Page 5
Take care to ensure excess wiring is not trapped between the cases
half’s when closing
- push
excess wires into the wall cavity. Never press on the LCD when closing the SMT-131 as it may crack.
Always press on the SMT-131 plastic case only.
DIP Switch Settings
Switch
Function
On
Off
Sw1
Indoor Fan Mode
3 Fan Speed
1 Fan Speed
Sw2
Equipment Type
Heat Pump
Heat Cool
Sw3
HP Mode (Sw2= ON)
HC Mode (Sw2=OFF)
Rev Valve Heat (B)
HE
–
Fan With Heat
Rev Valve Cool (O)
HG
–
No Fan In Heat
Sw4
2 / 4 pipe mode
2 pipe mode
4 pipe Mode
Sw5
Comp Protection Delay
5 Min Anti Cycle
Immediate Comp start
Sw6
Klixon (Ricardo) Mode
On
Off
Sw7
Ventilation Mode
Permitted
Not Permitted
Sw8
Door Station (Optional)
Fitted
Door Station Not Used
Note: The SMT-131 reads the switch settings on power up only. If you change any DIP switch
settings you must power cycle before these changes will take effect.
It is expected that only qualified people will make adjustment to these dip switch settings.
Knowledge of the HVAC system under the control of the SMT-131 is essential prior to making
adjustment to these DIP switch settings.
Caution
Incorrect adjustment of these DIP switch settings could cause HVAC equipment
damage. This would NOT be covered by warranty.
Wiring
–
HVAC Control
Terminal Designations
Terminal
Function
C
24V Neutral
R
24V Active - This voltage is switched back through the relays
Hi
Indoor Fan High Speed (
NOT
Used
in Single fan speed mode - Sw 1 = OFF)
Med
Indoor Fan Medium Speed (
NOT Used
in Single fan speed mode - Sw 1 = OFF)
Low
Indoor Fan Low Speed (Used in single & three fan speed mode)
Y
Compressor or Cool - (Based on Sw 2 setting)
W - O/B
Reversing Valve or Heat - (Based on Sw 2 setting)
A1
–
Cool
0-10V Output for Cooling (Typically used to control modulating valves)
A2
–
Heat
0-10V Output for Heating (Typically used to control modulating valves)
A3
–
Fan
0-10V Modulating Output for Indoor DC Fan
Com
–
0V
0V terminal - Used for 0-10V, sensor or digital inputs ground reference
A
Modbus Data A
B
Modbus Data B
SI
Remote temperature sensor input (Remote / average / Modbus data use)
DI
Digital (Switched input) for forced un-occupied or initiate doorbell function
WC
Window Contact - Forces SMT-131 OFF if window open > 5 min (Adjustable)
DS
Door Switch
–
Monitors room door status for occupancy detection
(see page 11)
PIR
PIR (Movement sensor) input for occupancy detection (see page 11)