OPTIONS
ELECTRIC HEATERS
The heater element is of the resistance open coil type. Thermal overheat cut-outs and fusible links are provided to shut-
off power to heaters in case of airflow failure. The heaters are available as an option and can be installed at the blower
outlet.
VALVE PACKAGES
A variety of valve packages, as a set are available as an option (3C & 3D for two pipe system and 4C & 4D for four pipe
systems). These valves are supplied loose for field installations.
THERMOSTAT
An attractive wall mount three speed thermostat with all required functions and features for safe and smooth operation
which can be used for cooling & heating. This thermostat can be supplied loose through separate Kit number.
TYPICAL THERMOSTAT
MODEL DECODING
3
1, 2 & 3
BASIC (SERIES)
4 & 5
SIZE
(x 100 CFM)
6
ELECTRICAL
SUPPLY (V-Ph-Hz)
13
OPTION
DWL
: COOLINE
CHILLED
WATER
FAN COIL
UNIT
02
03
04
06
08
10
12
14
16
18
20
B
: 220/240-1-50
N
: STANDARD
UNIT
12
FILTER
N
: NONE
A
: ALUMINUM
(1/2" THICK)
11
COIL
CONNECTION
R
: RH SIDE,
STANDARD
(FACING AIR
DIS-
CHARGE)
L
: LH SIDE,
OPTIONAL
(FACING AIR
DIS-
CHARGE)
10
FIN
A
: ALUMINUM
FIN
B
: COATED
ALUMINUM
FIN
C
: COPPER FIN
9
ACCESSORIES
N
: STANDARD
A
: 3C VALVE PACKAGE
(COOL ONLY)
B
: 3D VALVE PACKAGE
(COOL ONLY)
J
: 4C VALVE PACKAGE
(HEAT & COOL)
K
: 4D VALVE PACKAGE
(HEAT & COOL)
8
HEATER
N
: NO HEATER
D
: 2 kW
E
: 3 kW
G
: 5 kW
7
COIL
A
: 3 ROW CHILLED
WATER
J
: 3 ROW CHILLED
WATER + 1 ROW
HEAT
B
: 4 ROW CHILLED
WATER
K
: 4 ROW CHILLED
WATER + 1 ROW
HEAT
N
: NO HEATER
E
: 3 kW
G
: 5 kW
J
: 7 kW
M
: 10 kW