORD & AIR SWITCH
Model
Power Supply
(V,Ph,Hz)
Capability of Air
Switch (A)
Minimum Sectional Area
of Earth Wire (mm
2
)
Minimum Sectional Area
of Power Cord (mm
2
)
C
H-CH
8S
N
M
380~415,3,50
10
1.0
1.0
C
H-CH
10S
N
M
380~415,3,50
13
1.5
1.5
C
H-CH
12.5S
N
M
380-415,3,50
16
1.5
1.5
C
H-CH
15S
N
M
380-415,3,50
16
1.5
1.5
C
H-CH
22M
N
M
380-415,3,50
32
4
4
C
H-CH
25M
N
M
380-415,3,50
25
2.5
2.5
C
H-CH
35M
N
M
380-415,3,50
32
4
4
C
H-CH
45M
N
M
380-415,3,50
50
10
10
Содержание CH-CH10SNM
Страница 3: ...1 Mini Chiller Service Manual PRODUCT PRODUCT...
Страница 10: ...8 Mini Chiller Service Manual CONTROL CONTROL...
Страница 11: ...9 Mini Chiller Service Manual CONTROL UNITS CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Operation...
Страница 12: ...10 Mini Chiller Service Manual CONTROL 1 2 Heating Operation...
Страница 20: ...18 Mini Chiller Service Manual INSTALLATION...
Страница 25: ...23 Mini Chiller Service Manual Integral Type 1750 1290 foundation bolt 4 M12...
Страница 28: ...26 Mini Chiller Service Manual Model CH CH12 5SNM O Model CH CH15SNM O...
Страница 30: ...28 Mini Chiller Service Manual Model CH CH35MNM CH CH45MNM D419 D451 D420 D452 113 114 115 116...
Страница 31: ...29 Mini Chiller Service Manual MAINTENANCE...
Страница 33: ...31 Mini Chiller Service Manual 2 FLOW CHART OF TROUBLESHOOTING...
Страница 34: ...32 Mini Chiller Service Manual...
Страница 67: ......